GLEC-6 - Installation and maintenance
9
FläktGroup
DC-10087-GB 2018-01-03_R0
Specifications are subject to alteration without notice
If needed for easier motor and speed controller removal, the
back plate can be laid face down by detaching the self-drill-
ing screws from the standing skids, loosening standing skid
M8 bolts and turning the standing skids 90° to side. Standing
skids can also be completely removed.
When disassembling the front section, it could be useful to mark
part positions for easier reassembly.
9. Detach the cut-off by removing the M8 socket cap fixing bolts
from front plate and M8 bolts from side member.
Loosen standing skid bolt
11. Detach side members by removing the M8 bolts.
10. To detach the front plate, remove the M8 socket cap fixing
bolts from front plate and M8 bolts from both side members.
5.1.2 REASSEMBLING THE FAN
Note that there is a glass fiber sealing installed between panels,
side members and outlet connection. Remember to inspect the
glass fiber sealing from defects and replace if necessary.
Remember to check that the overlap is the same as measured
before and the inlet cone is precisely aligned with the impeller!
1. Reassemble the front section in reverse order. Insert all bolts,
but don’t tighten them yet.