background image

Middle area

Outllet water temperature symbol, the figure under is the temperature value.

Failure symbol.

Bottom area

Turning on timer symbol. It appears when setting turn on timer.

Turning off timer symbol. It appears when setting turn off timer. 

Clock symbol. It appears when setting time.

ON

OFF

7.2  Illustration for LCD Display

Top area

Circulation pump running.
Cooling mode symbol / Defrosting symbol(flash).
Heating mode symbol.
Auxiliary heat source start.

Parameter number symbol, the figure under is the parameter number .

Water tank temperature symbol, the figure under is the temperature value. 

Temperature setting symbol, the figure under is the temperature value.

Parameter value symbol, the figure under is the parameter value.

This symbol means heat pump has two compressors.

7.3  Water temperature setting

When the heat pump is switched on, just press         or         to adjust water temperature.

Initial state

For example
press

Flash

Hot Water Series

23

Summary of Contents for FFC-10

Page 1: ...HOT WATER ECO SOLUTION Air Source Heat Pump Applicable Models FFC 10 FFC 20 FFC 30 FFC 38 FFC 45 FFC 55 FFC 63...

Page 2: ...ting 6 Commissioning 6 1 Preparation Before Commissioning 6 2 Commissioning 5 Installation 5 1 Heat Pump unit Installation 5 2 Water System Installation 5 2 1 Water Tank Installation 5 2 2 Water Pipin...

Page 3: ...to day operation Each unit is fully tested in exchangers are durable for anti corrsion hard performance and safety before exit factory water high pressure and unexpected freeze Simple Maintenance and...

Page 4: ...pacity Net Gross Weight Dimension Packing Dimension 10 5 2 55 12 46 3 57 17 45 R410a Toshiba Rotary 1 55 60 226 2 3 Tube in shell 40 DN25 55 I IPX4 220 1 50 FFC 10 87 103 752x690x765 840x750x900 kW kW...

Page 5: ...12 88 22 18 817 8 2 55 60 FFC 38 249 294 1450x702x1060 1525x805x1220 380 3 50 R410a Sanyo Scroll 2 55 60 Tube in shell Dn40 I IPX4 45 10 8 18 6 16 2 27 89 967 9 7 55 61 FFC 45 268 316 1450x702x1260 1...

Page 6: ...et Water Inlet Power Cable Hole Power Cable Hole Wire ControllerCable Hole Wire Controller Cable Hole Hot Water Series 752 1450 752 Length mm 690 702 690 Wide mm 470 755 470 A mm 765 950 Height mm 965...

Page 7: ...708 680 B mm B L H W A B Water Outlet Water Inlet Power Cable Hole Wire Controller Cable Hole High Pressure Gauge system1 system2 system3 Low Pressure Gauge system 1 system2 system3 High Pressure Gau...

Page 8: ...F 10 6 HeatingCapacityCurves 2000 4000 6000 8000 10000 12000 14000 10 5 0 5 10 15 20 25 30 35 40 AmbientTemp H e a tin g C a p a city W 30 35 40 50 55 CO P Curves 1 00 2 00 3 00 4 00 5 00 6 00 7 00 10...

Page 9: ...pacityCurves 5000 8000 11000 14000 17000 20000 23000 26000 10 5 0 5 10 15 20 25 30 35 40 AmbientTemp H e a tin g C a p a c ity W 30 35 40 50 55 CO P Curves 1 00 2 00 3 00 4 00 5 00 6 00 7 00 10 5 0 5...

Page 10: ...acityCurves 10000 15000 20000 25000 30000 35000 40000 45000 10 5 0 5 10 15 20 25 30 35 40 Ambient Temp H e a tin g C a p a city W 30 35 40 50 55 CO P Curves 1 00 2 00 3 00 4 00 5 00 6 00 7 00 10 5 0 5...

Page 11: ...tyCurves 15000 20000 25000 30000 35000 40000 45000 50000 55000 10 5 0 5 10 15 20 25 30 35 40 AmbientTemp H e a tin g C a p a c ity W 30 35 40 50 55 CO P Curves 1 00 2 00 3 00 4 00 5 00 6 00 7 00 10 5...

Page 12: ...tyCurves 15000 20000 25000 30000 35000 40000 45000 50000 55000 60000 10 5 0 5 10 15 20 25 30 35 40 Ambient Temp H eating C apac ity W 30 35 40 50 55 CO P Curves 1 00 2 00 3 00 4 00 5 00 6 00 7 00 10 5...

Page 13: ...eatingCapacityCurves 20000 30000 40000 50000 60000 70000 10 5 0 5 10 15 20 25 30 35 40 Ambient Temp H eating C apac ity W 30 35 40 50 55 CO P Curves 1 00 2 00 3 00 4 00 5 00 6 00 7 00 10 5 0 5 10 15 2...

Page 14: ...CapacityCurves 20000 30000 40000 50000 60000 70000 80000 90000 10 5 0 5 10 15 20 25 30 35 40 Ambient Temp H eating C apac ity W 30 35 40 50 55 CO P Curves 1 00 2 00 3 00 4 00 5 00 6 00 7 00 10 5 0 5 1...

Page 15: ...gh pressure switch High pressure switch Low pressure switch Low pressure switch 4 way valve 4 way valve Suction accumulator Suction accumulator Compressor Compressor Condenser fin tube fin tube Evapor...

Page 16: ...exchanging area and higher efficiency Thermal expansion valve The 2 way thermostatic expansion valve ensures high efficiency when heating moreover ensures high efficiency when defrosting Evaporator T...

Page 17: ...stably accessible to the heat the air outlet The inlet and outlet of the pump otherwise the performance would be air blower are illustrated in the following influenced diagram The installation space s...

Page 18: ...over 1000mm A certain distance should be kept among the heat pumps and it should be at least 1 meter when several heat pumps are installed side by side more than 1000mm air inlet air intake more than...

Page 19: ...ter or the sinkhole for stop valve of the system according to local draining water more efficiently Discharge valve ambient temperature for avoiding icing of the is necessary on the drainpipe water su...

Page 20: ...lenoid Valve Check Valve Elec Heater Water Pump Y Shape Filter 18 Flow Switch Heat Pump Controller Heat Pump Dinning Hall Water Pump Filter Filter Flow Switch can omit Guest Room Sauna Room Drainage W...

Page 21: ...2 5x6mm 2 3x2 5mm 2 3x2 5mm 2 3x1 5mm 2 3x1 5mm 2 3x1 5mm 2 3x1 0mm 2 3x1 0mm 2 3x1 0mm 2 3x1 0mm 2 3x1 0mm 2 2x0 35mm 2 2x0 35mm 2 2x0 35mm 2 2x0 35mm 2 2x0 35mm Note the above specification is the...

Page 22: ...holes at a level parallel to the sight line as picture 3 The hole distance is 60mm diameter is 8mm 4 Place the plastic screws of the enclosure into the hole and use the tapping screw ST4 16 D 1 enclo...

Page 23: ...liable Inspection on the piping system check if the water piping system including water supply pipe return water pipe pressure gauge thermometer valves water level switch are installed correctly Pleas...

Page 24: ...ue Press them to adjust the value of water temperature clock timer parameters During failure checking and parameter checking press any of them to exit checking Long press it for more than 6 seconds yo...

Page 25: ...mode symbol Defrosting symbol flash Heating mode symbol Auxiliary heat source start Parameter number symbol the figure under is the parameter number Water tank temperature symbol the figure under is t...

Page 26: ...ash Step 6 Flash Press or to adjust the hour value Press to select minute and the minute value flashes Press or to adjust the minute value Press to confirm the value and return to normal display Norma...

Page 27: ...the setting temperature it will be restarted until the next time point of Timer on is arrived or the key is pressed Totally 1 ON OFF timers can be set And they can be applied to use for every day or o...

Page 28: ...rward b f Press to select hour and the hour value flashes Press or to adjust the hour value Press to select minute and the minute value flashes Press or to adjust the minute value Step 7 Press to star...

Page 29: ...one day timer Initial state Long press 6 seconds Parameter No Please correspond to the serial number in the table on page 34 Value Press to turn to parameter No 1 Press to select the value Step 2 Step...

Page 30: ...for cancelling timer Press M button Press M button Step 1 Confirm of Timer on is canceled and enter into the normal display Flash Step 6 Flash Step 8 Flash Step 9 Confirm the section of Timer off is...

Page 31: ...Hot Water Series 8 Circuit drawing Model FFC 10 29 In case the power of the heater is higher than 500W HR can not be connected to the heater directly an AC contactor or relay is required...

Page 32: ...Hot Water Series Model FFC 20 30 AC 380V 50Hz In case the power of the heater is higher than 500W HR can not be connected to the heater directly an AC contactor or relay is required...

Page 33: ...Hot Water Series 31 Model FFC 30 FFC 38 FFC 45 In case the power of the heater is higher than 500W HR can not be connected to the heater directly an AC contactor or relay is required 2 2...

Page 34: ...Model FFC 55 FFC 63 Hot Water Series 32 In case the power of the heater is higher than 500W HR can not be connected to the heater directly an AC contactor or relay is required 2 2...

Page 35: ...efore ex factory Users must not adjust it when inspection of the system is required before next the heat pump unit is in use operation Regular inspection is required for the power Users should call th...

Page 36: ...ant leak system 1 PF Refrigerant leak system 2 EF High pressure protection Pressure valve break down system 1 E4 High pressure protection Pressure valve break down system 2 E8 Water outlet temp sensor...

Page 37: ...nd adjust parameters Long press 6 seconds to enter parameter checking mode Warning Value Step 1 Step 2 Step 3 Step 4 Step 5 Normal display Flash Flash Press to confirm the value Press or to return nor...

Page 38: ...sign 0 no effective 1 effective 1 the wire control panel 2 the setting area X 2 10 Unit 3 The main board 3 the setting area Y 0 3 Unit 0 The main board 4 The interval for defrosting 15 99 Unit minute...

Page 39: ...Fill water into the water supply system 2 Discharge air from the water system 3 Open all the valves in the system 4 Clean the water filter Low heating capacity 1 Lack of refrigerant 2 Bad water system...

Page 40: ...he operation of the circulation pump and fix it 2 Change a bigger pump 3 Wash the water filter 4 Adjust or change the flow volume control device Over high compressor discharge pressure 1 Low water flo...

Page 41: ...e to ensure that all specifications are correct printing errors are beyond FireFly s control FireFly can not be held responsible for these errors Energy Efficient Homes and Businesses Pty Ltd Cell 083...

Reviews: