Control System FICO-128
INSTALLATION, USE AND MAINTENANCE
21 Alarm codes and situations in FCLA-128 shown
in Alarm History
22 Systems with battery in equipment where
afterblow is required before fan is stopped
0=
USER: Log in
1=
USER: Log out
2=
USER: Wrong password
3=
System start
4=
Power failure
5=
Fire Alarm
6=
Service Alarm
7=
Damper failure
8=
External Alarm
9=
Interlock
10=
Comm Error
11=
Damper test
1
Go to
Log in
on the control unit using the arrow keys, and
then press
ENTER.
2
Log into the system using code 2000.
Use the arrow keys to select a number and press
ENTER
after each number. If your code was correct,
Login
level 2
is shown.
3
Press
ENTER.
4
Go to
Parameters
using the arrow keys, and then press
EN-
TER
.
5
Select
Damper delay
and press
EDIT
, use the arrow keys to set
the time (range 0...510 s) for which the dampers will remain
open after the activation of fan interlocking; press
ENTER
to
exit.
Important
! The afterblow time set in the equipment control sys-
tem shall be shorter than the one we are setting here.
6
Press
ESC.