TROUBLESHOOTING
PULL MASTER SWITCH ON, NO RED LIGHT
“NON-PROVEN”
TRY BLOWER SWITCH, IF BLOWER ENGAGES,
TURN POWER OFF & TEST RED “NON-PROVEN”
LIGHT CONTACT BLOCK. SHUT POWER OFF TO
HEATER, TEST OHMS RESISTANCE ACROSS
CONTACT BLOCK. IF OHMS RESISTANCE GOOD,
FAULTY BULB
IF BLOWER DOES NOT ENGAGE, CHECK OUTPUT
POWER ON TRANSFORMER, SHOULD BE 120
VOLTS. IF NO POWER, TURN POWER OFF AND
CHECK FU1 (5A)FUSE, IF GOOD, CHECK FB4 (.5 A)
FUSES FOR CONTINUITY
IF TRANSFORMER HAS PROPER OUTPUT POWER,
CHECK VFD SCREEN FOR COMMAND. SHOULD
READ “STOP” BEFORE COMMAND. LOOK FOR
FAULT CODES ON SCREEN. REFER TO VFD FAULT
MESSAGE CHART. YOU CAN ALSO CHECK OHMS
RESISTANCE ACROSS CONTACT BLOCKS ON
BACK OF BLOWER SWITCH. BLOCK WITH RED
WIRES-CONTACTOR CONTROL, BLOCK WITH
YELLOW WIRES- VFD CONTROL. ALWAYS HAVE
POWER OFF TO TEST OHMS