8
© 2020 Carrier
FIGURE 4.
High Energy Power Pack.
SPARK ROD
In most applications, the HESI spark rod fits into a guide tube that houses the spark rod assembly.
Observe the following steps for installing the spark rod assembly:
1.
Carefully insert the spark tip into the guide tube until the spark rod extends into the primary
ignition zone. As a general guideline, with gas igniters position the spark tip flush with the front
of the baffle plate (Fig. 5). With oil igniters, position the spark tip 3 to 4 inches past the oil gun
tip (Fig. 6).
2.
When a retraction assembly is supplied, exercise the retract cylinder, either manually or auto-
matically, in the extend and retract positions to check for correct operation.
3.
Once the tip penetration is set, attach and tighten the locking device to the spark rod.
FIGURE 5.
LOCATION OF SPARK TIP IN GAS IGNITE
SPARK TIP