background image

MP-12/24 Fire Alarm Control Panel    Document 15440:G    6/6/96

11

Power Limiting Notes Continued

• For back knockouts, place the wire ties as shown in Figure 4.5.

• Use a lower knockout to run the wiring for non-power limited circuits and the upper knockout for

power limited circuits.

Alarm Initiating Devices

Wire all alarm initiating devices, including manual stations, heat detectors and smoke detectors, to zone
input terminals as shown in Figure 4.3. Refer to device data sheet for device connection information. Ob-
serve polarity when connecting polarized devices. Zone input terminals and polarity are:

Zone 1 Input: Terminal 7 positive, Terminal 6 negative.
Zone 2 Input: Terminal 7 positive, Terminal 8 negative.

All initiating devices connected to a given zone must be wired sequentially for proper supervision. Connect
the first device to the control panel, the second device connects to the first device, the third to the second
and so on. Remove the End-of-Line Resistor (ELR) from the control panel and install on terminals of the last
initiating device.

• Four-Wire Smoke Detectors

Power for four-wire smoke detectors may be obtained from terminals 5 (negative) and 7 (positive).
Supervise detector power with a listed end-of-line relay. Maximum current from terminals 5 and 7
should not exceed 100 mA. Two-wire detectors are recommended.

• Two-Wire Smoke Detectors

Compatible two-wire detectors can be connected directly to the zone input terminals. Polarity must
be observed. Two-wire detectors receive operating power from the zone terminals. Detector power
and alarm signals are transmitted through the same wires. The total peak standby detector current
per zone cannot exceed 2 mA. Compatible detectors are listed in the Device Compatibility Docu-
ment.

• Sprinkler System Waterflow Alarm Devices

Normally open waterflow alarm devices may be connected to this panel provided the system is used
in conjunction with a mechanical water motor gong.

Module shown connected to

power-limited circuit.

Module shown connected to

non power-limited circuit.

Figure 4.5:  Typical wiring diagram for back knockouts

Summary of Contents for MP-12

Page 1: ...12 Clintonville Road Northford CT 06472 MP 12 24 Fire Alarm Control Panel Instruction Manual P N 15440 G ECN 96 200 Document 15440 6 6 96 Rev G...

Page 2: ...yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body Use static suppressive packaging to protect electronic assemblies removed from the uni...

Page 3: ...Notification Appliance Circuits 6 External Device Power 6 Battery Charger 6 Optional Modules 7 Section Four Installation Instructions 8 PC Board Removal 8 Optional Module Installation 8 PC Board Inst...

Page 4: ...be used to notify a remote station or initiate a supplementary control function Standard Features A trouble circuit which monitors the following fault conditions Open detector loop s Low battery volta...

Page 5: ...AC The green LED is on when the control panel is operating from the AC power source Yellow and green LEDs both flash to indicate below normal line voltage brown out An extinguished green LED indicates...

Page 6: ...ting devices per zone 40 mA 10 mA Main Notification Appliance bell Circuits Activation By any zone alarm Disconnect By DISABLE switch Operation Style Y Class B Notification Appliances Use polarized UL...

Page 7: ...udible and visual trouble signals Remote Station Type MP 12 12 VDC polarity reversal MP 24 24 VDC polarity reversal Internal Resistance of Remote Station Output MP 12 112 ohms MP 24 660 ohms Ripple Vo...

Page 8: ...oard Cabinet and Dress Panel Optional Module Installation If an optional module is required mount it to the main printed circuit board as follows Refer to Figure 3 1 for location information Remove th...

Page 9: ...on the system door and mark the dry contacts used as non power limited circuits Note 1 Indicates non trouble state Note 2 All contacts rated 3 A 120 VAC 30VDC Note 3 For wiring refer to UL power limi...

Page 10: ...ng for non power limited circuits and the upper knockout for power limited circuits Module shown connected to non power limited circuit Module shown connected to power limited circuit Field Wiring All...

Page 11: ...e End of Line Resistor ELR from the control panel and install on terminals of the last initiating device Four Wire Smoke Detectors Power for four wire smoke detectors may be obtained from terminals 5...

Page 12: ...tral and 2 to a separate protected circuit coming directly from the line side of the main power feed to the building No other equipment may be connected to the fire alarm power circuit Wire must run c...

Page 13: ...n Appliances sound and alarm LED lights Reset system Repeat for each zone 2 Momentarily activate the following switches one at a time and check for a trouble signal RESET DISABLE 3 Depress the TROUBLE...

Page 14: ...determine as soon as possible if the problem is internal to the panel or in the external circuits Spare components known to be good are essential to fast efficient troubleshooting Follow the step by s...

Page 15: ...MP 12 24 Fire Alarm Control Panel Document 15440 G 6 6 96 15...

Page 16: ...43 A 0 050 A 0 056 A 1 The table shows the maximum current available for the operation of external power consuming devices connected to the control panel for different capacity standby batteries 2 Pow...

Page 17: ...MP 12 24 Fire Alarm Control Panel Document 15440 G 6 6 96 17 NOTES...

Page 18: ...MP12 24 Fire Alarm Control Panel Document 15440 G 6 6 96 18 NOTES...

Page 19: ...MP 12 24 Fire Alarm Control Panel Document 15440 G 6 6 96 19 NOTES...

Page 20: ...g constitutes the only warranty made by Fire Lite with respect to its products Fire Lite does not represent that its products will prevent any loss by fire or otherwise or that its products will in al...

Reviews: