EQUIPMENT:

   

FIRE

CLASS 

DUO-CEL

 

 

 

 

 

PUBLICATION:

  

OM_DUO-CEL_APP 

 

 

 

 

 

ISSUE No. & DATE:

 

2     20/06/18

 

PAGE 30 of 46 

Figure 12 

– Twin-Wire EOL device 

Resistor

330R   1W

Zener Diode

17V  5W

Connect bare leads to + & - 

terminals in last zone device

Sleeved EOL device

+ve

-ve

+ve Thick Lead

-ve Thin Lead

 

11.10.4 Maximum Number of 
Detectors/MCPs on a Zone 

For  the  standard  panel  with  10uF  EOL  capacitor, 
the  maximum  number  of  detectors  &  MCPs  per 
zone is limited to 32. 

For  the  standard  panel  with  EOL  resistor,  the 
maximum  number  of  devices  allowed  on  a  zone  is 
limited  by  the  quiescent  current  drawn  by  each 
device.  The  quiescent  current  will  be  listed  on  the 
device  data  sheet  provided  by  the  Manufacturer  of 
the device. See section 7.1 for details. 

The maximum quiescent current available to  power 
devices  on  a  zone  is  1.6mA.  Exceeding  this  value 
will  prevent  the  panel  from  correctly  monitoring  for 
open circuit fault conditions. 

For  the  Twin-Wire  panel  the  maximum  number  of 
detectors & MCPs per zone is limited to 16 (or less, 
see  section  7.1)  if  sounders  are  also  connected.  If 
no  twin-wire  sounders  are  on  the  zone  then  up  to 
30  detectors  &  MCPs  may  be  connected  (see 
section  7.1  for  details).  The  maximum  number  of 
twin-wire  sounders  permitted  is  12  (or  less;  see 
section 7.1)

Note: It is a recommendation of BSEN 54-2 that 
there  should  be  no  more  than  32  detectors  & 
MCPs in a zone. 

Figure 13 

– Standard Zone Wiring Diagram 

Detector.

Smoke or Heat 

Detector with 

diode base

(Schottky Diode 

preferred)

ZONE 1

Z1 + Z1 

+

-

+

-

+

-

+

10uF 35V

end-of-line Capacitor

1       2

1A   2A

Manual Call Point.

ALERT

:

CP200, CP230,

CP260

or equivalent with 

internal resistor 

between 470R & 1K

EVACUATE

:

CP211

Or equivalent with 

internal resistor 

between 360R & 220R

 

 

 

Summary of Contents for DUO-CEL

Page 1: ...LICATION OM_FC_DUO CEL_APP ISSUE No DATE 2 20 06 18 PAGE 1 of 46 2018 Johnson Controls Tyco Fire Security GmbH Victor von Bruns Strasse 21 8212 Neuhausen am Rheinfall Switzerland DUO CEL FIRE DETECTIO...

Page 2: ...ATION 22 9 3 RESISTOR EOL 22 9 4 TWIN WIRE 22 9 5 ALERT MODE 22 9 6 SELECTABLE ZONAL OR GENERAL ALARM SOUNDER OPERATION 23 9 7 BUZZER DISABLE 23 9 8 EARTH FAULT MONITORING 23 10 PANEL REPEATERS 23 10...

Page 3: ...RELAY CONTACT CONNECTION DETAILS 27 FIGURE 10 REMOTE CONTROL I P CONNECTIONS 28 FIGURE 11 ALARM CIRCUIT CONFIGURATION 29 FIGURE 12 TWIN WIRE EOL DEVICE 30 FIGURE 13 STANDARD ZONE WIRING DIAGRAM 30 FI...

Page 4: ...housed in an Acrylonitrile Butadiene Styrene ABS Plastic enclosure with a combined display control board mounted to the back box An ABS cover is fixed over the display control board leaving the field...

Page 5: ...EARTH FAULT REPEATER FAULT REMOTE I P FAULT CONTROLS ON 1 2 3 4 5 6 7 8 2 1 1 Panel Order Codes Descriptions CEL Part No Description Internal SLA Battery Not Supplied 508 031 701 1 Zone Panel Standard...

Page 6: ...8 Zone standard motherboard 508 031 704 2605505 Repeater c w PSE motherboard 508 031 705 2605506 Repeater no PSE motherboard 508 031 706 2605533 1 Zone twin wire motherboard 508 031 707 2605534 2 Zone...

Page 7: ...th control boards consist of a PCB with all components mounted on the front All LED indicators configuration switches links and user controls are mounted on this board The board accommodates the micro...

Page 8: ...other than the PS 1230 2 2 4 Repeater Panel The repeater panel uses the same control board and enclosure as the fire alarm panel The components for the redundant circuits zones alarm circuits etc are...

Page 9: ...latching Fire indication on zone 1 Resistor or capacitor EOL monitoring applies to all zones Not functional on Twin Wire panels Zone Short Circuit gives fault or fire alarm for backwards compatibilit...

Page 10: ...nt feature The following circuits can be independently disabled enabled Each Zone Fire Signal Output All Sounders Buzzer disablement feature DIL switch selectable option to allow the buzzer and Buzzer...

Page 11: ...E INTERNAL BUZZER MICROCONTROLLER PROGRAMMING SOCKET MOUNTING TAB PCB COVER PCB REMOTEO PS SILENCE BUZZER SILENCE RESOUND ALARMS RESET DISABLE TEST EVACUATE SELECT SUPPLY ON GENERAL FIRE GENERAL FAULT...

Page 12: ...TAB PCB COVER PCB REMOTEO PS NOTE 24V 0V Terminals are only available on the DC powered repeater panel NOTE Power Supply connections and battery fuse are only on the mains powered repeater SILENCE BUZ...

Page 13: ...tomatically adjusts the output voltage to provide the optimum safe charging voltage over an operating temperature range of 5oC to 40oC The charging voltage can be adjusted via the trimmer potentiomete...

Page 14: ...ot attempt to open or access any of the internal components The power supply contains no user serviceable parts To prevent overheating the ventilation holes in the cage must not be obscured 6 2 1 DUO...

Page 15: ...e Manual Call Point Current Limit 0 000 32 16 Thorn Tyco CP230 Alert Manual call point 590R 0 000 32 5 Thorn Tyco MCP230 Alert Manual Call Point 590R 0 000 32 5 Thorn CP260 Alert Manual Call Point 538...

Page 16: ...E 1 5mm csa Resistance per Km per Core Capacitance per Km Core to Core uF Capacita nce per Km Core to Screen uF FP200 12 1 0 08 0 15 MICC PYRO Light Duty 12 1 0 19 0 21 MICC PYRO Heavy Duty 12 1 0 13...

Page 17: ...f sounders WILL NOT allow more detectors to be used unless no sounders are connected see number in brackets in the table e All detector bases must have a 1N4002 diode fitted across the line IN and lin...

Page 18: ...m Fault Yellow OFF System is working correctly ON System is not functional Microcontroller failed or EEPROM data corrupted PSU Fault Yellow OFF power supply is healthy FLASH PSU fault and or battery f...

Page 19: ...o silence sounders Press again to resound the silenced sounders When controls are unlocked Reset Press to clear any fault alarm conditions and return the panel to the quiescent state When controls are...

Page 20: ...change the circuit status from test mode to disabled causing the General Test LED to switch off and the General Disablement LED to flash NOTE Disablements are stored in EEPROM and are not lost when th...

Page 21: ...s is displayed on the zone fault LEDs LED OFF No Dependency LED ON zone configured for dependency Operation of the SELECT button will then switch the Select cursor on flashing at the zone 1 fault LED...

Page 22: ...dependency coincidence detection and Alert Mode will not work correctly 9 4 Twin Wire The Twin Wire panels support Fulleon twin wire sounders on the zone circuits along with compatible detectors see...

Page 23: ...has been disabled This feature is provided for use during panel commissioning and maintenance only Ensure that the DIL switch is returned to the OFF position after commissioning maintenance tests are...

Page 24: ...No fault on Fire Signal output FLASH Fault on Fire Signal output ON Fire Signal output Disabled or in Test Sounder Flt Dis Tst Yellow OFF No Fault on Sounder circuits FLASH Fault on one or more Sounde...

Page 25: ...ability Evacuate Operates all sounders continuously and illuminates the Alert Evac On LED until the Silence Resound Alarms button is operated When controls are unlocked Silence Buzzer Silences the int...

Page 26: ...DER OUTPUT CIRCUITS ALARM CIRCUITS AL1 AL1 AL2 AL2 AL3 AL3 AL4 AL4 8 ZONE 4 ZONE 2 ZONE FIRESIGNAL FIRE RELAY N O P N C FAULT RELAY N O P N C NOT PRESENT ON PANEL REPEATER A B B A 0V 24V REMOTE I P 0V...

Page 27: ...ed condition this must be included in the battery capacity calculations 11 4 Fire Signal Output The Fire Signal output is fault monitored in the non energised condition It is designed to operate a sig...

Page 28: ...rt Evac On LED will illuminate on the panel and the internal buzzer will sound The Evacuate output will also operate 11 7 4 Silence Alarms The Silence Alarms function allows all active sounder circuit...

Page 29: ...be calculated to ensure that the minimum voltage at the end of each circuit exceeds the minimum required by each sounding device The voltage at the end of the circuit is given by the following calcul...

Page 30: ...urrent available to power devices on a zone is 1 6mA Exceeding this value will prevent the panel from correctly monitoring for open circuit fault conditions For the Twin Wire panel the maximum number...

Page 31: ...W end of line resistor 1 2 1A 2A Manual Call Point CP200 CP211 CP230 CP260 or equivalent with internal resistor between 220R 1K Figure 15 Twin Wire Zone Wiring Diagram Detector Smoke or Heat Detector...

Page 32: ...oid DrivenBell fittedwith polarising suppression diodes 1N4002 10K W EOLResistor NOTE The Alarm circuit terminals are marked for the active polarity When in quiescent monitoring mode the alarm circuit...

Page 33: ...able types The A B lines should be connected via one set of twisted pair cores the 24V 0V lines should be connected via another set of twisted pair cores If the cable includes a screen then this shoul...

Page 34: ...tput Mains On 27 15V Nominal 26 4V 28 4V No Output Maximum Output current Mains Failed 1 4A No Output DC Voltage Output Mains Failed 27V 20V No Output Output Protection Electronic current limiting No...

Page 35: ...nal vibration Frequency range 10 Hz to 150 Hz acceleration amplitude 0 1g Electromagnetic Compatibility Mains Supply Voltage Variations BSEN 50130 4 1996 Mains Supply Voltage Dips and Interruptions BS...

Page 36: ...ort circuit threshold 37 8mA 60R Evacuate Manual Call Point alarm threshold 22 8mA 37 8mA 60R 410R Detector Alert Manual Call Point alarm threshold 11 7mA 22 8mA 410R 1k2 Quiescent 2 2mA 11 7mA 1k2 8k...

Page 37: ...ic Amps 0 7 0 7 0 7 0 7 Cable requirements Cable resistance and current load must allow a voltage at the end of line which is above the minimum operating voltage of the sounders Outputs Evacuate Activ...

Page 38: ...e requirements Cable resistance and current load must allow a voltage at the end of line which is above the minimum operating voltage of the equipment connected Repeater Output Number of repeaters 1 t...

Page 39: ...use 7 12 Dependencies on more than one alarm signal Clause 7 13 Alarm counter Clause 10 Test condition 15 3 Ancillary Functions Not Required By EN54 The DUO CEL panel offers several auxiliary function...

Page 40: ...a fire alarm condition 15 6 Minimum Standby Battery Capacity Calculation This section describes how to calculate the minimum required standby battery capacity for the control panel To determine the ba...

Page 41: ...capacity Cmin required is given by Cmin 1 25 x Tfault x Ifault 2 x Talarm x Ialarm 1000 Ah _____ x _____ _____ _____ 1000 Ah 1 25 x _____ _____ 1000 Ah 1 25 x ______ 1000 Ah 1 25 x ______ 1000 Ah ____...

Page 42: ...eater 2 Wire Sounders on zones Symphoni 0 05 5 Squashni 0 05 5 SQG3 SDR 0 05 5 SQG3 AV 0 05 5 Conventional Sounders on sounder circuits Bedlam 0 30 Banshee 0 17 Detectors on zones Tyco M600 Series Apo...

Page 43: ...r 2 5mm 24V 0V Relay coil connections observe polarity P1 Relay contact 1 pole N C Relay contact 1 normally closed N O Relay contact 1 normally open P2 Relay contact 2 pole N C Relay contact 2 normall...

Page 44: ...Zones can be configured dependency coincidence mode On 5 General Alarms sounder operation Off Zonal Alarms sounder operation On 6 Short Circuit Fault monitoring on zones Off No Short Circuit Fault Mon...

Page 45: ...bly Drawing 1 5 AMP PSU BENTEL BAQ35T24 ZONE INSERT CARD BOARD COVER DISPLAY OVERLAY CONTROL BOARD 12 WAY EARTH BAR NOT FITTED ON 1 ZONE 2 ZONE PANELS REPEATER UNITS BACKBOX FRONT COVER LOGO THERMISTO...

Page 46: ...PMENT FIRECLASS DUO CEL PUBLICATION OM_DUO CEL_APP ISSUE No DATE 2 20 06 18 PAGE 46 of 46 2018 Johnson Controls Tyco Fire Security GmbH Victor von Bruns Strasse 21 8212 Neuhausen am Rheinfall Switzerl...