FIRECLASS Prescient III
4.3 Panel Quiescent State
Application, Installation & Commissioning Doc. version 2
29
7
Press
SELECTEER AAN/UIT
to switch off the edit
mode (the edit mode is automatically switched off if
no buttons are pressed for 60 seconds).
8
Move the
CONFIG SLU DIL
switch on the control
board to the OFF position.
4.3
Panel Quiescent State
The panel will be in the quiescent state when the
IN
BEDRIJF LED
is on steady, either the
AUTOMATISCH
& HANDBEDIENING LED
or the
HANDBEDIENING LED
is on steady and no other indications are present on the
display board or the control board.
4.4
Auxiliary Fire Condition
If a fire condition is detected on the Auxiliary zone, the
following occurs:
The
BRAND LED
pulses
The
EXTERNE GROEP
Fire LED
pulses
The
SIGNAAL GEVERS UIT LED
pulses
The
FIRE SIGNAL
output operates and the red
SYSTEEM AKTIEF LED
operates
The Aux Zone Fire output operates
Sounder circuits 1 & 2 operate
In this state, the buzzer can be silenced, both sounder
circuits can be silenced (and re-sounded if necessary)
and the fire condition can be reset by operation of the
HERSTEL BRANDALARM
button.
4.5
Single Extinguishing Zone
Fire Condition
4.5.1
MANUAL ONLY MODE
If a fire condition is detected on either zone 1 or zone 2
while the panel is in the MANUAL ONLY mode, the fol-
lowing occurs:
The
BRAND
LED
pulses
The
GROEP 1 Fire
or
GROEP 2 Fire LED
pulses
The
SIGNAAL GEVERS UIT LED
pulses
The
FIRE SIGNAL
output operates and the red
SYSTEEM AKTIEF LED
operates
The
ZONE 1 FIRE
or
ZONE 2 FIRE
output operates
Sounder circuits 1 & 2 operate
In this state, the buzzer can be silenced, both sounder
circuits can be silenced (and re-sounded if necessary)
and the fire condition can be reset by operation of the
HERSTEL BRANDALARM
button.
4.5.2
AUTOMATIC & MANUAL MODE
If a fire condition is detected on either zone 1 or zone 2
while the panel is in the AUTOMATIC & MANUAL
mode, the following occurs:
The
BRAND LED
pulses
The
GROEP 1 FIRE
or
GROEP 2 FIRE LED
pulses
The
SIGNAAL GEVERS UIT LED
pulses
The
FIRE SIGNAL
output operates and the red
SYSTEEM AKTIEF LED
operates
The
ZONE 1 FIRE
or
ZONE 2 FIRE
output operates
Sounder circuits 1 & 2 operate
The
SYSTEEM AKTIEF LED
pulses (pre-activated
condition)
The 1st Stage Shutdown output operates
In this state, the buzzer can be silenced, both sounder
circuits can be silenced (and re-sounded if necessary),
the fire condition can be reset by operation of the
HER-
STEL BRANDALARM
button and the extinguishing pre-
activated condition can be reset by operation of the
HERSTEL BLUSSING
button.
4.6
Two Extinguishing Zones
Fire Condition
4.6.1
Manual Only Mode
If a fire condition is detected on both zone 1 and zone 2
while the panel is in the MANUAL ONLY mode, the fol-
lowing occurs:
The
BRAND LED
pulses.
The
GROEP 1 FIRE
and
GROEP 2 BRAND LED
pulses.
The
SIGNAAL GEVERS UIT LED
pulses.
The
FIRE SIGNAL
output operates and the red
SYSTEEM AKTIEF LED
operates.
The
ZONE 1 FIRE & ZONE 2 FIRE
outputs oper-
ate.
Sounder circuits 1 & 2 operate.
In this state, the buzzer can be silenced, both sounder
circuits can be silenced (and re-sounded if necessary)
and the fire condition can be reset by operation of the
HERSTEL BRANDALARM
button.
4.6.2
Automatic & Manual Mode
If a fire condition is detected on both zone 1 and zone 2
while the panel is in the AUTOMATIC & MANUAL
mode, the following occurs:
The
BRAND LED
pulses.
The
GROEP 1 FIRE
and
GROEP 2 BRAND LED
pulses.
Note
The SLU configuration is stored in EEPROM
and is retained when the panel has no power.