INSTALLATION REQUIREMENTS
The fire has been designed to be installed in two main applications; either to fit into a suitable
opening created in the inner leaf of an outside wall or false chimney breast/extended fire sur-
round built to conceal the appliance. The appliance can also be fitted into an unserviceable or
inoperative fireplace served by a disused natural draught flue. It is recommended that the old
flue should be partially sealed off to prevent draughts, however some ventilation will be required
in the old flue to prevent condensation and dampness.
The cavity box and firebox must be installed onto a suitable non-combustible insulating surface
at least 12 mm thick covering the entire base area of the box. The fire must be used with a back
panel capable of withstanding 150°C minimum. Any combustible materials directly behind the
fire frame (or back panel) and close to the cavity box of the fire must be removed and replaced
with non-combustible material such as cement, browning, 'Superlux' board or equivalent materi-
als.
ROOM SIZING
The room size should be a minimum of 30m
2
(e.g. 11’6” x 11’6” x 8’) to allow adequate circula-
tion of air and ensure the correct operation of the fire. To calculate a room size in cubic metres
(m
3
) divide the room volume in cubic feet (ft
3
) by 35.3.
SITE REQUIREMENTS
The appliance may be installed by one of the following methods:
1.
Fitment against the inner face of a house wall with a suitably constructed false chimney breast
or rebated fire surround to enclose the depth of the fire. If a timber false chimney breast is con-
structed, clearances and insulation must be as for a timber constructed wall.
2.
Insertion into a purpose made opening in the inner leaf of a cavity wall or a disused conven-
tional fireplace opening. Bridging the cavity may cause unwanted moisture to track to the inside
of the house from the cavity and therefore should be avoided. Protection from moisture and
falling debris above the cavity box should be provided. If in doubt consult local building control
officers.
3.
Installation into a timber framed house wall using clearances and insulation as described in
the appropriate section. If in doubt, consult local building control officers.
The opening dimensions for insetting the appliance must be;
WIDTH :
between 410 mm and 440
mm and
HEIGHT :
between 560 mm and 580 mm high. The opening must be within these sizes
for the full depth of the cavity box in non-combustible applications. Applications involving com-
bustible materials e.g. timber battens in false chimney breasts, must use appropriate clearances
and insulation methods as described in the relevant section of these instructions.
2
APPLIANCE DATA
Gas Group
G20 Natural Gas CAT I2H
Inlet Pressure
20 mbar
Max Energy Input
Gross
2.6 kW
Net
2.35 kW
Max Gas Rate
0.25 m3/h
Min Energy Input
Gross
1.5 kW
Net
1.35 kW
Pilot Energy Input
Gross
166 W
Net
150 W
Setting Pressure
High
7.0 mbar (+/-0.25 mbar). Cold
7.5 mbar (+/-0.25 mbar). Hot
Low
2.0 mbar (+/-0.25 mbar). Cold
2.8 mbar (+/-0.25 mbar). Hot
Main Injector Burner
Stereo. Size 60 / Bray Cat 82 - 280
Gas Inlet Connection
8 mm compression
Ignition
Piezo spark
Spark Gap
4.0 mm (± 1.0mm)
Weight
20 Kg
Please see Data Badge affixed to appliance for current data.
This appliance is for use only with the gas type, and at the pressure stated on the appliance
Data Badge.
2.0
3.0
3.1
4.0
Summary of Contents for P30G FXL01
Page 2: ...FXL01...