2-11 Commissioning
The unit must not be started until all
documentation has been studied and all
electrical fitting and plumbing work has
been performed.
1
Familiarise yourself well with the documentation for the automatic control system
2
Check that the network settings are correct. For 230V 3~Phase, the unit and electric battery must be switched.
3
Start the unit as described in the documentation for the automatic control.
4
Program the various operating times and speeds (possibly including stop)
5
Check that the correct temperature regulation and temperature settings have been selected. Are the sensors located
correctly?
6
Check that the fans rotate freely.
7
Check that all air dampers work. The unit must not be operated with closed air dampers!
8
Check that all doors are properly closed.
9
Check that settings on the circuit board are correct (cf. chap. 2-9).
10 Check that the heat recovery system works correctly.
11
Check that the heat control works correctly.
12
If the unit has a water battery, you must test the frost function. Cool the frost sensor to below 5 °C.
The unit should stop and the air dampers close.
13
See chapter 4-1.3 Troubleshooting and follow the instructions.
14
Tighten all terminal blocks after commissioning.
Refer to guideline 112140 for more information
on start up and use of the control system.