Technical Guide
CN-IC1-12
Title
:
i-Controller Visograph Navigation REV.201.05
EXTERNAL
18
1-5JULY2021
Alarm History
The Alarm History will display a timestamp next to each
alarm indicating the last alarm occurrence.
Figure 39. Alarm History screen 1
Figure 40. Alarm History screen 2
Alarm Resets
Press T1 to return to the Alarms Menu. If a fan fail occurs
and the problem has been resolved, the fan fail alarm
needs to be reset to start normal operation. To reset the
fan, fail alarm, perform the following steps:
1.
Using the
and
buttons (T4 and T6,
respectively) ensure that the “OFF” value is
highlighted.
2.
Press the
(T5) button and the value should
blink.
3.
Using the
and
buttons increase and
decrease the value until “ON”
appears.
4.
Once the desired value has been reached press
the
button to set the value.
5.
Once the value has been set to “ON” the fan fail
alarm has been reset and the fan is ready for
operation.
6.
The value will automatically reset to “OFF” after
5 seconds.
Values will display as “ON/OFF” for
Fan Fail Reset, or “YES/NO” for Clear Alarms.
Figure 41. Alarm Resets screen
T1: Go to Alarms Menu
T4: Change value to ON
T5: Enter (Select and Set Value)
T6: Change value to OFF