Installation and Maintenance 

Roof Fan STOF

17

  

Fläkt Woods 

9734 GB 2015.06.30 

Specifications are subject to alteration without notice

7. SeRvICe, CONT.

7.2.2  CleANINg OF The ImpelleR, mOTOR ANd CASINg 

(INSulATed veRTICAl veRSION).

1. Switch off the fan from the isolator and wait 5 min. before start-

ing the maintenance work.

2. Open the fastening screws ~10 mm so that the casing can 

be opened. Fan can be locked to open position with stay 
fastener(s), picture 11.

3. Lift the fan casing to its open position and check that stay 

fastener(s) are correctly locked and the base frame is  
correctly fastened.

4. Clean the necessary parts of the fan.
5. Loose the stay fastener(s) and let the casing go to its closed 

position and tighten the fastening screws. Start the fan and 
check that impeller rotates freely and fan runs smoothly.

The casing can be cleaned also from upside by removing the roof 
panel, see point 3.1.2.

Catch

Stay fastener

Fastening 

screw

Figure 11.

Figure 12.

7.2.3 mOTOR ReplACemeNT (uNINSulATed veRSION)

NOTe!

Motor & impeller shall be always be replaced as a package. This 
package is available for size 400 and bigger. In case of smaller 
fans the complete unit is to be replaced.
Open ductwork below the roof fan shall be covered to protect 
tools and other small parts from dropping into the duct.
1. Switch off the fan from the isolator and wait 5 min. before  

starting the maintenance work.

2. 

Vertical version:

 Remove the casing and roof (fixed together) by 

loosening the M6 bolts and self-tapping screws. Open the M6 
bolts to detach motor bracket.

 

Horizontal version:

 Remove cowl (M6 bolts), fan guards (M6 

bolts) and motor bracket (M6 bolts).

3. Disconnect the cables.
4. Lift motor bracket with the motor and impeller up from the base 

frame.

5. Remove motor bolts (if necessary protect impeller-motor pack-

age from dropping down) and lift the motor bracket away.

6. Remove inlet cone (fastened with pop-rivets and sealing  

compound).

7. Install new inlet cone (remember sealing compound), and mo-

torized impeller.

8. Reconnect the cables.
9. When re-installing motor bracket and casing, check again that 

impeller can rotate without problems.

Start the fan. Check that rotational direction is correct and the 
impeller rotates freely and there are no abnormal noises coming 
from the fan.

Summary of Contents for STOF

Page 1: ...Installation and Maintenance STOF ROOF FAN Air movement Roof fans Air Comfort...

Page 2: ...y regulations Tools and protective equipment necessary for preventing accidents from occurring while installing and operating the fan must be used worn in accordance with the local safety regulations...

Page 3: ...fan is used to generate required air flow at current pressure drop equal to losses in the duct system This is done by using a rotating impeller inside the fan casing 3 1 Construction 3 1 1 Uninsulated...

Page 4: ...h 2 pcs 4 Junction box 5 Bottom plate 6 Inlet cone 7 Impeller 8 Rain cover 9 Motor bracket 10 Support 1 2 pcs 11 Motor 2 4 8 7 10 5 6 3 11 9 1 Figure 2 Figure 3 1 6 8 9 5 10 3 2 4 9 8 7 3 Technical sp...

Page 5: ...in a cold climate it is recom mended to use back draught shutter in the duct This prevents the humidity from freezing within the fan structure 3 3 Motors Motors are either 1 or 3 phase external rotor...

Page 6: ...t Win Wout Weight 190 245 130 358 348 8 225 328 226 447 467 447 469 10 310 328 306 447 467 447 469 16 355 438 341 557 577 557 579 22 400 508 351 627 647 627 649 27 450 598 382 717 737 717 739 36 500 7...

Page 7: ...o 630 Figure 5 H out W out W in A 9 19 A A A A 38 5 H 3 4 Dimensions Horisontal version Fan size A A1 H Win Wout Hout Weight 190 245 216 345 480 7 225 328 261 447 480 10 310 328 340 447 480 14 355 438...

Page 8: ...ge to the product 4 2 Transport safety The transport material is to be selected according to the packaging and the weight of the product Loading must be carried out as instructed 4 3 Intermediate stor...

Page 9: ...lation with roof curb BOGA EI30 all versions size 225 onwards Figure 7 1 Install the sealing tape within the delivery on the roof curb 2 Lift the fan and place it on the roof curb see point 4 4 Please...

Page 10: ...he base frame 2 Place the mounting frame on the base frame and fasten it with four screws or with anchor bolts if the base frame is made of concrete There are four 12 mm holes for screws in the instal...

Page 11: ...include any inlet guard If the installation method requires inlet opening must be protected 5 3 Important to note during electrical connections All necessary electrical and other safety instructions...

Page 12: ...504101 TOP TOP GREY GREY t 5 6 7 8 TK TK 11 12 CC CC t OC OC t START STOP 230V AL N ALARM 230V PE Wiring diagram STOF AB BLACK U2 BLUE V2 BROWN W2 YELLOW WHITE GREEN GREY GREY t YELLOW GREEN M 3 STOF...

Page 13: ...EEN M 1 STOF 400 bEC 1cc 0 E4504105 PE PE 1 50 Hz 230 V COM NC GND BLUE GND 0 10V YELLOW 0 10V 10V RED 10V 0 1 5 6 7 8 Isolator SAFE 2 0 0 9 10 GND Ain 10V 10 k STYZ 01 51 0 1 Potentiometer ALARM RELA...

Page 14: ...50 Hz 400 V L3 0 1 5 6 7 8 Isolator SAFE 2 0 0 9 10 L1 L2 1 2 3 4 11 12 ALARM RELAY 2A max 250VAC KL1 10 k STYZ 01 51 0 1 BMS SYSTEM Potentiometer STOF 500 bEC 3cc 0 STOF 630 bEC 3cc 0 Wiring diagram...

Page 15: ...is installed correctly and according to the instructions Check that all necessary safety equipment is installed and can be used The fan shall only be started when all essential instructions are follo...

Page 16: ...n cannot fall down 7 Service 7 2 1 Maintenance cleaning of the impeller motor and fan casing uninsulated versions sizes 225 630 1 Switch off the fan from the isolator and wait 5 minutes before startin...

Page 17: ...ll be always be replaced as a package This package is available for size 400 and bigger In case of smaller fans the complete unit is to be replaced Open ductwork below the roof fan shall be covered to...

Page 18: ...to protect tools and other small parts from dropping into the duct 1 Switch off the fan from the isolator and wait 5 min before starting the maintenance work 2 Remove the roof and casings by loosening...

Page 19: ...Installation and Maintenance Roof Fan STOF 19 Fl kt Woods 9734 GB 2015 06 30 Specifications are subject to alteration without notice 8 Declaration of conformity...

Page 20: ...cturing of a wide range of products and solutions for Air Movement Air Treatment Air Distribution Air Management and Air Diffusion with focus on two major benefits Air Comfort and Fire Safety With mar...

Reviews: