8

3.

The temperature sensors require 2 conductor, 18 gauge, shielded cable. Power limited, rated for
300V @105C. Use Belden 9318 or equivalent.

4.

The shield should be connected to the earth ground terminal on the wiring base of the Burner-
Logix Control (Terminal #E) or to the common ground established in the cabinet. The shield
should be taped at the sensor to avoid unintended contact with the sensor housing.

5.

All sensor wiring should be in a separate conduit. DO NOT install sensor wiring in any conduit
or junction boxes with high voltage wiring.

6.

Maximum wiring distance for sensor wiring is 100 feet.

7.

SeeTable 1 and 2 for wiring terminations.

Table 1:  Burnerlogix wiring connections

Table 2: PPC4000 wiring connections

NOTICE

When Fireye products are combined with equipment manufactured by others and/or integrated into
systems designed or manufactured by others, the Fireye warranty, as stated in its General Terms and
Conditions of Sale, pertains only to the Fireye products and not to any other equipment or to the
combined system or its overall performance.

WARRANTIES

FIREYE guarantees for 

one year from the date of installation or 18 months from date of manufacture

of its products to replace, or, at its option, to repair any product or part thereof (except lamps and
photocells) which is found defective in material or workmanship or which otherwise fails to conform
to the description of the product on the face of its sales order. 

THE FOREGOING IS IN LIEU OF

ALL OTHER WARRANTIES AND FIREYE MAKES NO WARRANTY OF MERCHANT-
ABILITY OR ANY OTHER WARRANTY, EXPRESS OR IMPLIED.

 Except as specifically

stated in these general terms and conditions of sale, remedies with respect to any product or part
number manufactured or sold by Fireye shall be limited exclusively to the right to replacement or
repair as above provided. In no event shall Fireye be liable for consequential or special damages of
any nature that may arise in connection with such product or part.

TS350/TS752

BLPS

PCV

AUX1

AUX2

Minco

Meas Sp

Temp Sp

BurnerLogix Terminals

1+

1+

6+

+ EXC

X (WHT/BLU)

X (WHT/BLU)

X (WHT/BLU)

2-

2-

7-

- COM

11 (WHT/GRN)

22 (WHT/VIO)

23 (BRN/WHT)

TS350/TS752

BLPS

PCV

AUX1

AUX2

SENS4

SENS5

Minco

Meas Sp

Temp Sp

PPC4000 Terminals

1+

1+

6+

+ EXC

P11.2

P11.2

P11.3

P11.3

P11.3

2-

2-

7-

- COM

P11.10

P11.9

P11.8

P11.7

P11.6

CAUTION: PROGRAM AND SET-UP

The proper operation of the BurnerLogix System and the pressure and temperature sen-
sors requires that the selected pressure ranges are appropriate for the application and
must match the pressure range programmed on the BurnerLogix Control. Insure that the
range of the selected sensor is correct for the application and the pressure range pro-
grammed on the BurnerLogix Integrated Flame Safeguard and Boiler Controller matches
the installed pressure sensor. Refer to Bulletin BLZ-1001.

FIREYE

BLZPTS-1

3 Manchester Road

NOVEMBER 19, 2013

Derry, New Hampshire 03038 USA

Supersedes November 6, 2013

www.fireye.com

Summary of Contents for BLPS-25

Page 1: ...rature Sensors have a 1 2 NPT mounting for the 2 4 and 8 thermowell probe The pressure and temperature sensors provide a 4 20 mA control signal over their respec tive stated ranges to the PPC4000 and BurnerLogix Control systems No setting or calibra tion is required for either type of sensor The PPC4000 and BurnerLogix Control systems perform continuous safety checks on the operation of all pressu...

Page 2: ...ns and conduit adapter cover BLPS 200 Pressure transducer 0 to 200 psi 0 to 13 8 Bar 4 20 mA output linear with pressure NPT mount ing Screw terminal connections and conduit adapter cover BLPS 300 Pressure transducer 0 to 300 psi 0 to 20 7 Bar 4 20 mA output linear with pressure NPT mount ing Screw terminal connections and conduit adapter cover TS350 2 Temperature sensor Range 32 F to 350 F 0 C to...

Page 3: ...7 Controls Primary Safety Component MCCZ7 File MP1537 Controls Primary Safety Certified for Canada MCCZ8 File MP1537 Controls Primary Safety Certified for Canada Component Factory Mutual FM Class 7610 Acceptable by Industrial Risk Insurers I R I FIGURE 1 Pressure Sensor BLPS 15 25 30 200 300 COM OUT GND EXC ...

Page 4: ...ored pressure or sensor should fall between 40 70 of the upper range of the sensor For example a steam boiler maintains 20 lbs pressure select the BLPS 30 Pressure Sensor with a 0 30 PSIG range 3 The sensors must be located where the ambient temperature will not exceed the maximum ambient operating temperature specified for the sensor 4 Insure that the pressure range programmed on the BurnerLogix ...

Page 5: ...he fitting and prevent proper operation of the sensor 9 Make all pipe connections in accordance with approved standards 10 When tightening the sensor apply a wrench to the hex flats located just above the pressure fit ting DO NOT tighten by using a pipe wrench on the housing Do not tighten the pressure sensor by hand MOUNTING TEMPERATURE SENSORS The immersion style temperature sensors have a NPT m...

Page 6: ...sensor if provided by the boiler man ufacturer 2 If no well connection is provided select an appropriate location for mounting the temperature sensor Preferably as close to the boiler outlet as possible OUTDOOR AIR TEMPERATURE 1 The outdoor air temperature sensor should be mounted on the outside of the building where it will be exposed to representative air temperature but not to direct sunlight A...

Page 7: ... separate conduit DO NOT install sensor wiring in any conduit or junction boxes with high voltage wiring 6 Maximum wiring distance for sensor wiring is 100 feet 7 See Table 1 for wiring terminations to the Burnerlogix 8 See Table 2 for wiring connections to the PPC4000 TEMPERATURE SENSORS 1 All wiring must be in accordance with National Electrical Code and local codes ordinances and regulations 2 ...

Page 8: ... conform to the description of the product on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES AND FIREYE MAKES NO WARRANTY OF MERCHANT ABILITY OR ANY OTHER WARRANTY EXPRESS OR IMPLIED Except as specifically stated in these general terms and conditions of sale remedies with respect to any product or part number manufactured or sold by Fireye shall be limited exclusively...

Reviews: