background image

 

 

Water Supply 

This filter will function properly when the water supply is furnished by a jet pump, submersible pump, variable 
speed  (constant  pressure)  pump  or  community  water  supply.    As  with  all  other  filter  systems,  however,  it  is 
imperative  that  the  well  pump  provides  enough  flow  rate  for  the  filter  to  adequately  backwash.    In  order  to 
ensure sufficient backwash flow rate the following pumping rate test should be performed prior to installing the 
IBW/IMBW. 

1.  Make certain no water is being drawn in the house. 

2.  Open spigot nearest pressure tank. 

3.  When well pump starts, close spigot and measure time (in seconds) to refill pressure tank (well pump 

turns back off).  This is 

Cycle Time

 

4.  Using a container of known volume, draw water from pressure tank and measure how many gallons 

until the pump turns back on again.  This is 

Draw Down

 

5.  Calculate pumping rate by dividing draw down by cycle time and multiplying by 60. 

 

Draw Down 

(gallons)

 

X  60 

Pumping Rate (gallons per minute) 

Cycle Time

 (seconds)

 

Example: 

Draw down is 8 gallons 
Cycle time is 65 seconds 

 

 

Location Considerations 

The  proper  location  to  install  the  IBW/IMBW  will  ensure  optimum  filter  performance  and  satisfactory  water 
quality.  The following factors should be considered in selecting the location of this system. 

1.  The IBW/IMBW must be installed after the pressure tank (private well system only). 

 

2.  The system should be installed as close as possible 

(preferably within 15’) to an adequate floor or 

laundry  drain  capable  of  handling  the  backwash  cycle  volume  and  flow  rate  (refer  to  unit 
specifications).    An  air  gap  should  be  provided  between  the  IBW/IMBW  drain  line  and  plumbing 
drain. 

 

3.  All water conditioning equipment should be installed 

at least 10’ prior to the water heater.  Water 

temperatures exceeding 100°F can damage the internal components of the control valve and filter 
tank. An expansion tank may need to be installed in the line to the water heater in order to allow for 
thermal expansion and comply with local plumbing codes. 
 

4.  Water pressure must not exceed the range of 25 - 100 psi. 

 

5.  The system must not be subject to freezing temperatures. 
 
6.  The control valve requires 115/120 V, 60 Hz electricity from an outlet that is not wired to a switch. 

 

7.  Never install a cartridge type filter prior to the IBW/IMBW.  Any cartridge or in-line filter (if desired) 

may  be  installed  after  the  IBW/IMBW  system.    This  will  prevent  restricting  the  water  flow  and 
pressure available for backwash. 

 

8.  Appliances requiring extended periods of continuous or high flow water use (i.e. geothermal heat 

pumps, swimming pools, lawn irrigation, outside hose bibs, etc.) should bypass the filter.   

 

8 gallons

 

  X  60  = 

7.4

 gpm  (gallons per minute) 

65 seconds

 

Pre-installation Instructions (cont.) 

Summary of Contents for IBW10-1

Page 1: ...s LLC 12630 US Highway 33 N Churubusco IN 46723 Phone 260 693 1972 Fax 260 693 0602 IBW IMBW Instruction Manual 170605 docx IBW IMBW Series Backwashing Filter System Installation Instructions and Owne...

Page 2: ...tions Page 6 Operating Displays Page 10 Maintenance Page 11 Troubleshooting Guide Page 13 Specifications Page 16 Component Parts Breakdown Page 17 Component Parts List Page 18 Control Valve Breakdown...

Page 3: ...ALIZER 0 50 PAIL 45 FA10 FILTER AG SUSPENDED SOLIDS REDUCTION 1 00 BAG 24 FA05P 0 50 PAIL 12 N05 NEUTRALIZER ACID NEUTRALIZER 0 50 PAIL 43 QFS05P QUARTZ FILTER SAND 0 50 PAIL 51 45mm x 55mm SEDIMENT R...

Page 4: ...f this system 1 The IBW IMBW must be installed after the pressure tank private well system only 2 The system should be installed as close as possible preferably within 15 to an adequate floor or laund...

Page 5: ...ed If necessary pliers can be used to unscrew the nut or cap Do not use a pipe wrench to tighten nuts or caps Do not place screwdriver in slots on caps and or tap with a hammer NOTE If the plumbing sy...

Page 6: ...regeneration cycle this position provides regeneration water to the unit while also providing untreated water to the distribution system Fig 2 2 Bypass Position The inlet and outlet handles point to...

Page 7: ...rivate well system turn off power to pump and drain pressure tank Make certain pressure is relieved from complete system by opening nearest faucet to drain system SHUT OFF FUEL ELECTRICAL SUPPLY TO WA...

Page 8: ...There must be an air gap at the end of the drain line to prevent siphoning of waste water AVOID OVERHEAD DRAINS AND DRAIN LINE LONGER THAN 15 STEP 10 MAKE SURE THE BYPASS VALVE IS IN THE BYPASS POSIT...

Page 9: ...y will show SET b The lower left of the display will show REGEN above and DAY below c A number will flash default 3 2 Using the UP or DOWN triangle pointing up or down buttons set the number of days d...

Page 10: ...pass valve counter clockwise until it is fully in the Service position Figure 2 Page 5 and leave the control valve in Backwash position for at least 10 minutes or until water flowing from the drain li...

Page 11: ...and will reset itself to provide treated water when the regeneration has been completed 3 Manual Regeneration Sometimes there is a need to regenerate before the control valve calls for it This may be...

Page 12: ...e from the electrical outlet to prevent it from advancing automatically 3 Disconnect the Control Valve from the Bypass Valve 4 Disconnect the Drain Line from the Control Valve 5 Unscrew Control Valve...

Page 13: ...ce the air is purged gradually turn the INLET knob of the bypass valve counter clockwise until it is fully in Service position Figure 2 Page 5 Then turn the OUTLET knob of the bypass valve counter clo...

Page 14: ...butor tube not seated properly in control valve D Water usage flow rate exceeds filter specifications 1 Verify bypass valve is in service position 2 Replace piston and seal assemblies 3 Verify distrib...

Page 15: ...trol valve 1 Ensure electrical outlet is functioning 2 Disassemble and clean control valve 3 Replace seals and or piston Filter backwashes at wrong time of day A Clock is not set properly B Power outa...

Page 16: ...oken wires verify motor plugged into connector J1 labeled MOTOR on control valve circuit board and reset control valve hold NEXT and REGEN buttons for 3 seconds 2 Remove piston and seal assemblies for...

Page 17: ...area 3 3 4 5 Peak 18 gpm ft 2 of media surface area 10 10 14 17 Backwash 10 gpm ft 2 of media surface area NOTE some medias may require a higher backwash rate 5 3 5 3 7 5 9 Service Pipe Size in Standa...

Page 18: ...17 3 1 4 5 6 2 Component Parts Breakdown...

Page 19: ...butor Tube 1 x 54 for model IBW15 IBW25 IMBW15 IMBW25 4 MTP1044N 10 x 44 Mineral Tank Nat Base 2 5 Top Opening For model IBW10 IMBW10 MTP1054N 10 x 54 Mineral Tank Nat Base 2 5 Top Opening For model I...

Page 20: ...19 Control Valve Breakdown...

Page 21: ...215 12 CV3177 01 Injector Screen 13 CV3010 1Z Plug Injector Assembly 15 CV3150 Retainer Split Ring 16 CV3151 Nut 1 Quick Connect 17 CH4615 Clip Elbow Locking 18 CV3163 O ring 019 19 CV3165 01 Retainer...

Page 22: ...plit ring 2 3 CV3105 O ring 215 2 3 CV3105 O ring 215 2 4 CV3149 Fitting 2 4 CV3189 Fitting 2 1 BRASS SWEAT 3 4 BRASS SWEAT Ref Part Description Qty Ref Part Description Qty CV3007 02 1 brass sweat as...

Page 23: ...ck connect 2 1 CV3151 Nut 1 quick connect 2 2 CV3150 Split ring 2 2 CV3150 Split ring 2 3 CV3105 O ring 215 2 3 CV3105 O ring 215 2 4 CV3628 Fitting 2 4 CV3629 Fitting 2 1 1 4 PLASTIC MALE NPT Ref Par...

Page 24: ...4 QUICK CONNECT 1 2 required SERVICE WRENCH CV3193 Although no tools are necessary to assemble or disassemble the valve the Service Wrench shown in various positions on the valve is available to aid i...

Page 25: ...24...

Reviews: