8
3.
The temperature sensors require 2 conductor, 18 gauge, shielded cable. Power limited, rated for
300V @105C. Use Belden 9318 or equivalent.
4.
The shield should be connected to the earth ground terminal on the wiring base of the Burner-
Logix Control (Terminal #E) or to the common ground established in the cabinet. The shield
should be taped at the sensor to avoid unintended contact with the sensor housing.
5.
All sensor wiring should be in a separate conduit. DO NOT install sensor wiring in any conduit
or junction boxes with high voltage wiring.
6.
Maximum wiring distance for sensor wiring is 100 feet.
7.
SeeTable 1 and 2 for wiring terminations.
Table 1: Burnerlogix wiring connections
Table 2: PPC4000 wiring connections
NOTICE
When Fireye products are combined with equipment manufactured by others and/or integrated into
systems designed or manufactured by others, the Fireye warranty, as stated in its General Terms and
Conditions of Sale, pertains only to the Fireye products and not to any other equipment or to the
combined system or its overall performance.
WARRANTIES
FIREYE guarantees for
one year from the date of installation or 18 months from date of manufacture
of its products to replace, or, at its option, to repair any product or part thereof (except lamps and
photocells) which is found defective in material or workmanship or which otherwise fails to conform
to the description of the product on the face of its sales order.
THE FOREGOING IS IN LIEU OF
ALL OTHER WARRANTIES AND FIREYE MAKES NO WARRANTY OF MERCHANT-
ABILITY OR ANY OTHER WARRANTY, EXPRESS OR IMPLIED.
Except as specifically
stated in these general terms and conditions of sale, remedies with respect to any product or part
number manufactured or sold by Fireye shall be limited exclusively to the right to replacement or
repair as above provided. In no event shall Fireye be liable for consequential or special damages of
any nature that may arise in connection with such product or part.
TS350/TS752
BLPS
PCV
AUX1
AUX2
Minco
Meas Sp
Temp Sp
BurnerLogix Terminals
1+
1+
6+
+ EXC
X (WHT/BLU)
X (WHT/BLU)
X (WHT/BLU)
2-
2-
7-
- COM
11 (WHT/GRN)
22 (WHT/VIO)
23 (BRN/WHT)
TS350/TS752
BLPS
PCV
AUX1
AUX2
SENS4
SENS5
Minco
Meas Sp
Temp Sp
PPC4000 Terminals
1+
1+
6+
+ EXC
P11.2
P11.2
P11.3
P11.3
P11.3
2-
2-
7-
- COM
P11.10
P11.9
P11.8
P11.7
P11.6
CAUTION: PROGRAM AND SET-UP
The proper operation of the BurnerLogix System and the pressure and temperature sen-
sors requires that the selected pressure ranges are appropriate for the application and
must match the pressure range programmed on the BurnerLogix Control. Insure that the
range of the selected sensor is correct for the application and the pressure range pro-
grammed on the BurnerLogix Integrated Flame Safeguard and Boiler Controller matches
the installed pressure sensor. Refer to Bulletin BLZ-1001.