background image

4

FIGURE 2.

Temperature Sensor - TS350-2, TS350-4, TS350-8

FIGURE 3.

Temperature Sensor - TS752-2, TS752-4, TS752-8

0.625” 

X = 2”,  4” or 8” 
 

11.0” [279]

7.5” [191]

WARNING: 

1.

 

Read these instructions carefully. Failure to follow them could result in a hazardous or 
dangerous condition. 

2.

 

Insure that the range of the selected sensor is appropriate for the application. Note: A 
general rule to follow when selecting the sensor range is that the expected value of the 
monitored pressure or sensor should fall between 40-70% of the upper range of the sensor. 
For example, a steam boiler maintains 20 lbs. pressure, select the BLPS-30 Pressure Sensor, 
with a 0-30 PSIG range 

3.

 

The sensors must be located where the ambient temperature will not exceed the maximum 
ambient operating temperature specified for the sensor. 

4.

 

Insure that the pressure range programmed on the BurnerLogix Boiler Room Control 
matches the installed pressure sensor. Refer to Bulletin BLZ-1001. 

5.

 

Do not mount any of the sensors where they could be used as a footstep. 

6.

 

Installation must be performed by a trained, experienced flame safeguard technician.

 

Summary of Contents for BLPS-25

Page 1: ...rature Sensors have a 1 2 NPT mounting for the 2 4 and 8 thermowell probe The pressure and temperature sensors provide a 4 20 mA control signal over their respec tive stated ranges to the PPC4000 and BurnerLogix Control systems No setting or calibra tion is required for either type of sensor The PPC4000 and BurnerLogix Control systems perform continuous safety checks on the operation of all pressu...

Page 2: ...ns and conduit adapter cover BLPS 200 Pressure transducer 0 to 200 psi 0 to 13 8 Bar 4 20 mA output linear with pressure NPT mount ing Screw terminal connections and conduit adapter cover BLPS 300 Pressure transducer 0 to 300 psi 0 to 20 7 Bar 4 20 mA output linear with pressure NPT mount ing Screw terminal connections and conduit adapter cover TS350 2 Temperature sensor Range 32 F to 350 F 0 C to...

Page 3: ...7 Controls Primary Safety Component MCCZ7 File MP1537 Controls Primary Safety Certified for Canada MCCZ8 File MP1537 Controls Primary Safety Certified for Canada Component Factory Mutual FM Class 7610 Acceptable by Industrial Risk Insurers I R I FIGURE 1 Pressure Sensor BLPS 15 25 30 200 300 COM OUT GND EXC ...

Page 4: ...ored pressure or sensor should fall between 40 70 of the upper range of the sensor For example a steam boiler maintains 20 lbs pressure select the BLPS 30 Pressure Sensor with a 0 30 PSIG range 3 The sensors must be located where the ambient temperature will not exceed the maximum ambient operating temperature specified for the sensor 4 Insure that the pressure range programmed on the BurnerLogix ...

Page 5: ...he fitting and prevent proper operation of the sensor 9 Make all pipe connections in accordance with approved standards 10 When tightening the sensor apply a wrench to the hex flats located just above the pressure fit ting DO NOT tighten by using a pipe wrench on the housing Do not tighten the pressure sensor by hand MOUNTING TEMPERATURE SENSORS The immersion style temperature sensors have a NPT m...

Page 6: ...sensor if provided by the boiler man ufacturer 2 If no well connection is provided select an appropriate location for mounting the temperature sensor Preferably as close to the boiler outlet as possible OUTDOOR AIR TEMPERATURE 1 The outdoor air temperature sensor should be mounted on the outside of the building where it will be exposed to representative air temperature but not to direct sunlight A...

Page 7: ... separate conduit DO NOT install sensor wiring in any conduit or junction boxes with high voltage wiring 6 Maximum wiring distance for sensor wiring is 100 feet 7 See Table 1 for wiring terminations to the Burnerlogix 8 See Table 2 for wiring connections to the PPC4000 TEMPERATURE SENSORS 1 All wiring must be in accordance with National Electrical Code and local codes ordinances and regulations 2 ...

Page 8: ... conform to the description of the product on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES AND FIREYE MAKES NO WARRANTY OF MERCHANT ABILITY OR ANY OTHER WARRANTY EXPRESS OR IMPLIED Except as specifically stated in these general terms and conditions of sale remedies with respect to any product or part number manufactured or sold by Fireye shall be limited exclusively...

Reviews: