Operations room
Room:
Protected against:
Ambient conditions:
Locked
Solar radiation
60 ... 70 % relative humidity, non-condensing;
temperature 3 - 40 °C
frost-free,
thermal radiation
depending on type 3 - 50 °C;
dry
vibration.
free of electrically conductive gases, explosive
gas mixtures, aggressive atmosphere. Caution:
Higher temperatures may lead to overload of the
compressors.
Minimum distances
Minimum distances
Volume [litres]
A
[mm}
B
[mm]
C
[mm]
400
600
800
1000
1200
1600
650
800
500
2000
2800
3500
5000
6500
8000
10000
1000
Installation examples
Distance system supply, system discharge, at return integration point, in the range 0.5 ... 1 ... m.
Please note:
If the return line is routed horizontally, do not implement the connection from below to avoid
additional contamination with dirt.
1. For design temperatures > 100 °C and > 110 °C, additional requirements from applicable European standards may apply.
2. Add additional auxiliary vessels symmetrically using a collector line (main vessel at centre) taking into account minimum
distances. The branch from the main vessel must be flexible.