SYSTEM  CONFIGURATION & OPERATION

The NAPCO Digital Communicator is configured by connecting the 

FW-PCTOOL Configuration Tool

 to P4 of the FW-

DACT Main Board. Once connected, if no text appears immediately on the LCD screen, hit any key on the numeric
keypad.

The  DACT supports three levels of restricted access to the 

Configuration Mode

 which allows for parameter

configuration and control of operation. Each level is associated with a separate 

Passcode

 (up to 8-digit numeric code)

and may be individually modified. Once a user gains access to the Configuration Mode, they are presented with a menu
of selections according to the level of access granted. The 

factory default

 Passcodes are:

Level I

- OPERATOR   

“11111111” 

Level II

- INSTALLER 

“22222222”  

 

Restore-to-Factory-Defaults

 can be initiated from the FW-PCTOOL 

without having to first access program mode,

by using the special Passcode ...

Restore-to-Factory-Defaults

“12345678”

Items accessible to Level(s) I and II 

ITEM

Access

Menu

Menu Label

Description

Number

Level

Category

00

I, II

Access Control

Logout of DACT

Exit from PROGRAM mode on LCD/Keypad.

01

I, II

Access Control

About DACT

Display copyright (company and date) and firmware version
information on LCD.

02

I, II

Access Control

Change Passcode

Support modification to specific passcode associated with
individual level.

10

I, II

Event Logging

Flush all events

Terminate any in-progress event reporting.
Remove “report pending” trigger (i.e. cancel attempts to report

queued events) and

Force event queue (FIFO) to empty state (i.e. erase any queued

event history).

11

I, II

Event Logging 

Send Test-Report

Immediately initiate test-report generated to Account #1.

12

I, II

Event Logging

Abort-Reporting

Terminate any in-progress event reporting.
Remove “report pending” trigger (i.e. cancel attempts to report

queued events).

NOTE: Unreported events are still resident within FIFO. Any
future events logged will restart attempts at reporting ALL
queued (unreported) event items. This action will also  add a
“Line (x) Trouble” event to the event queue.

13

I, II

Event Logging 

AC-Power Loss

Specify an (optional) delay time (in hours), from 00 (no delay) to

(delay)

20 (maximum delay). A report of the “AC-Power Loss” event will
be delayed by this value, and then only sent after the period has
expired with the signal still present. A “restoral” event of this
signal will be reported immediately, but only if a prior “off-normal”
event was successfully reported earlier. 

20

I, II

Real Time

Set System DATE

Assign local DATE (dd/mm/yy) to DACT Real-Time-Clock device.

Clock

The Year field will be presented in 4-digit format on LCD status

Parameters

line, with automatic 20/21 century adjustment for Y2K
compliance.

21

I, II

Real Time

Set System TIME

Assign local TIME (ss/mm/hh) to DACT Real-Time-Clock device.

Clock

The Hour field will be presented in 24-hour (military) format on

Parameters

LCD status line.

Summary of Contents for FW-DACT

Page 1: ...n and specifications contained in this manual are subject to change without prior notice by the manufacturer FW DACT Digital Communicator INSTALLATION and OPERATION MANUAL 1999 by NAPCO Security Systems Inc October 14 1999 LT 639NAP Rev 7 ...

Page 2: ...Notice for all FW DACT Sold in the U S A Page 2 CONNECTIONS AND SETTINGS Page 3 FIELD WIRING Page 4 SYSTEM CONFIGURATION OPERATION Page 5 REPORTING FORMATS Page 7 COMPATIBLE FIRE ALARM CONTROL PANELS Page 8 COMPATIBLE RECEIVERS Page 8 SPECIFICATIONS Page 9 BATTERY CALCULATIONS Page 9 WARRANTY Page 10 ...

Page 3: ... The FW DACT can transmit Common Alarm Common Supervisory and Common Trouble information on two telephone lines The DACT continuously supervises the state of each of two connected Telco Lines at approximately 1 minute intervals by both a Line DC level measurement and by checking for a Dial Tone If either fails a Line 1 or Line 2 Trouble event will be reported Once a Line has been restored a Line T...

Page 4: ...re listed by Underwriters Laboratories Inc ULI for use in slave application in conjunction with a Listed Fire Alarm Control Panel under Standard 864 Control Units for Fire Protective Signalling Systems and applicable section of Standard 1635 Digital Alarm Communicator System Units These Communicators comply with the National Fire Protection Association NFPA performance requirements for DACT s and ...

Page 5: ... the Communicator they should be performed by NAPCO Security Systems Inc or an authorized representative of NAPCO Security Systems Inc For information contact NAPCO Security Systems Inc at the address and phone numbers shown on the last page of this document ...

Page 6: ...ting to NAPCO Fire Alarm Control Panel FACP P2 RS 485 Connection for future expansion P4 Connector for FW PCTOOL Configuration Module I2 Status Indicator LED for Telco Line 1 Red when the line is in use Amber when there is a line fault I1 Status Indicator LED for Telco Line 2 Red when the line is in use Amber when there is a line fault ...

Page 7: ... To an optional Premise Telephone on the first Telephone Line via the required RJ31X Connector Line 2 Input Tip Ring To the second Telephone Line via the required RJ31X Connector Line 3 Output Tip Ring To an optional Premise Telephone on the second Telephone Line via the required RJ31X Connector Note that most AHJ s do not allow the connection of Premise Telephones See wiring tables and specificat...

Page 8: ...0 I II Event Logging Flush all events Terminate any in progress event reporting Remove report pending trigger i e cancel attempts to report queued events and Force event queue FIFO to empty state i e erase any queued event history 11 I II Event Logging Send Test Report Immediately initiate test report generated to Account 1 12 I II Event Logging Abort Reporting Terminate any in progress event repo...

Page 9: ...Page 7 22 I II Real Time Auto Report Time Assign time mm hh for DACT to perform periodic 24 hr Clock intervals Test report generation to monitoring station Parameters ...

Page 10: ...hoose which Account 1 or 2 will be the first to be attempted to be reached by the DACT when a TROUBLE event is to be reported See ITEM 50 for a description of the DACT report attempt operation 52 II Report Priority SUPERVISORY Choose which Account 1 or 2 will be the first to be Events attempted to be reached by the DACT when a SUPERVISORY event is to be reported See ITEM 50 for a description of th...

Page 11: ...nt Off Normal Test New event 608 00 000 Manually initiated dialer test Test New event 601 00 000 DACT External Events FW DACT Event Description Event Family Qualifier Code Group Contact Fire Alarm Alarm New event 110 00 000 Fire Alarm restored Alarm Restore 110 00 000 System Trouble detected Trouble New event 300 00 000 System Trouble restored Trouble Restore 300 00 000 Supervisory condition Super...

Page 12: ...ry condition Supervisory New event SS 00 Supervisory restored Supervisory Restore SR 00 COMPATIBLE FIRE ALARM CONTROL PANELS NAPCO FW DACT Compatible with NAPCO FW C2Z FW C4Z FW C4EZ Fire Alarm Control Panels COMPATIBLE RECEIVERS The NAPCO FW DACT is compatible with the following Digital Alarm Communicator Receivers DACR DACR Receiver Model Protocols SurGard MLR2 Multi Line Receiver ULC ULI Approv...

Page 13: ...Page 11 ...

Page 14: ...upervisory and Trouble status to a Central Monitoring Station using either Ademco Contact ID or SIA DCS Protocols M User configured using the FW PCTOOL Configuration Tool with three levels of Password control M Current Consumption Standby See compatible Fire Alarm Control Panel Installation and Operation Manual BATTERY CALCULATIONS FW DACT The FW DACT Battery Calculations are performed as part of ...

Page 15: ...IS IN LIEU OF ALL OTHER grow out of Seller s rendering of technical advice or OBLIGATIONS OR LIABILITIES ON THE PART OF service in connection with Buyer s order of the goods NAPCO furnished hereunder Any action for breach of warranty including but not NAPCO RECOMMENDS THAT THE ENTIRE SYSTEM limited to any implied warranty of merchantability must BE COMPLETELY TESTED WEEKLY be brought within the si...

Page 16: ...ly to you This warranty NAPCO is not an insurer of either the property or safety other rights which vary from state to state of the user s family of employees and limits its liability for any loss or damage including incidental or consequential damages to NAPCO s original selling price of the product regardless of the cause of such loss or damage Some states do not allow limitations on how long an...

Reviews: