background image

Supplied By www.heating spares.co  Tel. 0161 620 6677

2.8

REMOVING / RE-FITTING THE GLASS FRAME ASSEMBLY

a)

The glass frame is held in position by hooking the top flange over the 
combustion chamber opening at the top as shown in Fig. 10 below.

Fig. 10

b)

The assembly is then secured to the bottom of the combustion chamber
by the two hinge clamp brackets as shown below in Fig. 11.  These are 
clamped together to form the seal between the glass frame assembly 
and the combustion chamber.

NOTE :

Always ensure that a consistent seal between the combustion 
chamber and the glass frame is achieved.

Fig. 11

13

Glass Frame Assembly
locates over lip on top of
combustion chamber lid, and
drops onto flange as shown.
To remove, unclip base clips
as shown in Fig. 11 and lift
clear.

denotes correct 
final position of 
glass frame. 

Combustion
Chamber

Summary of Contents for Emberglow FEBC00MN

Page 1: ...Tel 0161 620 6677 Emberglow COAL EFFECT BALANCED FLUE GAS FIRE Installation and Maintenance Instructions Hand these instructions to the user Model No s FEBC00MN is for use on Natural Gas G20 at a supp...

Page 2: ...l 11 12 2 7 Fitting the terminal guard 12 2 8 Removal refitting of the glass frame 13 Section 3 Assembling Fuel Bed and Commissioning 3 1 Fitting the fuel bed 14 3 2 Lighting the appliance 15 16 3 3 F...

Page 3: ...ize 360 Pilot Type S I T 140 Series NG size 27 Max Gross Heat Input 5 25 kW Min Gross Heat Input 2 05 kW Gas Rate 0 470 m3 hr High 0 190 m3 hr Low Cold Pressure 20 0 1 0 mbar 8 0 0 4 in w g Ignition I...

Page 4: ...ber framed building please consult document IGE UP 7 issued by the Institute of Gas Engineers In Republic of Ireland No purpose made additional ventilation is normally required for this appliance when...

Page 5: ...12in opening window B Above an opening air brick 300mm 12in opening window C Horizontally to an opening air brick opening window etc D Below gutters soil pipes or drain pipes 300mm 12in E Below eaves...

Page 6: ...or other floor coverings over it The hearth must be fitted symmetrically about the fire opening and have a minimum width of 760 mm and a minimum projection of 350 mm forwards from the fire opening SE...

Page 7: ...does not distort when installed Ensure that the floor surface onto which the appliance is mounted onto is flat and the hearth size conforms to the requirements of section 1 5 on page 6 The minimum hei...

Page 8: ...flue pipe as specified in figure 4 Mark the position of the hole around this point Chisel out the area as marked on the wall We then recommend that a cardboard cylinder is placed around the flue pipe...

Page 9: ...minal assembly firmly into the rear of the combustion chamber as shown below in Fig 5 e Drill 3 off holes through outer flue pipe and into the mounting spigot and screw flue pipe and terminal assembly...

Page 10: ...d side of the product when viewed from the front It is therefore suitable for rear or right hand side gas supply See Fig 7 below 10 Rear gas supply route Position of Mortar or Fire Cement Seal around...

Page 11: ...ages 15 to 17 NOTE Please ensure that the battery that has been disconnected at the factory prior to packing is re connected The battery is located at the bottom L H S of the combustion chamber attach...

Page 12: ...terminal could come into contact with people near the building or be subject to damage CFM Europe also recommend the fitting of a flue terminal guard where regulations do not demand that it be fitted...

Page 13: ...mber by the two hinge clamp brackets as shown below in Fig 11 These are clamped together to form the seal between the glass frame assembly and the combustion chamber NOTE Always ensure that a consiste...

Page 14: ...tion centrally in the combustion chamber as shown below in Fig 12 Fig 12 b Fit the front ceramic coal form in front of the burner as shown below in Fig 13 Ensure that the front ceramic coal form is co...

Page 15: ...b for a few seconds whilst the air is purged from the supply pipe Bring the knob back to its start position and turn it several times to the pilot position The pilot should light Hold in the control k...

Page 16: ...put between high and low f Check that the gas pressure is 20 0 mbar 1 0mbar 8 0 in w g 0 4 in w g with the main burner operating on high To turn off the main burner g Turn right hand control knob cloc...

Page 17: ...CED THIS IS NORMAL AND DOES NOT EFFECT OR IMPAIR THE SAFETY OF THE APPLIANCE 3 3 FITTING OF THE FENDER Warning Please take care whilst handling the fender as it s cast iron construction means it is a...

Page 18: ...page 17 4 1 3 Remove the glass frame assembly from the fire as shown in section 2 8 on page 13 4 1 4 Remove the ceramic coal forms from the combustion chamber taking care not to damage them 4 1 5 Rem...

Page 19: ...n in section 2 8 on page 13 4 4 4 Remove the ceramic coal forms from the combustion chamber taking care not to damage them 4 4 5 Loosen the pilot pipe disconnect the ignition lead from the electrode a...

Page 20: ...Flavel Stockist whose details can be found on the CFM Europe website in the stockist section Control Valve B 82290 Pilot Body 70 36250 Thermocouple 70 36270 Pilot Gasket 70 35220 Ignition Electrode 7...

Page 21: ...Supplied By www heating spares co Tel 0161 620 6677...

Reviews: