5 | Parameterization
FISCHER Mess- und Regeltechnik GmbH
46 / 88
BA_EN_EA16
b) Function: root extracted [Level 5]
Menu path: Main menu/Configuration/Inputs/Analogue input 1/Characteristic
curve/
Characteristic curve
Function: Rooted
Level 4
Level 5 (parameters)
1
5
Damping
1,000 sec
Input
Lin. input range
2
Rooted measur. range
3
Limit:
4
w
Sub menu
Sub menu
Fig. 66:
Menu Characteristic curve root extracted
The input characteristic curve can be switched to a root extracted characteristic
curve with the parameter value
<Function: root extracted>
. There are two addi-
tional submenues on the parameter level.
• In the
Submenu: Lin. input range [Level 6] [
the input range is configured according to the technical data of the sensor
that is used.
• In the
Submenu: Rooted measur. range [Level 6] [
the measuring range (start, end, unit) is configured.
Pos. Value range
Description
1
Function: Root extracted
The characteristic curve type ‚
root
squared
‘ is selected.
2
Lin. input range
Submenu for configuration of the linear in-
put range.
3
Root extracted measuring
range
Submenu for configuration of the root ex-
tracted measuring range.
4
Limits
Yes (standard value)
No
The display and output signal can be lim-
ited to the set measuring range (start - end)
with this parameter.
5
Damping
0.000 … 30.000 s
The input signal can be dampened with this
parameter.
Submenu: Lin. input range [Level 6]
Menu path: Main menu/ Configuration/ Inputs/Analogue input 1/Characteristic
curve: root squared/lin. measuring range/
Lin input range
Level 5
Level 6 (parameters)
1
Unit
Pa
Input
2
Measur. range start
-50,000 Pa
Input
3
Measur. range end
50,000 Pa
Input
4
Zero-point window
1,000 %
Input
Fig. 67:
Submenu: Lin. input range