AIR VELOCITY

 

 
Air  velocity  is  critical  to  operation  of  the  unit  and  should 
not exceed 500 FPM. Do  not adjust drive to  exceed  this 
velocity. 
 
 

 
 
 
 
 

EXTERNAL STATIC 

These  units  are  not  normally  set  up  for  ducting.  Should 
ducting  be  necessary,  consult  the  factory  regarding 
blower and motor combinations. 
 

 

SIZING AND LOCATION

 

 

 
The  following  are  the  general  guidelines  for  sizing  and 
location of units. 
 

GENERAL AIR CLEANING

 

 
Sizing of equipment is based on the recirculation of clean 
air  in  the  contained  area.  Determine  the  total  cubic 
footage of the area to be cleaned. Determine the number 
of air changes that would be appropriate. This total is the 
actual CFM necessary. Divide this figure by the capacity 
of  the  SC  unit  that  will  be  used  and  this  determines  the 
number of units required. 

 
Example: 

Body Shop 
Desired air recirculation = 10 air changes/hr 
Size of room (L x W x H) = 100 x 75 x 20 ft 
Maximum CFM of SC-924 = 2100 CFM 
 
L x W x H X Air Changes/Hour  = Total CFM 
            60 
 
            Total CFM      = No. of units 
Maximum CFM of Air Cleaner  
 
150,000 x 10  = 25,000 CFM 
     60 
 
25,000  = 11.9 = 12 units 
 2,100 

 

In the example above, 12 units should be placed so that a 
uniform air flow pattern is developed. A good air flow will 
ensure good cleaning. 
 

 

MAINTENANCE SCHEDULE 

The  collecting  cell,s  ionizers,  prefilters  and  after  filters 
must be cleaned on a regular basis for the unit to function 
at its peak efficiency. The frequency of cleaning will vary 
from  one  environment  to  another.  For  instance,  in  a 

welding shop you may be required to wash the cell every 
3 days to 2 weeks depending on the work load of the unit.  
 
Every  environment  will  be  different.  Inspect  the  unit 
frequently until you determine the right washing schedule 
for your particular application. 

 

If your unit is equipped with an 

activated  carbon  filter 

it 

will  need  to  be  refilled,  depending  on  the  environment, 
every 3 - 6 months. Do not wash the carbon filter as this 
will render it useless. 
 
 

WASHING INSTRUCTIONS 

 
1.  Turn  both  the  fan  and  power  supply  switches 

OFF

 

and wait 15 seconds for high voltage to dissipate. 

2.  Open the cell access door and remove the collecting 

cells, ionizers, prefilters and after filters.  

3.  If  the  cell  plates  are  heavily  coated  it  may  be 

necessary to spray the cells with hot water to remove 
the  excess  contaminate  before  applying  detergent. 
Allow  excess  water  to  drain  off  the  cell  before 
applying detergent. 

4.  Place  the  cell  and  ionizer  in  a  tub  and  spray 

completely  with 

DAX  Detergent

,  allowing  detergent 

to run down both sides of the plates and ionizing fins. 
Let sit for 5 minutes. 

5.  Rinse  the  cell  well  with  hot  water  (140ºF  /  60ºC 

maximum). 

6.  If dirt remains on plates, let the cell soak in hot soapy 

water  for  30  minutes,  then  repeat  the  washing 
instructions listed above. 

Never use any instrument 

to clean the cell, as this may damage the ionizing 
wires or cell plates.

 

7.  An alternate method to clean the cell and ionizer is to 

soak them in a tub of Dax for 10-15 minutes. The Dax 
can be reused numerous times as long as the cell is 
kept from sitting in the sludge which will collect in the 
bottom of the tub. 

Never allow the cell or ionizer to 

sit longer than 15 minutes in the DAX or they will 
discolour. 

The  tub  should  be  covered  when  not  in 

use to prevent evaporation. 

CAUTION  

The cell plates are sharp. Handle with care. Take care 
not  to  damage  the  cell  by  hitting  the  cell  plates.  The 
cell plate spacing is critical for proper operation of the 
unit. 

CAUTION 

Avoid washing the cell or ionizer with a high pressure 
cleaner  as  this  may  cause  damage  to  the  cell  plates 
or fins. 

 

 

SC-924

 

Intake Velocity

 

 500 FPM

 

Discharge Velocity

 

2100 FPM

 

Internal Static

 

  .25 in WG

 

Summary of Contents for SC-924-1

Page 1: ...OPERATION MAINTENANCE MANUAL MODEL SC 924 1 SELF CONTAINED ELECTRONIC AIR CLEANER IMPORTANT PLEASE READ MANUAL BEFORE OPERATING UNIT ...

Page 2: ... is discharged through a 4 way directional defuser Weld nuts to accept 1 2 in threaded rods are incorporated into the cabinet top to facilitate hanging the unit PREFILTERS The washable prefilter measuring 16 x 20 in 40 6 x 50 8 cm is constructed of multi layers of aluminum mesh for maximum filtration of large particles AFTER FILTER The after filter measuring 16 x 20 in 40 6 x 50 8 cm is constructe...

Page 3: ...lication If your unit is equipped with an activated carbon filter it will need to be refilled depending on the environment every 3 6 months Do not wash the carbon filter as this will render it useless WASHING INSTRUCTIONS 1 Turn both the fan and power supply switches OFF and wait 15 seconds for high voltage to dissipate 2 Open the cell access door and remove the collecting cells ionizers prefilter...

Page 4: ... compressed air or vacuumed particularly around the cooling fan intake at the back of the motor CLEANING AND SERVICE The use of DAX Detergent is recommended for cleaning as it is a heavy duty solution used expressly for removal of accumulated pollutants on cell plates If used as directed DAX will not harm aluminum or steel if used as directed Any problem arising out of the use of another cleaning ...

Page 5: ......

Page 6: ......

Page 7: ...ses open circuit breakers or other damages due to the inadequacy or interruption of electrical service 5 Damage as a result of floods winds fires lightning accidents corrosive atmosphere or other conditions beyond the control of FIVE SEASONS COMFORT LIMITED 6 Parts not supplied or designated by FIVE SEASONS COMFORT LIMITED 7 FIVE SEASONS COMFORT LIMITED products installed outside the continental C...

Reviews: