Installation Guide
IN-IC1-15
Title
:
Jace to i-Controller REV.200 MPU (575V 40–70 Ton) Conversion
Flō
Tech Support 888-598-1198
11
4-6DEC2021
9.5
Dehumidification Test Mode
From the Main Menu, press and hold down
T7,
while holding
T7
down,
depress
T1
(
Field Technician
Options)
.
From the Field Technician Options screen, press
T2
(
Test
Modes
). Press
T3
(
2. Operational Tests
).
Use
to navigate to the
Dehumidification
Test Mode Off
and press
ENTER
.
When the "OFF" value begins blinking, press the
to
change the value to "ON", then press
ENTER
.
Wait for
10-minutes
, then terminate Dehumidification.
Terminate Dehumidification Test Mode (
OFF
)
From the Field Technician Options screen, press
T2
(
Test
Modes
). Press
T3
(
2. Operational Tests
).
Use
to navigate to the
Dehumidification
Test Mode
“
ON
”, then press
ENTER
.
When the "
ON
" value begins blinking, press
to
change the value to "
OFF
", then press
ENTER
.
Dehumidification mode is now turned “
OFF
”.
9.6
Heating Test Mode
From the Field Technician Options screen, press
T2
(
Test
Modes
). Press
T3
(
2. Operational Tests
).
Use
to navigate to the
Heat Test Mode Off
and press
ENTER
.
When the "OFF" value begins blinking, press the
to
change the value to "ON" and press
ENTER
.
Wait for
10-minutes
, then terminate Heating.
Terminate
Heating
Mode (
OFF
)
From the Field Technician Options screen, press
T2
(
Test
Modes
). Press
T3
(
2. Operational Tests
).
Use
and
to navigate to the
Heating Test
Mode On
and press
ENTER
.
When the "
ON
" value begins blinking, press the
change the value to "
OFF
", then press
ENTER
.
Heating mode is now turned “
OFF
”.
(A)
(B)
(C)
(D)
(E)
(F)
(G)
(H)
(I)
MODES OF
OPERATION
SUPPLY
FAN
COMP(S)
COND
FAN(S)
RECLAIM
HEATING
OUTDOOR
AIR
DAMPER
RETURN
AIR
DAMPER
BYPASS
AIR
DAMPER
INDICATE
PASS
or
FAIL
DEHUM
ON
ON
ON
N/A
OFF
OPEN
*
OPEN
**
OPEN
HEATING
ON
OFF
OFF
N/A
ON
OPEN
*
OPEN
OPEN
**
* Damper will be in the OPEN position (
typically 20 - 30%
- OPEN
0.5” –
1.50”
).
** This damper will be OPEN to its minimum position.
Table 6: Test mode unit status