FLX-PC

®

 Vacuum / Pressure Controller

 

Operation Manual

 

 

FM-060M-0-84B 

Events History Log 

The  last  50 events  are  kept  inside  the 

FLX-PC

®

  unit  for 

consultation. 
To  access  this  information,  press  and  hold  the  push-button 
for 3 seconds then release the push-button. 

* * * V E R :   1 . 0 . 0 * * *  
1 0 0 0 : 4 5 : 3 3   H R S  

The  first  line  indicates  the  version  of  the  software  of  the 

FLX-PC

®

 unit. 

The second line shows the total operating time of the vacuum 
pump.    When  the  hour  counter  reaches  the  value  of 
9999:59:59, the counter returns to 0:00:00. 

Note

:  When  the  24VDC  supply  is  removed  from  the 

FLX-PC

®

 unit, the hour counter returns to 0:00:00. 

Press the push-button momentarily to scroll through each of 
the events in history up to a maximum of 50 events.  The list 
will go back to the first event at the end of the last event. 

* * * V E R :   1 . 0 . 0 * * *  
  1   P U M P   S T O P  

The  display  will  automatically  return  to  its  normal  condition 
after 10 seconds of inactivity of the push-button. 

Note

:  When  the  24VDC  supply  is  removed  from  the 

FLX-PC

®

 unit, all events are cleared from the history. 

Pressure Units 

The  pressure  is  initially  displayed  in  BAR.    It  can  also  be 
displayed in KPA, PSI or BAR/PSI.  This last unit will display 
the  BAR  when  in  a  vacuum  and  the  PSI  under  positive 
pressure. 
To  change  the  unit,  press  and  hold  the  push-button  for 
10 seconds then release the push-button. 

B A R                            
 

The  current  unit  will  be  displayed.    Press  the  push-button 
momentarily to scroll through the various units. 

K P A                            
 

 

P S I                            
 

 

B A R / P S I                            
 

Once  the  unit  has  been  selected,  the  display  will 
automatically return  to  its normal  condition  after  10 seconds 
of  inactivity  of  the  push-button;  the  change  of  units  will  be 
completed. 

Note

:  When  a  unit  is  changed,  the  hour  counter  returns  to 

0:00:00 and all events are cleared from the history. 

Trouble Condition 

A  trouble  signal  is  transmitted  to  the  release  control  panel 
when  the 

FLX-PC

®

  unit  is  not  powered  or  a  defect  of  the 

microcontroller is present. 

Note

:  The  vacuum  pump  will  not  operate  if  a  trouble 

condition is present on the 

FLX-PC

®

 unit. 

 

Note

:  When  the  24VDC  supply  is  removed  from  the 

FLX-PC

®

  unit,  the  hour  counter returns  to  0:00:00  and  all 

events are cleared from the history. 

The opening of the 

FLX-PC

®

 unit must only be performed by 

a  qualified  technician.    No  operation  requires  to  remove the 
front cover. 

Specifications 

Voltage supply range:  20 to 28VDC 
Maximum  current  consumption:  40mA  under  normal 

supervisory condition; 75mA under alarm condition 

Contacts rating:  30VDC, 1A (resistive) 
Pump control rating:  30VDC, 45mA 
Inputs rating:  30VDC, 2mA 
Pressure range:  -14.7 to 175PSI (-1 to 12.1BAR) 
Piping connection size/material:  1/2-NPT, C836 Brass 

Useful Conversions 

 

BAR 

KPA 

PSI 

 

-0.220 

-22 

-3.19 

 

-0.180 

-18 

-2.61 

 

-0.150 

-15 

-2.18 

 

-0.140 

-14 

-2.03 

 

-0.130 

-13 

-1.89 

 

 

12.07 

1207 

175 

Summary of Contents for FLX-PC

Page 1: ...FM 060M 0 84B Vacuum Pressure Controller Model FLX PC Operation Manual...

Page 2: ...Operation Manual FM 060M 0 84B Manufactured by FIREFLEX Systems Inc 1935 Lionel Bertrand Blvd Boisbriand Quebec Canada J7H 1N8 Tel 450 437 3473 Toll free 866 347 3353 Fax 450 437 1930 Web Site http w...

Page 3: ...in Normal Condition 1 LCD Display Intensity Vacuum Pump Control 2 Supervisory Pressure Forced Shutdown Reset Low and High Pressure 2 Alarm Pressure 2 Operation Mode 2 Quick Detection of Sprinkler Ope...

Page 4: ...have been taken in the preparation of this manual to assure its accuracy FIREFLEX Systems Inc assumes no liability resulting from any errors or omissions in this manual or from the use of the informat...

Page 5: ...tion The system pressure is displayed in real time on the first line see PRESSURE UNITS CONVERSION section for a list of other units of pressure 0 1 8 0 B A R 1 6 8 3 0 2 5 5 2 0 The second line shows...

Page 6: ...ection D VACUUM SUPPLY of the Operation and Maintenance Manual of the FIREFLEX VACTEC system to correct the situation If the vacuum level reached 0 220 BAR this indicates a high level of vacuum and th...

Page 7: ...hold the push button for 10 seconds then release the push button B A R The current unit will be displayed Press the push button momentarily to scroll through the various units K P A P S I B A R P S I...

Page 8: ...ire protection system The vacuum pump control is made via a 24VDC isolation relay whose contacts activate the contactor that controls the vacuum pump The connections are all done via the connections o...

Reviews: