4.3.2. REGULATION TS-ELIS B-E WIRING DIAGRAMS
Power supply 3x400V/50Hz
•
ELiS B-E-100 (min. 5x2,5 mm
2
) (Overcurrent B16)
•
ELiS B-E-150 (min. 5x4,0 mm
2
) (Overcurrent B20)
•
ELiS B-E-200 (min. 5x4,0 mm
2
) (Overcurrent B25)
Door contact DCe/DCm (door closed
– contacts opened; door
opened
– contacts closed) (OMY 2x0,5 mm
2
)
ATTENTION:
Switch 4 on SW3 to the position “E” and then restart the system
switching it off for 5 seconds. Each time the device is switched off the
heaters are being cooled for next 30 seconds
Air curtain step switch with thermostat TS (OMY 5x0,5 mm
2
)
•
HEAT- heating mode
•
FAN - room thermostat deactivated
•
COOL - cooling mode
•
1;2;3
– step switch