CoMMissioning

Boiler check:

u

  Baffles should be checked as they may have been 

disturbed during transport.

u

  Check that the condensate trap is fitted securely, 

primed with water and piped out into a suitable drain. 
It is easier to check the trap when the boiler door is 
removed.

u

  The boiler door should be refitted, complete with 

graphite seal and then tightened.

Flue check: 

u

  The flue must be fitted correctly, with a fall back to the  

boiler. Note: internal fall of 2.5˚ within the flue.

u

  For concentric balanced flue:

 

-  the cone supplied should be inserted in to the end     
   of the flue;

 

-  the wall plate should be fitted with an opening

 

  for air under the flue;

 

-  check that the flue guard is fitted.  

u

  When installing a Combipac HE the 90˚ bend should 

be fitted pointing up.

Please refer to burner manual for the following sections:

u

  Boiler set-up.

u

  Burner settings.

u

  Flue gas analysis and fine tuning of burner.

HanDing oveR

The householder should receive:
•  A clear and concise demonstration of the boiler      
 

operation and any system controls.

•  This manual, the burner manufacturer’s manual
 

and any other instructions.

•  OFTEC forms CD10 and CD11.
•  The Boiler Passport.

The householder should be advised to:
•  Service the boiler annually and to ensure that the  
 

service records in the Boiler Passport are completed.

•  Read the terms and conditions of warranty.
•  Keep all boiler documentation in a safe place.

a commissioning record should be completed

and a copy retained by the engineer.

this can be found in the Boiler Passport.

CoMMissioning

u

  it is the responsibility of the installer to ensure 

that the boiler is properly commissioned when first 
used.

u

 the boiler should be commissioned by a 

 

 

 

competent, qualified engineer, preferably oFteC 
registered and familiar with Firebird products.

u

  the installation certificate and the commissioning 

certificate within the Boiler Passport should be 
completed and posted to Firebird within 28 days 
of installation (this can also be done online on the 
Firebird website). a copy should be retained by the 
commissioning engineer.

u

  the system should be checked thoroughly.

CHeCKlist FoR installing anD

CoMMissioning a FiReBiRD BoileR

Pre-installation check:

Is  the  following  documentation  included  with  the       
boiler, installation manual, boiler passport, burner 
manufacturer’s manual?

u

  Is the base on which the boiler is to be installed solid?

u

  Allow sufficient room for future servicing of the boiler.

Where does the flue terminate:

u

  Make sure there is no window, door or fence within 1 

metre of the flue-terminal.

u

  If the flue terminates in a corner or into an allyway,         

re-circulation of the combustion gases in the air intake 
could occur. A plume dispersal may be required or 
an alternative flue arrangement might be available. 
Contact the Firebird technical department for advise.

u

  The  appropriate  class  1  flue  must  be  used  with  a           

conventional flue installation. Contact Firebird if 
unsure.

Power supply:

u

  Is a timed, permanent, power supply available, via a 

fused spur with a 230V 50Hz mains electrical supply 
and a 5A fuse?

liquid fuel supply:

u

  The burner is set for 28 Second Class C2 fuel.

u

  A 15 micron oil filter should be placed in line with an 

isolating valve prior to entry to the burner.

u

  There must be a remote sensing fire valve.

u

  Verify that the fuel tank has been installed correctly as 

per building standards.

Summary of Contents for Envirogreen Combi HE

Page 1: ...the householder once installation is complete Combi HE Combipac HE Slimline Combi HEATING SOLUTIONS ENVIRONMENT INNOVATION TECHNOLOGY Technical Manual Condensing BoileR C o m b i H E C o m b i p a c H...

Page 2: ......

Page 3: ...nd efficiency of all domestic central heating oil boilers Our boilers and burners are supplied as matched units Page 1 Safety 2 2 Standards Regulations 3 2 1 Condensate Disposal 4 2 2 Flue Regulations...

Page 4: ...ht following eye contact or prolonged reddening of the skin The small quantities of adhesives and sealants used in the product are cured They present no known hazards when used in the manner for which...

Page 5: ...Building Regulations To ensure the highest standards of installation safety it is important that the boiler be installed in compliance with the following regulations where applicable It is the respon...

Page 6: ...r in an unheated garage should not exceed 3 meters and Should be lagged with water proof insulation to prevent freezing Boiler Sealed Condensate Drain Discharge Pipe 75mm Soak Away Lime Stone Chipping...

Page 7: ...of the boiler on the base fixed to the casing of the boiler or mounted on the wall alongside the boiler Condensate pump wired in to come on with burner Inlet connected to condensate trap at base of bo...

Page 8: ...1 STANDARDS REGULATIONS Condensate Disposal Condensate Trap Fitting 1 Push washer into trap socket and screw trap onto boiler socket 2 Push flexible pipe onto trap socket 3 Final assembly Washer S S...

Page 9: ...Q R Pressure Jet Location Appliance Burner Type Condensing UK ROI NI A Directly below an opening airbrick opening window etc 1000mm 600mm B Horizontally to an opening airbrick opening window etc 1000m...

Page 10: ...ved for low level flue and low level balanced flue discharge when tested to BS EN 303 1 5 Terminating positions must be at least 1 8m distant from a fuel storage tank unless a wall with at least 30 mi...

Page 11: ...disperse vapours 3 The effect of the moisture generated must be considered in relation to the possible corrosion of metal parts it might reach and to the possible formation of ice on pathways in freez...

Page 12: ...ate System 35 flexible liner suitable for condensing applications System 35 adaptor 500mm Adjustable length Boiler adaptor Condensing boiler Condensing boiler NOTE All brick chimney constructions must...

Page 13: ...piers with a waterproof membrane between the piers of the tank Fuel storage tanks should not be sited within 1 8m of boiler flue outlets Do not allow household waste or hot ashes container in vicinity...

Page 14: ...ause Burner Lockout The boiler is factory fitted with a burner control box lockout safety feature which operates automatically if a fault occurs in the burner operation Should this occur the light on...

Page 15: ...uate temperature controls to ensure return values are as stated above PLASTIC PIPING The boiler thermostat control and safety system is not designed and must not be relied on to protect plastic pipe f...

Page 16: ...not allow the unit to exceed 1 bar while filling and a maximum of 2 bar when the radiators are at full operating temperature The automatic air vent will allow air to dispel from the boiler To remove a...

Page 17: ...ost protection It is also required to operate the post purge function on the burner when applicable If a permanent live supply is not provided the burner will not operate Permanent live Earth Neutral...

Page 18: ...d flue TOP mark Snorkel 1 Push the flap valve into the balanced flue air intake 2 Ensure that the flap valve is in the correct position 3 Push the snorkel hose over the flap valve and air intake and s...

Page 19: ...ls may not be sufficient to cope with plume dispersal from a condensing boiler 3 17 3 2 Combi HE Combipac HE INSTALLER GUIDELINES 90 terminal should be tilted up to prevent condensate droping from end...

Page 20: ...760 300 157 61 642 372 344 72 40 676 47 Model Envirogreen output range Weight kg Dimensions mm H W D A C E F G I J K M N Envirogreen Combipac HE 12 20kW 200 945 720 625 795 180 95 691 285 351 133 34...

Page 21: ...1 Heat deflector ACC000HTD ACC000HTD ACC000HTD 12 1 Air hose ACC000SSH ACC000SSH ACC000SSH 13 1 Flap valve ACC000FLP ACC000FLP ACC000FLP 14 1 Control panel ACP001CCE ACP001CCE ACP001CCE 15 1 Casing r...

Page 22: ...1 1 Heat deflector ACC000HTD ACC000HTD ACC000HTD 12 1 Flap valve adapter ACC000FVA ACC000FVA ACC000FVA 13 1 Flap valve ACCOOOFLP ACCOOOFLP ACCOOOFLP 14 1 Control panel ACP001CCP ACP001CCP ACP001CCP 15...

Page 23: ...ue Assembly 125 5 mm dia 125 5 mm dia 125 5 mm dia Max Low Level Flue Length 1 5m 1 5m 1 5m Max High Level Balanced Flue Length 6m 6m 6m Heating System Sealed Fit in accordance with BS 7074 Part 1 BS...

Page 24: ...perates automatically if a fault occurs in the burner operation Should this occur the light on the front of the burner will illuminate Press the reset button a maximum of two times If the boiler fails...

Page 25: ...ufacturer for their instruction on how to ensure their product never overheats Our boiler control and safety high limit thermostats are not designed to fulfil this function Firebird accepts no respons...

Page 26: ...ith a 5A fuse This appliance must be earthed A qualified electrician must carry out all electric wiring in accordance with current ETCI IET Regulations and any local regulations which may apply The bo...

Page 27: ...nced flue TOP mark Snorkel 1 Push the flap valve into the balanced flue air intake 2 Ensure that the flap valve is in the correct position 3 Push the snorkel hose over the flap valve and air intake an...

Page 28: ...760 147 325 80 Envirogreen Slimline Combi 20 26kW 168 855 520 600 760 147 325 80 A W H I D A C J Cut out 70x130 mm 770 730 750 780 65 45 80 120 135 Front View Side View Rear View Top View Central heat...

Page 29: ...ose ACC000FLX ACC000FLX 10 1 Stat pocket ACC001PKT ACC001PKT 11 1 Heat deflector ACC000HTD ACC000HTD 12 1 Air hose ACC000SSH ACC000SSH 13 1 Flap valve ACC000FLP ACC000FLP 14 1 Control panel ACP001CSL...

Page 30: ...125 5 mm dia Max Low Level Flue Length 1 5m 1 5m Max High Level Balanced Flue Length 6m 6m Heating System Sealed Fit in accordance with BS 7074 Part 1 BS 5449 OFTEC standards and all other relevant le...

Page 31: ...that the boiler is properly commissioned when first used u The boiler should be commissioned by a competent qualified engineer preferably OFTEC registered and familiar with Firebird products u The ins...

Page 32: ...es including the tubular baffles in the condensing section and clean them 2 Remove the condensate trap and clean it place a tray under the connection for the trap Vacuum out any loose debris from the...

Page 33: ...t be in accordance with a instruction technical manuals b all relevant standards and codes of practice 4 A competent qualified engineer preferably OFTEC registered using the correct installation and t...

Page 34: ...ace Heating Water Heating elmax kW elmin kW PSB kW ENVIROGREEN Combi HE 12 20kW A B 20 93 75 62 21 46 0 155 0 051 0 002 20 26kW A B 26 93 74 80 21 47 0 143 0 046 0 002 26 35kW A B 35 93 70 109 23 52 0...

Page 35: ......

Page 36: ...ts please contact Firebird Heating Solutions Ltd dar s Industrial Estate Baile Mhic re Co Cork P12 HK51 Ireland t 353 0 26 45253 f 353 0 26 45309 e info firebird ie web www firebird ie Firebird Heatin...

Reviews: