BASIC SET UP PROCEDURE/LED INDICATION

TASK

ACTIONS

LED STATUS

Flame 

Strength 

(8)

Ready

Flame
On/Off

Learn

Target
Flame

Learn 

Background

Flame

RUN

(none)

All Active

ON

Active

OFF

OFF

Enter
Password

Simultaneously depress:

Target Flame Select

 and

Background Flame Select

buttons, then release

Disabled

ON

Active

ON

ON

Depress and release: 

UP

 

button five times

5th ON

ON 

Active

ON

ON

Accept
Password

Simultaneously depress:

Target Flame Select

 and

Background Flame Select

buttons, then release

5th ON

FLASH

Active

FLASH

FLASH

Aim 
Scanner

Depress and hold*:

Target Flame Select

 button

Adjust scanner alignment for 
flame maximum signal then 
secure scanner position.

All Active

FLASH

ON

*(RF is energized if 

Target Flame Select 

button is held)

ON

OFF

Learn
Target
Flame

Depress and release:

UP or DOWN

 button while 

holding

Target Flame Select

 button*

All Active

FLASH

ON

*(RF is energized if 

Target Flame Select 

button is held)

FLASH

OFF

Learn Target Flame completed

All Active

ON

Active

OFF

OFF

Learn
Background
Flame
(if required)

Enter and Accept Password as 
described above

5th ON

FLASH

Active

FLASH

FLASH

Depress and release:

Background Flame Select

button

All Active

FLASH

Active

OFF

ON

Learn Background Flame 
completed

All Active

ON

Active

OFF

OFF

RUN

(none)

All Active

ON

Active

OFF

OFF

*WARNING: Depressing and holding the “Target Flame Select” button during the AIM
and Learn Target Flame procedures will keep the flame relay contacts closed, allowing the
burner to operate without bypassing the burner management system input. 

During this process you must visually confirm that the flame is present. 

Only when the “Target Flame Select” button is released will the flame relay status be
determined by the actual flame signal strength

Summary of Contents for 85IRF series

Page 1: ...K3 Flame Scanners are derivatives of the standard Phoenix product but utilizing an advanced optical filter This filter adjusts the optical sensitivity of the detection cell to pick up wavelengths of l...

Page 2: ...UNTING FLANGE P N 35 318 1 2 ORDERED SEPARATELY DIMENSIONS IN INCHES MM PURGE AIR CONNECTION 3 8 18 NPT OR 3 8 19 BSP PL 1 11 1 2 NPT OR 1 11 BSP PL SIGHT PIPE CONNECTION 1 46 36 97 1 84 46 79 HOUSING...

Page 3: ...X X 85IRF1 2QD X X X X X X X X X X X 85UVF1 2QD X X X X X X X X X X X 85UVF1 1QDK3 X X X X X X X X X X 85UVF1 2QDK3 X X X X X X X X X X X CERTIFICATION IN HAND Table 2 PART NUMBER DESCRIPTION NOTES 35...

Page 4: ...NUMBER DESCRIPTION LENGTH METERS FEET 59 546 3 8 Conductor 3 meter cable assembly with 8 pin female connector 3 meters 9 feet 10 inches 59 546 6 8 Conductor 6 meter cable assembly with 8 pin female c...

Page 5: ...and or use with dirty dusty fuels may require up to 15 SCFM 425 l min Pressure Adequate to overcome furnace or windbox pressure ELECTRICAL Input Power 24 Vdc nominal 20 15 supply current 200 mA Elect...

Page 6: ...me reliably thus prohibiting the delivery of fuel to the burner Note Ensure the correct FFRT Flame Failure Response TIme is selected prior to commissioning INSTALLATION PROCEDURE 1 The best results ar...

Page 7: ...and close to the periphery of the throat where the ultraviolet radiation is at a maximum See Figures 3 and 4 Having determined an appropriate location for the sight tube cut a clearance hole for a 2...

Page 8: ...ure must not exceed its maximum rating of 150 F 65 C Excessive temperatures will shorten scanner life Both requirements will be satisfied by a continuous injection of purge air at either the 3 8 housi...

Page 9: ...FOR SPECIAL APPLICATIONS HIGH PRESSURE 35 127 HEAT INSULATING NIPPLE 35 127 HEAT INSULATING NIPPLE 60 1199 1 NPT SEALING COUPLING WITH QUARTZ WINDOW REQUIRED WHEN SCANNER LENS IS EXPOSED TO EXCESSIVE...

Page 10: ...ot the Red wire CAUTION The Phoenix flame scanner requires 24 Vdc power for operation Connection to a 24 Vac or 120 Vac power source will damage the scanner Refer to wiring diagrams External 2 0 Amp f...

Page 11: ...4 SCANNER CABLE COLOR CODE NEW 59 546 CABLE COLOR CODE Connector Pin No FUNCTION OLD 59 497 CABLE COLOR CODE For reference only 2 Black 24 vdc Input Black Red 6 Blue 24 vdc Input White Blue 8 Yellow...

Page 12: ...RNAL FACTORY WIRE COLOR TB1 1 24 Volt WHITE TB1 2 24 Volt BLACK TB1 3 4 20 mA VIOLET TB1 4 4 20 mA GREY TB2 1 FAULT RELAY PINK TB2 2 FAULT RELAY RED TB2 3 FLAME RELAY WHITE RED TB2 4 FLAME RELAY WHITE...

Page 13: ...optional Background Flame TARGET FLAME SELECT The Target Select button is used to begin the learn or store process for the target flame This will auto matically set all the necessary switching thresho...

Page 14: ...or 4th Once you have selected the correct value Press both the Target Flame Select and Background Flame Select buttons simultaneously to store The stored value can be displayed and checked at any tim...

Page 15: ...ns and adjusts it up to the correct level The Flame Strength should BRIEFLY GO BELOW 6 LEDs If the LEDs stay at 7 or above add orifices to minimize the signal see page 28 If the signal strength does n...

Page 16: ...Detection Thresholds Learning Target Flame Only Step 3 Learn Store the Background Flame optional see note above Note Use Step 1 instructions on page 14 to enter the pass code before Step 3 can be carr...

Page 17: ...test the flame relay s plus a power cycle to test the fault relay see Table 5 This test will detect 25 of possible DU failures of the device Table 5 Proof Testing Step Action 1 Bypass the safety func...

Page 18: ...epress and release UP or DOWN button while holding Target Flame Select button All Active FLASH ON RF is energized if Target Flame Select button is held FLASH OFF Learn Target Flame completed All Activ...

Page 19: ...rnal error SINGLE SOURCE Single flicker frequency source has been detected This is identified as not a genuine flame OVER RANGE UV IR emissions had too much energy to learn flame condition Use orifice...

Page 20: ...6 F 80 C NEG 5 FAULT Internal voltage levels have exceeded allowed tolerances Verify supply voltage is within pub lished limits Possible fault with inter nal power supply PLUS 5 FAULT Internal voltage...

Page 21: ...ASS CODE ACCEPTED Step 2 Commit the Default File Profile to EEPROM To save the Default Profile to the scanner s permanent memory and exit this mode Press and hold the Background Flame Select button fo...

Page 22: ...th the Target Flame Select and Background Flame Select buttons simultaneously Use the UP or DOWN buttons to select LED number 2 passcode Press both the Target Flame Select and Background Flame Select...

Page 23: ...een the lit LED and the scanner parameters When the Target Flame Select button is released the display will change and show a series of LEDs that corresponds to the value of the parameter selected To...

Page 24: ...age and Binary Value Tables LED Parameter LEDs Display As Value Calculation Interpretation 8 Single Source Detected ON or OFF ON Single Source Detected OFF No Single Source 7 Peak Frequency Binary Val...

Page 25: ...onding binary value Peak Frequency Binary Value and add them together 3 Multiply this sum times 2 5Hz for the Peak Frequency Determining Single Source Single Source Detected determination is simple If...

Page 26: ...FF event 25 5 to 80 5 5 10 Power Spectrum Density The Power Spectrum Density setting is a percentage of the learned flame s power spectrum density The percentage is used to calculate the threshold of...

Page 27: ...desired continue to the next parameter using the UP or DOWN buttons and program the parameter as previously discussed Step 4 Saving or Discarding Parameter Settings To SAVE the modified parameters to...

Page 28: ...y Heat Insulating Nipple The heat insulating nipple P N 35 127 3 BSP or 35 127 1 NPT prevents heat transfer from the hot sight pipe to the scanner head Sealing Coupling with Quartz Window The sealing...

Page 29: ...12C 53 121 4 Orifice 093 Diameter 12D 53 121 5 Orifice 109 Diameter 12E 53 121 6 Orifice 125 Diameter 12F 53 121 7 Orifice 187 Diameter 12G 53 121 8 Orifice 250 Diameter 12H 53 121 9 Orifice 375 Diame...

Page 30: ...efective in material or workmanship or which otherwise fails to conform to the descrip tion of the product on the face of its sales order THE FOREGOING IS IN LIEU OF ALL OTHER WARRANTIES AND FIREYE MA...

Reviews: