PFSIFP8
Intelligent Fire Alarm Control Panel
Installation and Operation Manual
Page 15
LOOP10
LOOP8
LOOP7
LOOP6
LOOP5
LOOP4
LOOP3
LOOP2
LOOP1
LOOP9LOOP10
O+ O-
O+ O-
O+ O-
O+ O-
O+ O-
O+ O-
O+ O-
O+ O-
O+ O- O+ O-
I+ I-
I+ I-
I+ I-
I+ I-
I+ I-
I+ I-
I+ I-
I+ I-
I+ I-
I+ I-
OUTPU
T
TO FPE
+ --
OUTPUT TO
SOUNDER
+ --
ALARM
ROUTING
+ --
FEED
BACK
F2 F1
REPEATER
A B
FAULT
OUTPU
T
NO COM NC
Fig. 4-3
Description:
LOOP1
~
LOOP10:
Each loop can have maximum 242 addressable devices. The
FACP can have maximum 8 loops. If loop isolators are connected into the Class A
loop, the detectors protected by the isolators will not be lost in case of short or open
circuit with the loop, and the FACP reports loop fault.
OUTPUT TO FPE:
It outputs according to settings in Section 6.3.2 when there is
fire alarm. It can be disabled, and does not output when fire alarm occurs in
disabled state. It can be included into C&E equation, but cannot be set at delay
mode. The FACP reports fault when there is short or open circuit with connecting
lines.
OUTPUT TO SOUNDER:
It outputs according to settings in Section 6.3.2 when
there is fire alarm, which can be stopped by choosing SILENCE key. Output can be
disabled, and there is no output in disabled state. It can be included into C&E
equation, and can be set at delay mode. The FACP will report fault when