Installation Guide

 

IN-IC1-15

 

Title

:

 

Jace to i-Controller REV.200 MPU (575V 40–70 Ton) Conversion

 

 

Flō 

Tech Support 888-598-1198 

11

 

4-6DEC2021 

 

9.5

 

Dehumidification Test Mode 

From the Main Menu, press and hold down 

T7,

 

while  holding 

T7

  down,

 

depress 

T1 

(

Field  Technician 

Options)

 
 From the Field Technician Options screen, press 

T2

 (

Test 

Modes

). Press 

T3

 (

2. Operational Tests

). 

 
Use 

 

  to  navigate  to  the 

Dehumidification 

Test Mode Off

 and press 

ENTER

 
When the "OFF" value begins blinking, press the 

 to 

change the value to "ON", then press 

ENTER

.  

 
Wait for 

10-minutes

, then terminate Dehumidification. 

Terminate Dehumidification Test Mode (

OFF

 
From the  Field Technician Options  screen, press 

T2

  (

Test 

Modes

). Press 

T3

 (

2. Operational Tests

). 

Use 

 

  to  navigate  to  the 

Dehumidification 

Test Mode 

ON

”, then press 

ENTER

 
When  the  "

ON

"  value  begins  blinking,  press 

  to 

change the value to "

OFF

", then press 

ENTER

 

Dehumidification mode is now turned “

OFF

”.

 

 

9.6

 

Heating Test Mode

 

From the  Field Technician Options  screen, press 

T2

  (

Test 

Modes

). Press 

T3

 (

2. Operational Tests

). 

 
 Use 

 

 to navigate to the 

Heat Test Mode Off 

and press 

ENTER

.  

 
When the "OFF" value begins blinking, press the 

 to 

change the value to "ON" and press 

ENTER

.  

 
Wait for 

10-minutes

, then terminate Heating. 

 
Terminate 

Heating

 Mode (

OFF

 
From the  Field Technician Options  screen, press 

T2

  (

Test 

Modes

). Press 

T3

 (

2. Operational Tests

). 

 
Use 

  and 

  to  navigate  to  the 

Heating  Test 

Mode On

 and press 

ENTER

 
When  the  "

ON

"  value  begins  blinking,  press  the 

 

change the value to "

OFF

", then press 

ENTER

 

Heating mode is now turned “

OFF

”.

 

 
  

 

 

 

(A) 

(B) 

(C) 

(D) 

(E) 

(F) 

(G) 

(H) 

(I) 

MODES OF 

OPERATION 

SUPPLY 

FAN 

COMP(S) 

COND 

FAN(S) 

RECLAIM 

HEATING 

OUTDOOR 

AIR 

DAMPER 

RETURN 

AIR 

DAMPER 

BYPASS 

AIR 

DAMPER 

INDICATE 

PASS

 or 

FAIL

 

DEHUM 

ON 

ON 

ON 

N/A 

OFF 

OPEN

*

 

OPEN

**

 

OPEN 

 

HEATING 

ON 

OFF 

OFF 

N/A 

ON 

OPEN

*

 

OPEN 

OPEN

**

 

 

* Damper will be in the OPEN position (

typically 20 - 30%

 - OPEN 

0.5” –

 

1.50”

). 

** This damper will be OPEN to its minimum position. 

Table 6: Test mode unit status 

 

Summary of Contents for i-Controller

Page 1: ...oat Switch 4 6 5 Install New CO2 Sensor 5 6 6 Install Space Temp RH Combo Sensor 5 7 Install The i Controller Components 6 7 1 Remove Existing Jenesys Controls 6 7 2 Install New i Controller and Expan...

Page 2: ...rols Screwdriver Step Drill Bit for CO2 Sensor Probe Installation Refrigerant Tee with Schrader Depressor 2 Schrader Cores 4 Conductor Shielded Twisted Wire or Equivalent 5 Conductor Shielded Twisted...

Page 3: ...gths of Black 18 AWG wire to the following i Controller green plug connection points 1 7 8 25 28 61 See Figure 1 for plug orientation Attach 10 lengths of Red 18 AWG wire to the following i Controller...

Page 4: ...the 0 667 PSI Discharge transducers on the liquid lines of circuits 1 2 3 4 If there are spare service ports on the unit install the transducers on a spare service port If spare service ports are not...

Page 5: ...w Figure 3 CO2 sensor location inside the unit Wire the new CO2 based on the following see Figure 4 24VAC Red wire 24VAC Black wire COM Green wire CO2 SIGNAL White wire NOTE Do not wire the CO2 sensor...

Page 6: ...1 down 2 up 3 down 4 down NOTE The actual switch may be white but for illustrative purposes the switch is black in the Figure 6 below Figure 6 Fl i Controller Expansion Addressing Wire the 2 expansion...

Page 7: ...Comp 1 SG WHT 12 Discharge Press Comp 1 0V BLK 8 Discharge Press Comp 1 Pwr RED 15 Suction Press Comp 2 SG WHT 13 Suction Press Comp 2 0V BLK 8 Suction Press Comp 2 Pwr RED 15 Discharge Press Comp 2...

Page 8: ...Reheat Reclaim Inlet Probe 2 SG 29 Reheat Reclaim Inlet Probe 2 0V 28 This indicates that you will be attaching to a 10 wire not a pin This indicates that you will be attaching to the CSTB1 Table 3 In...

Page 9: ...aim do not wire 24VAC to point 86 The dry common from the refrigeration rack reclaim control is connected to point 86 Existing Points Expansion Module A Expansion A Pin See Wiring Diagram in Unit ERV...

Page 10: ...With a field highlighted press ENTER the value will begin blinking While the highlighted value is blinking use the and set the value Press ENTER a second time to accept changes The controller will au...

Page 11: ...hen press ENTER Dehumidification mode is now turned OFF 9 6 Heating Test Mode From the Field Technician Options screen press T2 Test Modes Press T3 2 Operational Tests Use to navigate to the Heat Test...

Page 12: ...ions button Using the to navigate to the value that you wish to change With a field highlighted press ENTER the value will begin blinking While the highlighted value is blinking use the set the value...

Page 13: ...l Tech Support 888 598 1198 13 4 6DEC2021 11 Appendix 11 1 i Controller Layout 1 24VAC Power Point 9 and 1 2 Analog Inputs 3 Digital Inputs 4 Digital Outputs 5 Analog Outputs 11 2 Expansion Board Layo...

Reviews: