Technical Guide
CN-IC1-12
Title
:
i-Controller Visograph Navigation REV.201.05
EXTERNAL
7
1-5JULY2021
6.
Repeat steps 1-
4 until all “Occupied” values have
been set.
7.
Press the
(T8) button to view the
“Unoccupied” set points.
8.
Repeat steps 1-
4 until all “Unoccupied” values have
been set.
9.
Once all changes have been completed, press the
(T7
) to return to the “Occupied” set points
screen or press the
(T1) button to return to
the Main Menu.
Figure 8. Occupied Set Points - screen 1
T1: Go to Main Menu
T4: Scroll Up/Increase Value
T5: Enter (Select and Set Value)
T6: Scroll Down/Decrease Value
T7: Go to Previous Page
T8: Go to Next Page
Figure 9. Unoccupied Set Points - screen 2
Figure 10. VAV & Power Exhaust Fan Set Points - screen 3
Zone Thermostat Control
Units configured to use 2-Stage zone thermostats have
the internal heating and cooling setpoints disabled for
both Occupied and Unoccupied modes. However, the
internal Dew Point set point is still active for both modes.
Figure 11. Occupied Set Point screen 1 with TSTAT active
Figure 12. Unoccupied Set Point screen 2 with TSTAT active