background image

09

Troubleshooting Chart

Risk of electric shock. Always disconnect the pump from the power source before handling inspections or repairs.

Symptom

Possible Cause(s)

Corrective Action

Pump will not run

1.   Poor electrical connection, blown fuse, tripped 

breaker or other interruption of power; 

improper power supply

2.   Motor or switch inoperative (go to manual 

operation)

2a. Float movement restricted
2b. Switch will not activate pump or is defective
2c. Defective motor
3.   Insuffi cient liquid level

1.  Check all electrical connections for security. 

Have electrician measure current in motor leads, 
if current is within ± 20% of locked rotor Amps, 
impeller is probably locked. If current is 0, 
overload may be tripped. Remove power, allow 
pump to cool, then re-check current.

2a. Reposition pump or clean basin as required to 

provide adaquate clearance for float

2b. Disconnect level control. Set ohmmeter for a 

low rang, such as 100 ohms full scale and 
connect to level control leads. Actuate level 
control manually and check to see that 
ohmmeter shows zero ohms for closed switch 
and full scale for open switch. (Float Switch)

2c. Check winding insulation (Megger Test) and 

winding resistance. If check is outside of range, 
dry and re-check. If still defective, replace per 
service instructions.

3.  Make sure liquid level is above the pump
4.  Re-check all sizing calculations to determine 

proper pump size.

5.  Check discharge line for restrictions, including 

ice if line passes through or into cold areas.

6.  Remove and examine check valve for proper 

installation and freedom of operation

7.  Open valve
8.  Check impeller for freedom of operation, 
  security and condition. Clean impeller cavity 
  and inlet of any obstruction
9.  Loosen union slightly to allow trapped air to 

 escape. Verify that turn-off level of switch is set 

  so that the suction is always flooded. Clean vent
  hole
10. Check rotation. If power supply is three phase, 

reverse any two of three power supply leads to 
ensure proper impeller rotation

11. Repair fixtures as required to eliminate leakage
12. Check pump temperature limits and fluid

temperature

13. Replace portion of discharge pipe with flexible

connector or tighten existing piping.

14. Turn to automatic position
15. Check for leaks around basin inlet and outlets

Pump will not turn off 

2a. Float movement restricted
2b. Switch will not activate pump or is defective
4. Excessive inflow or pump not properly sized for 

application

9. Pump may be air locked causing pump not to flow
14. H-O-A switch on panel is in "HAND" position

Pump hums but doesn’t run

1.  Incorrect low voltage
8.  Impeller jammed or loose on shaft, or inlet 

plugged

Pump delivers insufficient capacity

1.  Incorrect low voltage
4. Excessive inflow or pump not properly sized for

application

5.  Discharge restricted
6. Check valve partially closed or installed backwards
7. Shut-off valve closed
8.  Impeller jammed or loose on shaft, or inlet 
  plugged
9.  Pump may be air locked causing pump not to flow
10. Piping fixtures leaking or discharge before the 
  nozzle

Pump cycles too frequently or runs periodically 

when f ixtures are not in use

6.  Check valve partially closed or installed backwards
11. Fixtures are leaking
15. Ground water entering basin

Pump shuts of f and turns on independent of

switch, (trips thermal overload protector). 

CAUTION!

Pump may start unexpectedly. 

Disconnect power supply.

1.  Incorrect low voltage
4. Excessive inflow or pump not properly sized for

application

8.  Impeller jammed or loose on shaft, or inlet 

plugged

12. Excessive water temperature (internal 

protection only)

Pump operates noisily or vibrates excessively

2c. Worn bearings, motor shaft bent
5.  Debris in impeller cavity or broken impeller
10. Pump running backwards
13. Piping attachments to building structure too 

loose or rigid

NOTE: 

Flo Fab Pumps assumes no responsibility for damage or injury due to disassembly in the field. Disassembly of the pumps or supplied accessories other 

than at Flo Fab Pumps or its authorized service centers, automatically voids warranty.

Summary of Contents for 2FFSTEP

Page 1: ...Installation Operation Maintenance Manual Submersible Effluent Pumps 2FFSTEP 0 5 1 HP 3450 RPM IMPORTANT Read all instructions in this manual before operating or servicing a pump...

Page 2: ...nstalled in locations classified as hazardous in accordance with the National ElectricCode ANSI NFPA70 DANGER Caution indicates a potentially hazardous situation which if not avoided MAY result in min...

Page 3: ...tironASTMA 48class30 MOTORHOUSING CastironASTMA 48class30 SEALPLATE CastironASTMA 48class30 IMPELLER Singlevaneenclosed Polypropylenewithstainlesssteelinsert SHAFT Stainlesssteel O RINGS SquareshapedB...

Page 4: ...and shall NOT be installed in locations classified as hazardous in accordance with the National Electrical Code NEC ANSI NFPA 70 or Canadian Electric Code CEC The pump should never be installed in a...

Page 5: ...e current or the sensor will not work properly TEMPERATURE SENSOR ELECTRICAL RATINGS Volts Continuous Amperes Inrush Amperes 110 120 3 00 30 0 220 240 1 50 15 0 Wire Size If longer power cable is requ...

Page 6: ...p oil If after five minutes the pressure is still holding constant and no bubbles oil seepage is observed slowly bleed the pressure and remove the gauge assembly Replace oil Leek must be located and r...

Page 7: ...square ring replace if cut or damaged Disconnect capacitor leads from capacitor Remove motor bolts lift cover body and stator assembly from seal plate Remove snap ring to remove rotor assembly Remove...

Page 8: ...07 Repair Parts FFBPSTEP For Repair Part Please supply Model Number and Serial as shown on Name Plate and Part Description and Part Number as shown on Parts List...

Page 9: ...HT200 16 Impeller 117 3 1 Polypropylene 17 Casing 1 HT200 18 U shpe ring 31 5 x 44 3 x 6 5 1 NBR40 19 Casing sealing washer 1 Rubber 20 Hex socket cap screws 1 4 20UNCx28 2 304 21 V shape ring 1 NBR4...

Page 10: ...e reverse any two of three power supply leads to ensure proper impeller rotation 11 Repair fixturesasrequiredtoeliminateleakage 12 Check pump temperature limits and fluid temperature 13 Replace portio...

Page 11: ......

Reviews: