4 |
* B-
W temperature increase at inlet air 10ºC and heating agent temperature 90/70ºC / B-E temperature increase at inlet air 10ºC
▪
Fan
– motor with plastic rotor;
▪
Heat exchanger
– copper-aluminium, connecting stub ½”;
electrical heaters PTC;
▪
Casing
– sheet steel RAL; color white RAL 9016,
– back elements - expanded polypropylene EPP;
colour
– grey;
– air inlet fins - anodized aluminum
2. TECHNICAL DATA
B-W-
100
B-N-
100
B-E-
100
B-W-
100 2R
B-W-
150
B-N-
150
B-E-
150
B-W-
150 2R
B-W-
200
B-N-
200
B-E-
200
B-W-
200 2R
Power supply [V/Hz] |
230/ 50
3x400
/ 50
230 /
50
230 / 50
3x400
/ 50
230 /
50
230 / 50
3x400
/ 50
230 /
50
Power consumption [kW]
0,34
0,42
7,5
0,34
0,36
0,44
11,5
0,36
0,38
0,49
15,5
0,38
Current consumption [A]
1,5
1,9
11
1,5
1,6
2
16,6
1,6
1,7
2,2
22,4
1,7
IP/insulationclass
IP 21 / F
Connecting stub
[”]
½
-
½
½
-
½
½
-
½
Max. water temperature [
o
C] |
95
-
95
95
-
95
95
-
95
Max. water pressure [MPa]
1,6
-
-
1,6
1,6
-
-
1,6
1,6
-
-
1,6
Temperature increase (∆T) [ºC]*
15
-
11
28
15
-
12
31
16
-
13
33
Weight [kg]
32,3
31,7
34,5
33,7
41,2
38,9
42,4
43,7
50
47,2
53,2
53,2
Weight of unit filled with water [kg]
33,1
-
-
35,2
42,4
-
-
45,7
51,6
-
-
56,4
2.1. CONSTRUCTION
Summary of Contents for ELIS B-E-100
Page 7: ... 7 7 8 9 10 11 12 13 14 ...
Page 10: ...10 1 2 3 4 5 6 7 ELiS B W N 8 ELiS B E 4 2 CONNECTING GUIDE ...
Page 25: ...26 ...