1
FIREYE
MODULAR
MicroM
FLAME SAFEGUARD CONTROLS
WARNING: Selection of this control for a particular application should be made by a com-
petent professional, licensed by a state or other government. Inappropriate application of this
product could result in an unsafe condition hazardous to life and property.
DESCRIPTION
The Fireye MicroM Series Flame Safeguard Control is a compact, microprocessor based, modular
burner management system designed to provide automatic ignition and continuous flame monitoring
for commercial sizes of heating and process equipment firing any type of fuel.
The MicroM is designed to be backward compatible with existing TFM, UVM and M-Series II con-
trols. The MicroM MC120 and MEC230 chassis with the appropriate MEP100, MEP200 and
MEP500 series programmers provide operation similar to its predecessors and is usually directly
interchangeable. The MEC320 and MEC480 chassis with the appropriate MEP300, MEP400 and
MEP600 series programmers provide additional enhancements such as early spark termination, pilot
proving, and interrupted pilot.
The advantages of the MicroM are zero dependence on discrete components previously used for tim-
ing functions. The MicroM, through the use of micro-controller technology, incorporates smart diag-
nostic LED's, smart reset function for multi-burner applications, optional alpha-numeric display
output (ED510), and serial communications via a Modbus or E500 Communication Interface. The
MicroM system also provides additional amplifier selections. Along with the standard UV and Flame
Rod/Photocell amplifiers are UV self-check, Infrared, Cadmium Sulfide and a dry contact amplifier
for use with the Fireye Phoenix scanner. All amplifiers are available with flame failure response
times of 0.8 seconds or 3 seconds nominal (4 second maximum) and each provide a set of test jacks
with a uniform range of 0-10 VDC for the measurement of flame signal intensity.
A complete MicroM system includes the appropriate flame detector, plug-in amplifier and program-
mer modules which connect into a standard chassis and wiring base. Interchangeable programmer
and amplifier modules allow for complete versatility in selection of control function, timing and
flame scanning means. Functions such as relight, recycle, non-recycle, two stage capability, non-
recycle air flow, proof of air flow open at start, purge timing, early spark termination, pilot proving
and pilot cutoff are determined by the appropriate programmer module. Type of flame scanner (UV,
Repetitive UV Self-Check, Flame Rod, Photocell, IR or Cadmium Sulfide or dry contact) and the
flame failure response time (FFRT) are determined by the amplifier module. Optional plug-in daugh-
ter boards provide additional features such as remote reset, alpha-numeric display and serial commu-
nications.
The MicroM programmers are micro-controller based modules that control the sequence of opera-
tion and also interface with plug-in amplifiers, meter boards, display drivers and external communi-
cation devices. The programmers are available in an assortment of configurations necessary to
MC-5000
OCTOBER 2003
UL
APPROVED
LISTED
C
US