Installation Guide
IN-IC1-15
Title
:
Jace to i-Controller REV.200 MPU (575V 40–70 Ton) Conversion
Flō
Tech Support 888-598-1198
6
4-6DEC2021
Figure 5.3. 501-1125 Temp Sensor Mounting Position In RH
IMPORTANT:
If you have a 203-5752, move the jumper on
JP3 from 10V to 5V on the combo sensor.
NOTE:
Do not wire the combo sensor to the i-Controller or
Expansion Module at this time.
7.
Install The i-Controller Components
7.1
Remove Existing Jenesys Controls
Locate the Jenesys controls. Remove all Jenesys controls
from the din rail.
NOTE:
If the Jenesys inputs and outputs are not labeled,
label these wires before proceeding.
7.2
Install New i-Controller and Expansions
Mount the i-Controller and expansion modules on DIN
rails.
Double-check that the Expansion Modules are addressed
as 1 &2. Verify the addressing and adjust as necessary on
the dip switches (location called out in
Figure 6
. This figure
is an example of expansion A setup).
Expansion A
–
1 up, 2 down, 3 down, 4 down
Expansion B
–
1 down, 2 up, 3 down, 4 down
NOTE: The actual switch may be white but for illustrative
purposes, the switch is black in the
Figure 6
below.
Figure 6.
Flō
i-Controller Expansion Addressing
Wire the 2 expansion modules to the main i-Controller via
the
CAN Bus
port in a daisy change based on the following:
•
Expansion Module (B) 30 (+)
→
Expansion Module (A) 30 (+)
→
i-Controller 100 (+)
•
Expansion Module (B) 32 (-)
→
Expansion Module (A) 32 (-)
→
i-Controller 101 (-)
•
Expansion Module (B) 33 (gnd)
→
Expansion Module (A) 33
(gnd)
→
i-Controller 102 (gnd)
7.3
Install Visograph
Mount the Visograph and connect it to the i-Controller
port.
Wire the Visograph based on the following:
•
White wire VNR (Visograph)
→
103 (i-Controller)
•
Red wire + (Visograph)
→
104 (i-Controller)
•
Black wire
–
(Visograph)
→
105 (i-Controller)
7.4
Connect the i-Controller to Power
Connect transformer 1’s low voltage common to black 10”
wire from i-Controller pin 1.
Connect transformer 1’s low voltage 24V to red 10” wire
from i-Controller pin 9.
7.5
Connect the Expansion Modules to Power
Connect transformer 2’s low voltage common to black 10”
wire from all three expansion modules pin 1.
Connect transformer 2’s low voltage 24V to red 10” wire
from all three expansion modules pin 9.