DO NOT DRAG the cooker. Lift
the feet clear of the floor.
Fig. 5c Incorrectly raising the cooker
Ventilation Requirements (GB & IE only)
The appliance should be installed in a room or space with an air supply in accordance with BS 5440-2:2000.
For rooms with a volume of less than 5 m3 : permanent ventilation of 100 mm3 free area will be required.
For rooms with a volume of between 5 m3 and 10 m3 : permanent ventilation of 50 cm3 free area will be required unless
the room has a door which opens directly to the outside air, in which case no permanent ventilation is required.
For rooms with a volume greater than 10 m3 : no permanent ventilation is required.
Regardless of room size, all rooms containing the appliance must have direct access to the outside
air via an openable window or equivalent.
Where there are other fuel burning appliances in the same room, BS 5440-2:2000 should be consulted to determine the
correct amount of free area ventilation requirements.