Summary of Audible Notification 

(Alpha Display Keypads) 

SOUND CAUSE 

DISPLAY 

LOUD, 

INTERRUPTED* 

 Keypad 

External 

FIRE ALARM

 

FIRE

 is displayed; descriptor of zone in alarm is 

displayed.

 

LOUD, 

CONTINUOUS* 

 Keypad 

External 

BURGLARY/AUDIBLE EMERGENCY 

ALARM  

ALARM 

is displayed; descriptor of zone in alarm is 

also displayed. 

ONE SHORT BEEP 
 (not 

repeated) 

Keypad only 

a. SYSTEM DISARM   
b. SYSTEM ARMING ATTEMPT 

WITH AN OPEN ZONE. 

c.  BYPASS VERIFY  

a. 

DISARMED/READY TO ARM 

is displayed.  

b. The number and descriptor of the open protection 

zone is displayed. 

c.  Numbers and descriptors of the bypassed 

protection zones are displayed (One beep is heard 
for each zone displayed). Subsequently, the 
following is displayed: 

DISARMED BYPASS Ready 

to Arm

 

ONE SHORT BEEP 
  (once every 15 

sec.) Keypad only 

SYSTEM IS IN TEST MODE 

Opened Zone identifications will appear. 

TWO SHORT BEEPS 
  (once every 5 sec.) 

Keypad only 

SYSTEM IS ABOUT TO 

AUTOMATICALLY EXIT TEST 
MODE 

Opened Zone identifications will appear. 

ONE BEEP 
  (every 60 sec.)  

Keypad only 

LOW BATTERY AT A TRANSMITTER 

LO BAT 

displayed with description of transmitter.

 

TWO SHORT BEEPS 
  Keypad only  

ARM AWAY OR MAXIMUM     

ARMED AWAY or ARMED MAXIMUM

 is displayed. 

Red ARMED indicator is lit. 

THREE SHORT 

BEEPS 

 Keypad 

only 

a. ARM STAY OR INSTANT   
b. ZONE OPENED WHILE SYSTEM 

IS IN CHIME MODE.   

c. ENTRY WARNING** 

a. 

ARMED STAY ZONE BYPASSED

 or 

ARMED 

INSTANT ZONE BYPASSED 

is displayed. Red 

ARMED indicator is lit. 

b. 

CHIME 

displayed, descriptor of open protection 

zone will be displayed if the [

] key is pressed. 

c. 

DISARM SYSTEM OR ALARM WILL OCCUR

 is 

displayed. 

RAPID BEEPING  
 Keypad 

only 

a. TROUBLE   
b. AC POWER LOSS ALERT*** 
c.  MEMORY OF ALARM  

a. 

CHECK

 displayed.  Descriptor of troubled 

protection zone is displayed. 

b. 

AC LOSS

 displayed (may alternate with other 

displays that may be present). 

c. 

FIRE 

or 

ALARM 

is displayed; descriptor of zone in 

alarm is displayed.  

SLOW BEEPING  
 Keypad 

only 

a. ENTRY DELAY WARNING**  
b. EXIT DELAY WARNING  
 (if 

programmed) 

a. 

DISARM SYSTEM OR ALARM WILL OCCUR

 is 

displayed. Exceeding the delay time without 
disarming causes alarm.  

b. 

ARMED AWAY 

or 

ARMED MAXIMUM

 is displayed 

along with 

You May Exit Now

 

If bell is used as Notification Appliance, fire alarm is pulsed ring; burglary/audible emergency is steady ring.  

**  Entry warning may consist of three short beeps or slow continuous beeping, as programmed by your installer. 
***  Loss of system battery power is not indicated or annunciated by the keypad (warnings are for loss of AC power only).  

Summary of Contents for FA1670C

Page 1: ...7 7 70 0 0 0 0 0 0 0C C C C C C C C F F F F F F F FA A A A A A A A1 1 1 1 1 1 1 17 7 7 7 7 7 7 70 0 0 0 0 0 0 00 0 0 0 0 0 0 0C C C C C C C C Commercial Fire and Burglary Commercial Fire and Burglary...

Page 2: ...2...

Page 3: ...CCESSING OTHER PARTITIONS 23 To Access another Partition 23 Global Arming 23 Master Keypad Operation 24 Common Lobby Operation 26 How User Codes Affect the Common Lobby 27 CHECKING FOR OPEN ZONES 28 U...

Page 4: ...o Display The Event Log 55 TESTING THE SYSTEM TO BE CONDUCTED WEEKLY 57 Using the 5 TEST Key 57 Testing Your System 57 FIRE ALARM SYSTEM 58 In Case Of Fire Alarm 58 Silencing a Fire Alarm 58 Event Dis...

Page 5: ...provides appropriate information for display on the Keypad s used with the system and initiates appropriate alarms Your system may also have been programmed to automatically transmit alarm or status...

Page 6: ...on The burglary protection portion of your system must be turned on or armed before it will sense burglary alarm conditions Your system provides four modes of burglary protection STAY AWAY INSTANT and...

Page 7: ...ing the alarm If your system is connected to a central monitoring station an alarm message will also be sent To stop the alarm sounding simply disarm the system Memory of Alarm When an alarm condition...

Page 8: ...em functions in another partition by using the GOTO command Note that only those partitions authorized and programmed by the installer can be accessed in this manner To GOTO another partition enter yo...

Page 9: ...manual is not conveniently accessible when you need to perform a system procedure with which you are not familiar To view the abbreviated instructions Simply press and hold down the function key of i...

Page 10: ...at will sound during alarms and troubles It will also beep during certain system functions such as during entry exit delay times during CHIME mode and when depressing keys to perform system functions...

Page 11: ...ROUBLE ALARM SUPV POWER 6160CR2 003 V0 ARMED READY R Primary Fire Keypad FA570CR IMPORTANT When using the keypad to enter codes and commands sequential key depressions must be made within 3 seconds of...

Page 12: ...STAY 1 OFF 2 B D C A AWAY ARMED READY R Burglary Keypad FA570KP IMPORTANT When using the keypad to enter codes and commands sequential key depressions must be made within 3 seconds of one another If...

Page 13: ...ing an alarm Late arrivals can enter through an entry delay zone without causing an alarm if the system is disarmed before the entry delay time expires See ARMING PERIMETER ONLY for a full explanation...

Page 14: ...d while unlit indicates system not ready LED ARMED INDICATOR RED Lit when the system has been armed STAY AWAY INSTANT or MAXIMUM LED POWER INDICATOR GREEN Lit when AC power is applied to the system LE...

Page 15: ...slow beeping will sound throughout the exit delay period Entry Delay gives you time to disarm the system when you reenter through the designated entrance door But the system must be disarmed before th...

Page 16: ...ithin the limits of each code s authority level a system armed with one user s code can be disarmed by another user s code with the exception of the Operator Level C code See Authority Levels paragrap...

Page 17: ...erator level users Level 3 Operator A Can perform system functions in assigned partitions but cannot add or delete other users Level 4 Operator B Same as Operator A except Operator B cannot bypass zon...

Page 18: ...er can only be DELETED or CHANGED from within the partition he is assigned User numbers must be entered as 3 digit entries Single digit user numbers must be preceded by a 00 example 003 004 etc Securi...

Page 19: ...existing user s code to the code entered in step 3 See Changing A User s Code section USER NUMBER 003 ENTER AUTH LEVEL Enter the authority level 1 6 for this user within this partition 1 master 2 man...

Page 20: ...Again press 0 or 1 If yes the system will automatically assign a user number for use in that partition and will prompt for authority level and global arm options for this user within the partition see...

Page 21: ...er number is already in use and will prompt whether or not this is a new user Enter 0 to change the existing user s code to the code entered in step 3 USER 002 CHANGED SUCCESSFULLY The system will con...

Page 22: ...y in use and will prompt to confirm that it should be deleted Press 0 NO or 1 YES USER CODE DELETED If yes that user s code will be removed from all partitions to which it was assigned and all authori...

Page 23: ...until 2 minutes have elapsed with no keypad activity AAAA alpha descriptor programmed by the installer X partition number Global Arming The Global Arming option may be assigned for use by some users...

Page 24: ...the need for a security officer in a building to have to log on to various partitions from one partition s keypad to find out where an alarm has occurred A description of a typical display follows SYS...

Page 25: ...be displayed one at a time To display a new partition s status press Partition No This will display the status of the new partition The Armed LED on a Master keypad will be lit only if all partitions...

Page 26: ...fects the lobby is disarmed the lobby will also be disarmed b The common lobby cannot be armed unless every partition selected to affect the lobby is armed c Arming the last partition that affects the...

Page 27: ...titions you have access to and another affecting partition is disarmed one you do not have access to you will not be able to arm the lobby and the message UNABLE TO ARM LOBBY PARTITON will be displaye...

Page 28: ...ome keypads light a green LED when the system is ready If not lit the system is not ready to be armed READY 1 Do not enter security code but simply press FAULT 005 FRONT UPSTAIRS BEDROOM Typical fault...

Page 29: ...eviated instructions for the READY key will appear first followed by the zone descriptors Displaying all descriptors is useful when you need to know the zone number of a particular zone as when bypass...

Page 30: ...mergency zones to be bypassed To bypass zones the system must be disarmed first BYPASS 1 Enter your security code and press 6 2 Enter zone number s for the zones to be bypassed e g 001 002 003 etc IMP...

Page 31: ...s will be displayed along with the word BYPASS Wait for these zones to be displayed before arming Arming the system before bypassed zones are displayed eliminates all bypasses 3 DISARMED BYPASS READY...

Page 32: ...abled for group bypassing Access to the partition s containing the zones being bypassed Global arming capability To use the Group Bypass feature BYPASS 1 Enter your security code and press 6 then pres...

Page 33: ...STAY mode 3 when activated automatically bypasses all zones assigned to STAY modes 1 AND 2 Check with your installer for a list of the zones that are bypassed during each STAY mode Close all perimeter...

Page 34: ...es an option to set each burglary zone for Auto stay All zones enabled for auto stay except for perimeter and day night types of zones has exit delay time when the partition is armed Check with your i...

Page 35: ...zones assigned to INSTANT modes 1 and 2 Check with your installer for a list of the zones that are bypassed during each INSTANT mode Close all perimeter windows and doors before arming see CHECKING F...

Page 36: ...rance door during the exit delay period without causing an alarm You may also reenter through the entrance door but must disarm the system within the entry delay period or an alarm will occur Close al...

Page 37: ...opened or if any movement is detected inside the premises You may leave through the entrance door during the exit delay period without causing an alarm but an alarm will be sounded as soon as someone...

Page 38: ...exit the armed partition without having to disarm and then rearm the partition To Quick Exit the premises 1 Press the key and then press the 9 key 2 The system will sound the exit beeps if enabled an...

Page 39: ...the system and silence burglary or fire alarms OFF 1 Enter your security code and press 1 DISARMED READY TO ARM 2 The Ready message will be displayed if no alarms have occurred while armed and the ke...

Page 40: ...e Rapid Flashing Memory of alarm indicating an alarm has occurred Arming To arm in the AWAY mode turn the key to the right for 1 second and release Keypads will beep twice and the red light will stay...

Page 41: ...only when the system is disarmed 1 To turn Chime Mode on enter the security code and press 9 CHIME MODE ON The CHIME MODE ON message will appear for about 2 seconds then disappear To display this mess...

Page 42: ...oring agency or installer When a message is waiting to be viewed the message shown below will appear MESSAGE PRESS 0 FOR 5 SECS 1 Press and hold down 0 key for 5 seconds 2 The message could take up to...

Page 43: ...ess both keys of the assigned pair at the same time If your keypad s have lettered keys for panic functions press the designated key and hold down for at least 2 seconds to activate the panic function...

Page 44: ...using a relay so that a door such as in a lobby can be unlocked momentarily using a keypad command Ask your installer if this has been done in your system Executing To activate the relay enter your s...

Page 45: ...ay have restricted the use of this function Please check with your installer ENTER DEVICE NO 00 QUIT 01 Enter the 2 digit number of the device to be activated Note that if an invalid number is entered...

Page 46: ...IMPORTANT The selected delay cannot be reduced once it is set A 1 hour delay can be increased to 2 hours though 4 The system will automatically send a message to the central station informing them tha...

Page 47: ...y s disarm window Enter the desired hour Press to move to the minutes field The minutes are entered in the same manner The AM PM indication is changed by hitting any key 0 9 while the cursor is under...

Page 48: ...the desired number 1 7 Monday 1 An X will appear under that day indicating the previously entered schedule for that day is active Entering a day s number again will deactivate that day Pressing 0 will...

Page 49: ...the same device For example timer 2 could be used Monday Friday as in the previous example and timer 3 could be set to turn the air conditioner on and off at different times Saturday and Sunday To ent...

Page 50: ...nter 00 00 if this timer is not being used to turn something OFF for the days selected below Ex using one timer to turn lights on one day and using another timer to turn them off on another day 00 DAY...

Page 51: ...le You can initiate a random schedule by either of the following methods 1 Enter your security code and press followed by 41 This will randomize up to 30 minutes the activation time of all devices pro...

Page 52: ...lay Group Close XX minutes Relay Group 10 Relay Group Close YY seconds Relay Group Check with your installer for the amount of time Arm Disarm Commands Activation times 1 Beginning 2 End and 3 During...

Page 53: ...rtition Partition s 41 Enable Closing Window by partition Partition s 42 Enable Access Window for access group Access Group Access Control Commands Action Code Action Specifier 55 Access Point Grant A...

Page 54: ...e when either the system exits the 77 Mode or the scheduled time is reached depending on the action selected Press to continue Enter the action specifier This defines what the action will affect relay...

Page 55: ...ying the COMPLETE log or only those events occurring since the last installer service RECENT In addition events in the other partitions can be viewed by users authorized to access those partitions Not...

Page 56: ...OG TYPE CCC UUU Typical Category Select Screen ALARM EVENT LOG Displays time and date for zones which have either caused an alarm or have been restored in the selected partition CHECK EVENT LOG Displa...

Page 57: ...cally exit the Test mode if there is no activity no doors or windows are opened and closed no motion detectors are activated etc for 60 minutes The system will beep the keypad s twice every 5 seconds...

Page 58: ...and notify your local Fire Department immediately 4 If no flames or smoke are apparent investigate the cause of the alarm The descriptor of the zone s in alarm appears at the keypad Silencing a Fire A...

Page 59: ...only be activated by the installer or a master user from Partition 1 keypads as follows 1 Enter the corresponding security code and press 69 make sure the burglary portion of the system is disarmed K...

Page 60: ...by a display of 6XX where XX 01 32 indicates a trouble on a supervised relay corresponding relay number 01 32 CHECK or TRBL display accompanied by a display of 8XX where XX 00 30 indicates a trouble o...

Page 61: ...ntrol will not operate while on line A display of HSENS and a zone number indicates a smoke detector with a high sensitivity level which may cause false alarms CALL FOR SERVICE IMMEDIATELY A display o...

Page 62: ...an be used to escape Indicate escape routes for each room Keep these routes free from obstruction and post copies of the escape routes in every room 4 Assure that all fire doors are shut while you in...

Page 63: ...in most units and applications provide 2 4 years of service Actual battery life will depend on the environment in which the sensor is used the number of signals that the transmitter in the sensor has...

Page 64: ...to turn off If the sensor is not activated the display will automatically clear within approximately 1 hour Routine Care Treat the components of your security system as you would any other electrical...

Page 65: ...keypad but may or may not silence the fire bells depending on system programming A second User Code 1 OFF sequence may be required The Silenced LED on the FA570CR keypad will light Resetting Alarms T...

Page 66: ...windows are violated while system disarmed Test Mode Enter code Press TEST 5 Activates alarm sounder and allows sensors to be tested View Messages Press and hold 0 for at least 5 seconds Message from...

Page 67: ...ress Enter 71 or 72 Activate output device as programmed Enter security code Press Enter 70 Activate output device manually Control Output Device Enter security code Press Enter 77 Activate output dev...

Page 68: ...MAXIMUM ARMED AWAY or ARMED MAXIMUM is displayed Red ARMED indicator is lit THREE SHORT BEEPS Keypad only a ARM STAY OR INSTANT b ZONE OPENED WHILE SYSTEM IS IN CHIME MODE c ENTRY WARNING a ARMED STA...

Page 69: ...is connected Consult the dealer or an experienced radio TV technician for help INDUSTRY CANADA IC STATEMENTS This device complies with RSS210 of Industry Canada Operation is subject to the following...

Page 70: ...cal the telephone company will notify the customer as soon as possible Also you will be advised of your right to file a complaint with the FCC if you believe necessary The telephone company may make c...

Page 71: ...e tiquette certifie que le mat riel est conforme certaines normes de protection d exploitation et de s curit des r seaux de t l communications Le minist re n assure toutefois pas que le mat riel fonct...

Page 72: ...injury or death Passive Infrared Motion Detectors can only detect intrusion within the designed ranges as diagrammed in their installation manual Passive Infrared Detectors do not provide volumetric a...

Page 73: ...Change a User s Code 21 Change User Code 18 CHECK 60 Chime 6 41 Closing Time 46 Comm Failure 61 Common Lobby 26 Delaying Closing Time 46 Delete a User 22 Delete User Code 18 Descriptors 29 Device Time...

Page 74: ...ndomize Output Devices 51 Ready 28 READY 41 Ready Key 28 Relay commands 52 Relay Menu Mode 45 Replacing Batteries 63 RF BUTTON 19 Routine Care 64 Schedules 7 46 Security Code 16 Security Codes 16 Sens...

Page 75: ...URPOSE OR OTHERWISE WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF IN NO CASE SHALL SELLER BE LIABLE TO ANYONE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRA...

Page 76: ...NOTES...

Page 77: ...NOTES...

Page 78: ...NOTES...

Page 79: ...NOTES...

Page 80: ...Copyright 2009 Honeywell International Inc www firstalertprofessional com 2 Corporate Center Drive Suite 100 P O Box 9040 Melville NY 11747 K0377 1V2 K0377 1V2 7 09 Rev A...

Reviews: