background image

29

28

чѵс$)/*-.Ȃ /$)"*--*.$*))4./ (+ -!*-() 

•  “PH” or relative Acidity/ Alkalinity are of key importance in managing the production of system corrosion. It is 

recommended that PH Level of the system water be between 7 and 8.5 (ideally 7.4/7.5). A Lower PH level than 

recommended would be classed as acidic and corrode all metals. Alternatively, too high a PH level would be alkaline 

and will corrode aluminium components within the wetted part of the system.

•  When considering a chemical treatment product to add to the system, we recommend products which incorporate a 

($3!*-0Ȃ -$)"Ѷ$)*- -/**)/-*'/#  ' 1 '(*-  Ȃ /$1 '4ѵ

•  Oxygen Ingress should be minimised by the use of closed systems and barrier pipe within the system design.

• 

""- ..$1 $*).җ.0#.ޕ03- .$0 .Ҙ+-*(*/ *--*.$*))Ѷ*)/$)0 /**.*0)' ..) 0/-'$. *-ޕ0.# *0/

completely. We would recommend a jointing approach that removes the need to use such compounds and adopt 

the use of heat free systems.

• 

!/-$/$*)'.*' -ޔ//$)".- 0. /# )2 2*0'- *(( )/# 0. *!- *")$. # ($'/- /( )//*ޕ0.#

out and neutralise the system (see section 3.1 below). In addition, it is strongly advised to contact the manufacturer 

of the chemical treatment to gain early involvement prior to treatment as to the correct application and chemical to 

use.

•  The accumulation of sludge & debris can cause deposit corrosion which leads to pitting. We recommend the use 

*!- *")$. # ($'/- /( )//*ޕ0.#*0/)) 0/-'$. /# .4./ ()$/$*)Ѷ$/$../-*)"'41$. /*

contact the manufacturer of the chemical treatment to gain early involvement prior to treatment as to the correct 

application and chemical to use.

8.3 Refurbishment and Improvement to existing systems

•  It is vitally important that before commencing works on existing systems that a complete scan of the water quality 

of the system be taken. If it is found that the system contains products of corrosion and/or PH levels in excess 

of the required norms, it is recommended that the existing water is conditioned and treated PRIOR to the work 

commencing.

8.4 System commissioning (water quality) Water Treatment Chemicals

• 

 *)*/- *(( )/# 0. *!-22/ -!*-#4-0'$/ ./$)"0 /*/# -$.&*!*--*.$*)*!/# 2/ - $)"' ȅ$)

the system and potentially, the internals of the system being exposed to the air due to partial draining.

• 

# ($''4*. 2/ -.#*0' $)''ޔ''$)"/$1$/$ .$)*-) 2$/#/# # ($'()0!/0- -.ҁ

recommendations and in accordance with BSRIA BG29 2012.

• 

ȅ -.0$/' ޔ''$)")ޕ0.#$)"- "$( $.0. Ѷ- ' 1)//*/# .4./ ((/ -$'Ѷ''# ($'.0. /* .0$/'

for HIU must comply with EU norms DIN EN 12828 and current guidelines for heating systems. In addition, they 

should also be non hazardous, non toxic and biodegradable.

•  The use of correct cleaners and inhibitors is of primary, environmental concern. All chemicals used to treat the 

system should not contain phosphates, sulphuric acid, nitrites. See BS7593:2006 Code of Practice for treatment of 

water in domestic hot water space heating systems.

•  Inhibitors should meet Buildcert as a minimum and preferably be recommended by the Energy Savings Trust (ESR).

•  Acid based cleaners are unsuitable for older systems as there is a risk of “pinholing” on radiators. They will also 

require some form of neutralisation process before being discharged or require being taken away for disposal.

8. Appendix A

8.5 Recommendations for system conditioning - (Basic process)

• 

# .4./ ((0./ ޕ0.# )$)#$$/ $)*-) 2$/#цфшт)/# *( ./$0$'$)" -1$ .

Compliance Guide.

•  The chemicals used should contain the following aspects of their composition:

 

Surfactants to reduce surface tension allowing chelating agents to attach to the residues.

 

Chelating agents will then entrap the calcium carbonate within the solution.

 

Dispersant’s are used to hold residues in suspension.

 

The inhibitor then prevents corrosive attacks on metals during cleaning.

 

 0Ȃ -./*($)/$)) 0/-' ѵ

 

Chemicals shall be of a type suitable for disposal through a conventional sewer or foul drain (i.e. no requirement 

for tankering or specialist disposal).

 

Neutralisation.

 

For cooling applications, specialist chemicals and advise should be sought.

8.6 Site installation conditions – Installation of the system

It is recommended that:

 

/ -.*'0' ޕ03.#*0' 0. җ)*#'*-$ Ҍ Ҙ/# - !*- ҂# /!-  ҃.4./ (.- - *(( ) ѵ

 

The area of installation should be free from gypsum dust, brick dust, screed or other possible contaminants. 

чѵц *(( ) ȅ -- җ Ҙ /2*-&-$(-4.$ 

•  Any relevant details of the installed units and system conditioning to be documented in the O&M manual.

• 

# - .#*0' ' -)*/$ޔ/$*)*!)4# ($'+-*0/. Ѷ/ . /+' *)/#  ѵ

•  If there is a requirement for a partial drain down, the inhibitor should be topped up to the required level with full 

details.

• 

 #$"#'4- *(( )/#/''. -1$$)"ҝ$).+ /$*) /.+ -()0!/0- -ҁ.$)./-0/$*).җ Ѷޔ'/ -Ѷ# ($'. /Ҙ$.

fully adhered to.

•  Any checklist sticker placed within the casing by the manufacturer must be completed.

8. Appendix A

Summary of Contents for logoEco A2RXE

Page 1: ...GB Technical information for installation and operation LogoEco Heat Interface Unit HIU A2RXE Instantaneous Hot Water Space Heating...

Page 2: ...hoot technician 25 8 Appendix A 27 Appendix B 31 Appendix C 32 Contents Symbols and abbreviations Symbols Abbreviations CAUTION general safety remark CAUTION risk of shock CAUTION hot surfaces risk of...

Page 3: ...ater temperature This may lead to a domestic hot water temperature that is higher or lower than its set point Hot water can cause burns 1 3 Priority switching 2 4 2 2 2 1 2 0 water If there is a power...

Page 4: ...purpose it is advised to design the SH circuit in such a way that the SH return temperatures are as low as possible Keep following condition in mind during installation 4 2 0 0 4 2 General Plumbing R...

Page 5: ...orrect current or overcurrent The circuit breaker must have a contact separation of at least 3mm in all poles and should isolate the appliance and all associated controls The HIU must at all times be...

Page 6: ...P1 Description Type District heating station for indirect heating and instantaneous domestic hot water Mounting Wall mounted Dimensions 490 x 275 x 640 mm WxDxH height of the case Heating System 2 Con...

Page 7: ...on make sure that there is a board installed e g plywood min 18mm to support the structure which is strong enough to hold the HIU Use a 4mm drill bit at least 40mm depth for the wall plugs If the wall...

Page 8: ...may be hot or energized Contact may lead to shock burn or electrocution 1 Disconnect the HIU from the mains power 2 Open all space heating circuits in the property Turn the room thermostat and all ra...

Page 9: ...un quietly without any air noise 5 0 0 its operating mode setting 0 4 0 the automatic air vent anti clockwise Turn on the circulation pump and let it run until all air 1 0 the pump setting and close t...

Page 10: ...ice CAUTION Parts and components may be hot or energized Contact may lead to shock burn or electrocution 1 Close all valves 2 Check all nuts for leakage nuts may become loose during transport 3 Make s...

Page 11: ...n the table below Settings You can choose between the performance view and settings view If you press the push button for 2 to 10 seconds the user interface switches to select selection if the user in...

Page 12: ...procedure needs to be repeated Problem Cause Solution Pump not running Not connected or connected correctly Connect correctly Pump too hot dry operation or overheating protection active Allow pump to...

Page 13: ...e electronics Contact your supplier 0 Tap is opened unit is in tapping operation Close Tap Sensor s are not connected or bad contact Check wire tree connections and connect the sensors properly then r...

Page 14: ...e a light humming sound Rattling sound Flow sensor not installed correctly 2 4 Other defects Contact your supplier Guidelines for System Conditioning of Heating and Cooling Networks for Flamco Limited...

Page 15: ...mendations and in accordance with BSRIA BG29 2012 0 0 0 1 4 0 0 for HIU must comply with EU norms DIN EN 12828 and current guidelines for heating systems In addition they should also be non hazardous...

Page 16: ...tor of possible corrosion Chemical assessment PH value hardness precipitate composition and concentration of chemical treatment and type of treatment contained within the water A UKAS registered lab i...

Page 17: ...8 Bleed point G 1 8 BT 19 Water hammer arrester G 3 4 WM x G 3 4 BT l 84 5 21 Flow sensor SIKA 22 Non return valve 24 circulation pump DHW Lowara 25 circulation pump space heating Grundfos UPM3 AUTO 1...

Page 18: ...35 34 Contact Notes United Kingdom Flamco Limited Washway Lane St Helens Merseyside WA10 6PB United Kingdom 44 1744 744 744 0 222 0...

Page 19: ...Flamco Limited Washway Lane WA10 6PB St Helens Merseyside United Kingdom T 44 17 447 447 44 F 44 17 447 447 00 E 0 222 0 0 0...

Reviews: