background image

F

IRE

F

LEX

®

  N

2

 

B

LAST

®

 

Integrated Fire Protection System 

O

WNER

'

O

PERATION 

&

 

M

AINTENANCE 

M

ANUAL

 

Page 18 of25 

FM-076B-0-6A

 

5.3  OPERATION 

5.3.1  Air supply Style "A" 

See figure 5.3. 

To apply air pressure: 

Establish AC power for the air compressor by activating the 
correspondent circuit breaker at the electrical distribution 
panel.  Close the air inlet drain valve 

(E12)

.  Start 

compressor by activating the

 

compressor isolating 

switch 

(E15)

 located within the unit (see figure 4.4). 

If the air compressor motor fails to start or slows down 
under load, shut the compressor off.  Check that the supply 
voltage agrees with the motor nameplate. 

To close the air supply: 

Turn off the compressor isolating switch 

(E15)

 (see 

figure 4.4). 

To adjust system air pressure (air compressor switch): 

WARNING !  

The cut-out/cut-in differential switch adjustment 

screw (small screw to the right) is factory set.  DO NOT 
CHANGE ITS SETTING.  Any unauthorized modification of 
this setscrew adjustment will void the system warranty and 
may also prevent the system from operating normally. 

The air compressor cut-off pressure switch 

(E2) 

(shown in 

figure 5.1 with its cover removed) has its air compressor 
cut-out adjustment screw (middle screw) factory set.  This 
switch should not need any adjustment but if necessary, 
follow the instructions below: 

1.  Remove the cover of the air compressor cut-off 

pressure switch 

(E2)

2.  To raise the cut-out pressure of the air compressor, 

turn the cut-out adjustment screw (middle screw) half a 
turn CLOCKWISE. 

3.  Open the main drain valve 

(D3)

 and let the pressure 

drop until the air compressor 

(E1) 

restarts.  Check 

pressure reading on the system pressure gauge 

(E3)

 

when the air compressor stops.  Repeat until the 
desired pressure is reached (refer to table 5).  Once all 
is done, replace the cover on the switch 

(E2)

Note:

  Do not turn the cut-out adjustment screw (middle 

screw) all the way down in one shot.  Proceed by steps.  Use 
the same method turning the cut-out adjustment screw 
COUNTER-CLOCKWISE to lower the air compressor cut-out 
pressure. 

Figure 5. - Front view of the air compressor cut-off 

pressure switch 

Turn clockwise to increase

both cut-out and cut-in

pressure adjustment

Factory set

DO NOT CHANGE !

FM-072Q-0-109B

 

5.3.2  Air supply Style "B"

 

See figure 5.4. 

To apply air pressure: 

Turn on upstream air supply.  If the unit is equipped 
with the optional dehydrator (refer to section 5.5), close 
the air inlet drain valve 

(E12)

 and open the air shut-off 

valve 

(E14)

Open APMD

 (E5)

 input valve 

(E6)

 by placing handle in 

line with valve body then open APMD

 (E5)

 output 

valve 

(E7)

 by placing handle in line with the valve body. 

In order to accelerate filling of sprinkler piping by air 
pressure, bypass valve 

(E8)

 can be opened by placing 

handle in line with valve body while piping is initially 
filled by the air compressor.  This valve 

(E8)

 must then 

be closed (handle crossways to valve body) and kept in 
this position once the system is filled with air. 

To close the air supply: 

Close APMD output valve 

(E7)

 by placing handle 

crossways to valve body then close APMD

 (E5)

 input 

valve 

(E6)

 by also placing handle crossways to the 

valve body.  Be sure bypass valve 

(E8)

 is closed 

(handle crossways to valve body). 

To adjust system air pressure: 

Be sure APMD

 (E5)

 input valve 

(E6)

 and output 

valve 

(E7)

 are both open (handle in line with the valve 

body), and bypass valve 

(E8)

 is closed (handle 

crossways to valve body) prior to performing this 
operation.  Loosen lock nut of the DMPA

 (E5) 

and turn 

pressure adjustment nut clockwise to increase air 
pressure or counter-clockwise to decrease pressure.  
Tighten lock nut. 

Note:

  Depending on site conditions, the internal filter of 

the APMD

 (E5)

 may need maintenance on a regular 

basis.  Refer to Viking Data Sheet #127 for more details. 

Summary of Contents for N2 BLAST

Page 1: ...FireFlex Preaction Double Interlocked Electric Pneumatic Release Self Contained Fire Protection Systems O M Manual FM 076B 0 6A 2020 The Leader in Nitrogen Generation Technology...

Page 2: ...al is prohibited While all reasonable efforts have been taken in the preparation of this manual to assure its accuracy FIREFLEX Systems Inc assumes no liability resulting from any errors or omissions...

Page 3: ...r 3 2 5 BlastOff Leak Detection System 3 2 6 N2 Blast AutoPurge System 3 2 7 Nitrogen generator 3 Air Pressure Maintenance Device 3 3 PREACTION SYSTEM 4 3 1 DESCRIPTION 4 3 2 CONFIGURATION 4 3 3 RELEA...

Page 4: ...mpressor Style A 16 5 2 Air Pressure Maintenance Device Style B 17 5 3 OPERATION 18 5 3 1 Air supply Style A 18 5 3 2 Air supply Style B 18 5 4 MAINTENANCE AND INSPECTION 19 5 4 1 Air supply style A 1...

Page 5: ...be installed in a dry and clean location Verify that all equipments are properly heated and protected to prevent freezing and physical damage The unit and its components must be kept free of foreign...

Page 6: ...Key alike locks on all cabinet doors Manufactured under ISO 9001 quality control procedures 1 6 CONFIGURATION FIREFLEX N2 Blast Preaction systems are built around the Viking trim using straight throug...

Page 7: ...t in larger Fire Protection Systems those requiring more Nitrogen to compensate for the NFPA acceptable leak rate 2 5 BlastOff Leak Detection System Unless the leak rate is catastrophic the supervisor...

Page 8: ...1724 kPa working water pressure max and is available in the following diameters f 1 40 mm f 2 50 mm f 3 80 mm f 4 100 mm 3 3 RELEASE Release trim for the electric pneumatic operated double interlocke...

Page 9: ...If the system does not operate as it should make the necessary corrections according to manuals issued or consult your distributor or FIREFLEX Systems Inc 8 Make sure that building owner or a delegate...

Page 10: ...ntrol valve D1 8 When full flow develops from the drain test valve B6 CLOSE the drain test valve and verify that there is no flow from the drip check valve B7 when the plunger is pushed 9 FULLY OPEN t...

Page 11: ...S To take system out of service WARNING Placing a system out of service may eliminate the fire protection capabilities of the system Prior to proceeding notify all Authorities Having Jurisdiction Cons...

Page 12: ...l come on and the Operating green light will illuminate until the N2 storage tank pressure reaches maximum approximately 75 Psi and the compressor shuts off Reset the remote release control panel Sole...

Page 13: ...the main drain valve D3 2 Verify that low air supervisory operate within pressure setting from table 5 3 3 Close the Inspectors test valve or the main drain valve D3 4 Establish recommended air press...

Page 14: ...efer any noted problems or deficiencies to authorized service personnel for correction 4 8 5 Semi annual inspection 1 Check main water supply control valve D1 switch upon movement of the hand wheel 2...

Page 15: ...6B 0 6A Page 11 of 25 Figure 4 1 P ID Tank Provided with brackets and Strap Riser towards the nozzles N2 Blast Compressor Air Maintenance Device s AMD s Supplied by Fireflex Preaction Compressor Preac...

Page 16: ...Integrated Fire Protection System OWNER S OPERATION MAINTENANCE MANUAL Page 12 of25 FM 076B 0 6A Figure 4 2 FIREFLEX N2 Blast shown without doors FM 06LM 0 1A 4 FM 06LM 0 1A 4 See figures 4 3 4 4 for...

Page 17: ...icted orifice B4 Spring loaded check valve B5 Alarm test valve B6 Drain test valve B7 Drip check valve B8 Drain check valve B9 Pressure operated relief valve PORV B10 Emergency release valve B11 Prime...

Page 18: ...076B 0 6A Figure 4 4 FIREFLEX N2 Blast storage tank FM 06LM 0 1A 1 FM 06LM 0 1A 1 N1 Nitrogen generator air pressure maintenance device N2 Nitrogen generator air pressure maintenance device control v...

Page 19: ...system refer to chapter 4 6 PLACING THE SYSTEM BACK IN SERVICE AFTER OPERATION 5 FULLY OPEN the system shut off valve D4 Reset the remote releasing control panel Figure 4 7 Shut off valve option Main...

Page 20: ...30Vac 60Hz 220Vac 50Hz 1 6 5 0 Amp 2 5 Amp 1 3 Amp 1 3 7 4 Amp 3 7 Amp 2 5 Amp 1 2 10 0 Amp 5 0 Amp 4 0 Amp 1 18 0 Amp 9 0 Amp 6 0 Amp 115 230 Vac 60Hz air compressor selection Table H P CFM 40 PSI Sy...

Page 21: ...ry nitrogen cylinders and piped to the air inlet port of the unit Air supply style B provides an Air Pressure Maintenance Device APMD trim factory mounted in the FIREFLEX N2 Blast cabinets E16 This se...

Page 22: ...eplace the cover on the switch E2 Note Do not turn the cut out adjustment screw middle screw all the way down in one shot Proceed by steps Use the same method turning the cut out adjustment screw COUN...

Page 23: ...e pump to run hotter and results in longer operating cycles N2 Blast Nitrogen generator Intake filters The N2 BLAST FPS 250 and FPS 750 utilize three different filters The filters must be changed out...

Page 24: ...d air flow through the APMD E5 will allow Determine the appropriate pressure to be maintained in the system refer to table 5 The APMD E5 should be checked after installation or repair and adjusted as...

Page 25: ...section replaced by Dehydrator option A when used TO OPTIONAL ACCELERATOR plugged when not used FM 061H 0 118B 1 CONTRACTOR S HYDROSTATIC TEST PORT system side 2 E2 E11 TO DRAIN COLLECTOR Air option c...

Page 26: ...RATOR plugged when not used E4 plugged with SureFire trim FM 061H 0 119B 1 CONTRACTOR S HYDROSTATIC TEST PORT system side E5 TO SPRINKLER RISER E8 Note The external air supply must be restricted to in...

Page 27: ...dicated on figure 6 1 6 2 REMOTE CONTROLED FIREFLEX N2 Blast Without integrated releasing control panel For application with FIREFLEX N2 Blast unit provided without integrated releasing control panel...

Page 28: ...OUTLET TBB TBA TBC CONTROL PANEL except for Remote Controlled Unit SPRINKLER RISER SCH 40 GROOVED OUTLET T R G M D P F S FM 06LM 0 2A OPTIONAL SHUT OFF VALVE CONTROL PANEL TBA TBB TBC N Q C A B Syste...

Page 29: ...RING OF INPUT POWER SOURCE Branch circuit for air compressor shall not be the same as the control panel power source 6 7 8 9 10 11 C NO NC MAIN VALVE C NO NC SHUT OFF VALVE Contact provided for connec...

Page 30: ...other damages suffered by anyone There are no other warranties expressed or implied with regard to the products other than those contained herein Some jurisdictions may not allow limitations on how l...

Reviews: