PFSIFP8
Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 25
possible damage to it.
If it is system fault, please check and repair in time. If the panel needs to be shut
down, please make detailed notes.
If it is field device fault, please repair it in time. You can disable it if the fault cannot
be cleared for some reason, and enable it when the fault is removed.
5.7 Rules for Message Display
If there are multiple messages in the system, they will be displayed in the following order:
fire alarm, pre-alarm, supervisory, fault, disable.
1 The earliest fire alarm is displayed in priority. The latest pre-alarm, supervisory,
fault, and disabled message are displayed in priority.
2 In any display mode, the system will return to displaying message of the higher
priority if there is no operation within 30s.
5.8 Rules for Sound Indication
The FACP will sound to indicate fire alarm or fault messages.
The FACP gives continuous sound when fire alarm occurs.
The FACP gives slow sound (2s on, 2s off) when there is supervisory message.
The FACP gives slow sound (1s on, 1s off) when fault occurs.
The FACP will give sound of higher priority if two types of event occur simultaneously.