MP-12/24 Fire Alarm Control Panel    Document 15440:G    6/6/96

7

Optional Modules

The MP-12/24 will accept one of the following optional modules:

• Dry Alarm Contacts (MP-AC12; MP-AC24). Two Form-C rated 3 A @ 120 VAC and 30 VDC (resistive).
•  Dry Alarm and Trouble Contacts (MP-AT12; MP-AT24). One Form-C Alarm and one Form-C Trouble,

both rated 3 A @ 120 VAC and 30 VDC (resistive).

• Remote Station Output Modules Models MP-TRT12 and MP-TRT24 output alarm and trouble. Models

MP-TR12 and MP-TR24 output alarm only.

Activation: By any zone alarm.
Disconnect: By an internal service switch, off-normal switch produces audible and visual trouble signals.
Remote Station Type: (MP-12) 12 VDC polarity reversal; (MP-24)  24 VDC polarity reversal.
Internal Resistance of Remote Station Output: (MP-12) 112 ohms; (MP-24) 660 ohms.
Ripple Voltage: Less than 2.0 Vp-p.
(Not suitable for separate transmission of both alarm and trouble signals to Remote Station).

System Control Switches

• Reset
• Trouble Silence
• Disable

System Status Indicators

• Red Zone alarm LED.
• Yellow system trouble LED.
• Green AC power LED.

Figure 3.1:  Component and Terminal Locations

Transformer
Harness
Connector

AC Circuit
Breaker

Optional Module
Connector

+    -     -    +    -

{

Initiating

Device

Circuits

Alarm

LEDs

Reset
Switch

Trouble

LED

Disable
Switch

Trouble
Silence
Switch

AC Power

LED

Battery
Connector

Hot

Neutral

{

Primary

AC Power

No Connection

Notification

Appliance

Circuit

{

Summary of Contents for MP-12

Page 1: ...12 Clintonville Road Northford CT 06472 MP 12 24 Fire Alarm Control Panel Instruction Manual P N 15440 G ECN 96 200 Document 15440 6 6 96 Rev G...

Page 2: ...yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body Use static suppressive packaging to protect electronic assemblies removed from the uni...

Page 3: ...Notification Appliance Circuits 6 External Device Power 6 Battery Charger 6 Optional Modules 7 Section Four Installation Instructions 8 PC Board Removal 8 Optional Module Installation 8 PC Board Inst...

Page 4: ...be used to notify a remote station or initiate a supplementary control function Standard Features A trouble circuit which monitors the following fault conditions Open detector loop s Low battery volta...

Page 5: ...AC The green LED is on when the control panel is operating from the AC power source Yellow and green LEDs both flash to indicate below normal line voltage brown out An extinguished green LED indicates...

Page 6: ...ting devices per zone 40 mA 10 mA Main Notification Appliance bell Circuits Activation By any zone alarm Disconnect By DISABLE switch Operation Style Y Class B Notification Appliances Use polarized UL...

Page 7: ...udible and visual trouble signals Remote Station Type MP 12 12 VDC polarity reversal MP 24 24 VDC polarity reversal Internal Resistance of Remote Station Output MP 12 112 ohms MP 24 660 ohms Ripple Vo...

Page 8: ...oard Cabinet and Dress Panel Optional Module Installation If an optional module is required mount it to the main printed circuit board as follows Refer to Figure 3 1 for location information Remove th...

Page 9: ...on the system door and mark the dry contacts used as non power limited circuits Note 1 Indicates non trouble state Note 2 All contacts rated 3 A 120 VAC 30VDC Note 3 For wiring refer to UL power limi...

Page 10: ...ng for non power limited circuits and the upper knockout for power limited circuits Module shown connected to non power limited circuit Module shown connected to power limited circuit Field Wiring All...

Page 11: ...e End of Line Resistor ELR from the control panel and install on terminals of the last initiating device Four Wire Smoke Detectors Power for four wire smoke detectors may be obtained from terminals 5...

Page 12: ...tral and 2 to a separate protected circuit coming directly from the line side of the main power feed to the building No other equipment may be connected to the fire alarm power circuit Wire must run c...

Page 13: ...n Appliances sound and alarm LED lights Reset system Repeat for each zone 2 Momentarily activate the following switches one at a time and check for a trouble signal RESET DISABLE 3 Depress the TROUBLE...

Page 14: ...determine as soon as possible if the problem is internal to the panel or in the external circuits Spare components known to be good are essential to fast efficient troubleshooting Follow the step by s...

Page 15: ...MP 12 24 Fire Alarm Control Panel Document 15440 G 6 6 96 15...

Page 16: ...43 A 0 050 A 0 056 A 1 The table shows the maximum current available for the operation of external power consuming devices connected to the control panel for different capacity standby batteries 2 Pow...

Page 17: ...MP 12 24 Fire Alarm Control Panel Document 15440 G 6 6 96 17 NOTES...

Page 18: ...MP12 24 Fire Alarm Control Panel Document 15440 G 6 6 96 18 NOTES...

Page 19: ...MP 12 24 Fire Alarm Control Panel Document 15440 G 6 6 96 19 NOTES...

Page 20: ...g constitutes the only warranty made by Fire Lite with respect to its products Fire Lite does not represent that its products will prevent any loss by fire or otherwise or that its products will in al...

Reviews: