FireFlex FLX-PC Operation Manual Download Page 6

Page 2 

 

FLX-PC

®

 Vacuum / Pressure Controller

 

Operation Manual

 

 

FM-060M-0-84B 

Vacuum Pump Control 

The system is designed to maintain a level of vacuum in the 
piping network between -0.150 BAR and -0.180 BAR.  These 
values are fixed and cannot be changed. 

Supervisory pressure 

The pump starts at -0.150 BAR and stops at -0.180 BAR. 

- 0 . 1 5 0   B A R         +    
 

When  the  pump  is  in  operation,  the  sign [

]  appears  to  the 

right of the first line. 

Note

:  The  vacuum  pump  will  not  operate  if  a  trouble 

condition is present on the 

FLX-PC

®

 unit. 

Forced Shutdown 

The forced shutdown of the vacuum pump takes place when 
the  deluge  valve  is  operated,  an  automatic  sprinkler  has 
been  activated  or  that  the  vacuum  pump  has  worked  for  a 
period of more than 35 minutes. 

- 0 . 1 8 0   B A R         *    
 

When the pump is shutdown, the sign [

] is displayed to the 

right of the first line. 
To allow the vacuum pump to start, you must first correct the 
situation and put the system in normal condition of operation.  
Refer  to  the  section 

 B 

 

MECHANICAL  SECTION

  of  the 

Operation 

and 

Maintenance 

Manual 

of 

the 

F

IRE

F

LEX

®

VACTEC

®

 system. 

Once  the  system  is  back  in  operating  condition,  press  and 
hold  the  push-button  for  5 seconds  to  restart  the  vacuum 
pump.  Release the push-button as soon as the pump starts 
or until the sign [

] disappears. 

Note

:  The  history  display  appears  after  3 seconds;  do  not 

release the push-button before the end of 5 seconds. 

Low and High Pressure 

A  supervisory  signal  is  transmitted  to  the  release  control 
panel in the following situations: 

- 0 . 1 4 0   B A R              
L O W   P R E S S .  

When  the  vacuum  level  reaches  -0.140 BAR.    This  can 
happen  if  the  vacuum  pump  does  not  work.    Refer  to  the 
section 

 D 

 

VACUUM  SUPPLY

  of  the  Operation  and 

Maintenance  Manual  of  the 

F

IRE

F

LEX

®

VACTEC

®

  system  to 

correct the situation. 

If the vacuum level reached -0.220 BAR, this indicates a high 
level of vacuum and this situation is abnormal.  Refer to the 
section 

 D 

 

VACUUM  SUPPLY

  of  the  Operation  and 

Maintenance  Manual  of  the  system 

F

IRE

F

LEX

®

VACTEC

®

  to 

correct the situation. 

- 0 . 2 2 0   B A R              
H I G H   P R E S S .  

Note

:  Supervisory  signals  are  kept  latched  for  a  period  of 

5 seconds. 

Alarm Pressure 

Note

:  This section do not applies to vacuum single interlock 

pre-action systems. 

An  alarm  pressure  signal  is  transmitted  to  release  control 
panel when the vacuum level reaches -0.130 BAR. 

- 0 . 1 3 0   B A R              
A L A R M   P R E S S .  

Note

:  Alarm signal is kept latched for a period of 5 seconds. 

Operation Mode 

The 

FLX-PC

®

  unit  can  be  configured  to  match  the  different 

types  of  interlock  for  a  pre-action  system,  via  switch SW1 
located  inside  the  case.    This  switch  is  configured  at  the 
factory and should not be changed. 

Quick Detection of Sprinkler Opening  

The 

FLX-PC

®

  unit  can  be  configured  so  that  it  can  quickly 

detect  an  automatic  sprinkler  opening;  this  configuration  is 
done via the switch SW2 located inside the case.  When this 
mode is enabled, the letter [D] is displayed to the right of the 
first  line.    This  allows  for  a  time  of  operation  less  than 
5 seconds  between  the  automatic sprinkler  opening  and  the 
opening of the deluge valve. 

- 0 . 1 6 0   B A R         D    
A L A R M   S P K  

This operation is valid under the following conditions: 

Sprinkler K Factor 

Network Capacity 

K5.6(80)  to  K<11.2(161) 

2000 US gal (7.57m

3

K11.2(161) to  K<25.2(363) 

3000 US gal (11.4m

3

K25.2(363) and bigger 

4000 US gal (15.1m

3

An alarm pressure signal is transmitted to the release control 
panel  when  a  variation  of  the  vacuum  corresponding  to  the 
opening of a vacuum sprinkler is detected. 

Summary of Contents for FLX-PC

Page 1: ...FM 060M 0 84B Vacuum Pressure Controller Model FLX PC Operation Manual...

Page 2: ...Operation Manual FM 060M 0 84B Manufactured by FIREFLEX Systems Inc 1935 Lionel Bertrand Blvd Boisbriand Quebec Canada J7H 1N8 Tel 450 437 3473 Toll free 866 347 3353 Fax 450 437 1930 Web Site http w...

Page 3: ...in Normal Condition 1 LCD Display Intensity Vacuum Pump Control 2 Supervisory Pressure Forced Shutdown Reset Low and High Pressure 2 Alarm Pressure 2 Operation Mode 2 Quick Detection of Sprinkler Ope...

Page 4: ...have been taken in the preparation of this manual to assure its accuracy FIREFLEX Systems Inc assumes no liability resulting from any errors or omissions in this manual or from the use of the informat...

Page 5: ...tion The system pressure is displayed in real time on the first line see PRESSURE UNITS CONVERSION section for a list of other units of pressure 0 1 8 0 B A R 1 6 8 3 0 2 5 5 2 0 The second line shows...

Page 6: ...ection D VACUUM SUPPLY of the Operation and Maintenance Manual of the FIREFLEX VACTEC system to correct the situation If the vacuum level reached 0 220 BAR this indicates a high level of vacuum and th...

Page 7: ...hold the push button for 10 seconds then release the push button B A R The current unit will be displayed Press the push button momentarily to scroll through the various units K P A P S I B A R P S I...

Page 8: ...ire protection system The vacuum pump control is made via a 24VDC isolation relay whose contacts activate the contactor that controls the vacuum pump The connections are all done via the connections o...

Reviews: