Type 627F

5

To remotely vent the pilot, remove the vent and install 

obstruction-free tubing or piping into the 1/4 NPT 

vent tapping.  Provide protection on a remote vent by 

installing a screened vent cap into the remote end of 

the vent pipe. 
If the regulator requires repositioning, refer to the 

Body Area Maintenance procedures and/or the 

Diaphragm Case Area Maintenance procedures in 

the Maintenance section to reposition the regulator 

for the application.
The Type 627F regulator requires a downstream control 

line.  Install the control line before putting the regulator 

into operation.  Ensure that the downstream control 

line piping is at least 3/8 inch / 9.5 mm or larger outside 

diameter tubing and connected to a straight section of 

outlet piping several pipe diameters downstream of the 

regulator.  Connect the other end of the control line to 

the pilot side connection (marked “sense”).
The Type 627F regulator also requires inlet pressure to 

be piped to the pilot supply connection (see Figure 2).  

If the optional factory pilot supply piping

 

was not

 

selected, run a 3/8 inch / 9.5 mm outer diameter or 

larger supply line from the upstream pipeline or from 

the 1/4 NPT body tap (ductile iron body only) to the 

pilot inlet connection marked “in”.
Do not make the upstream pipeline connection in a 

turbulent area, such as near a nipple, swage, or elbow. 

To properly isolate the regulator, install a hand valve in 

the pilot supply line, and provide vent valves to relieve 

pressure from the regulator.

Overpressure Protection

!

WARNING

Personal injury, property damage, 

equipment damage, or leakage 

due to escaping gas or bursting of 

pressure-containing parts may result 

if this regulator is overpressured or 

is installed where service conditions 

could exceed the limits given in 

Specifications section or where 

conditions exceed any ratings of the 

adjacent piping or piping connections.
To avoid such injury or damage, provide 

pressure-relieving or pressure-limiting 

devices (as required by the appropriate 

code, regulation, or standard) to 

prevent service conditions from 

exceeding limits.

Additionally, physical damage to the 

regulator could cause personal injury or 

property damage due to escaping gas. 

To avoid such injury or damage, install 

the regulator in a safe location.

Startup and Adjustment

Startup

!

WARNING

To avoid personal injury or property 

damage due to explosion or damage to 

regulator or downstream components 

during startup, release downstream 

pressure to prevent an overpressure 

condition on the diaphragm of 

the regulator.
In order to avoid an overpressure 

condition and possible equipment 

damage, pressure gauges should 

always be used to monitor pressures 

during startup.

1.  Slowly open the upstream shutoff valves to the 

pilot and the regulator inlet.

2.  Slowly open the downstream shutoff valves to the 

pilot sense connection and the regulator outlet.

3.  Check all connections for leaks.
4. 

Make final pilot control spring adjustments 

according to the Adjustment procedures.  Standard 

factory setpoint is approximately mid-range of the 

pilot spring range.

Adjustment

The range of allowable pressure settings is marked 

on the pilot.  If a pressure setting beyond this range 

is necessary, substitute the appropriate pilot control 

spring.  Change the pilot stamping to indicate the new 

pressure range.  
The only adjustment necessary on a Type 627F 

regulator is the pressure setting of the pilot control 

spring.  Turning the pilot adjusting screw clockwise 

into the spring case increases the spring compression 

and pressure setting.  Turning the pilot adjusting screw 

counterclockwise decreases the spring compression 

and pressure setting.

Summary of Contents for 627F

Page 1: ...codes rules and regulations and Emerson Process Management Regulator Technologies Inc Regulator Technologies instructions If the regulator vents gas or a leak develops in the system service to the un...

Page 2: ...ure Capabilities 1 20 to 180 F 29 to 82 C Flow Coefficients See Table 4 IEC Sizing Coefficients See Table 5 Pressure Registration External Pilot Supply Connection 1 4 NPT Pilot Sense Connection 1 4 NP...

Page 3: ...FILTER FACTORY INSTALLATION OPTIONAL PILOT DIAPHRAGM LEVER VALVE DISK TYPE 6351F PILOT TYPE 627F REGULATOR MAIN REGULATOR DIAPHRAGM RESTRICTION BLEED FIELD INSTALLED DOWNSTREAM CONTROL LINE PILOT ADJ...

Page 4: ...n blown free of foreign debris 5 The regulator may be installed in any position as long as the flow through the body is in the direction indicated by the arrow cast on the body and both pilot openings...

Page 5: ...rvice conditions could exceed the limits given in Specifications section or where conditions exceed any ratings of the adjacent piping or piping connections To avoid such injury or damage provide pres...

Page 6: ...sional tolerances etc use only replacement parts manufactured or furnished by Fisher Instructions are given below for replacing the disk assembly orifice diaphragm and O rings These procedures may als...

Page 7: ...install on the stem key 10 4 Apply lubricant to the stem key 10 and insert the stem into the diaphragm casing key 5 and hook it on the lever key 15 5 Apply lubricant to the O ring key 7 and insert par...

Page 8: ...ot pounds 9 5 N m of torque 11 To change the tension spring remove the spring seat bolt key 61 from the tension spring key 32 and unscrew the spring retainer key 53 12 Install the tension spring key 3...

Page 9: ...le Parts List Type 627F Main Regulator Figure 3 Key Description Part Number Type 627F Parts Kit includes keys 4 7 9 11 12 13 23 55 and 63 Aluminum or Ductile iron casing R627FX00A12 Stainless steel ca...

Page 10: ...012 Medium Gain 17A2029X012 Low Gain 17A7277X012 Figure 3 Type 627F Main Regulator Assembly continued OPTIONAL PILOT SUPPLY TUBING TYPE 6351F PILOT TYPE 627F ACTUATOR 42B1863 D Type 627F Main Regulato...

Page 11: ...12 11 16 17 14 15 18 55 5 29 31 32 62 61 34 36 56 54 37 23 24 19 L1 L1 L2 L2 L2 L2 L2 APPLY LUBRICANT 1 L1 MULTI PURPOSE NLGI GRADE 1 GREASE L2 ANTI SEIZE COMPOUND 1 Lubricants must be selected such...

Page 12: ...on Process Management product remains solely with the purchaser Industrial Regulators Emerson Process Management Regulator Technologies Inc USA Headquarters McKinney Texas 75069 1872 USA Tel 1 800 558...

Reviews: