LDM-32F PN 50055:C 03/20/01
29
4. LDM Communications
Receive Only LDM-32Fs
For duplicate annunciation of system points, LDMs can be configured for
Receive Only annunciation. Receive Only LDMs must be set to the same
address as the LDM they duplicate, but are not fully supervisable. Receive
Only LDMs intercept information being transmitted to a Receive/Transmit
LDM so that this information can be duplicated at an intermediate display
location. When configured for Receive Only operation, LDMs cannot transmit
information to the host control panel. Remote Acknowledge, Silence, or Reset
cannot be performed. Control switches on Receive Only LDMs are for local
lamp test only. If a Receive/Transmit LDM is located at the end of the EIA-
485 bus, it will provide supervision of Receive Only LDMs located on the EIA-
485 bus between the Receive/Transmit LDM and the FACP.
Receive/Transmit LDM-32F
LDMs that are configured to serve as full-function annunciators can both
receive status information for annunciation as well as transmit commands to
the control panel through custom-wired point control switches. This allows the
LDM to initiate control panel switch functions from a remote location in
addition to displaying the status of the system. In order for wiring connecting
all Receive/Transmit LDMs to be supervised, the LDM-32F addressed as '01'
must be placed at the end of the EIA-485 loop farthest from the FACP. Only
address '01' is supervised.
Figure 20 LDM-32F Supervision
Fire Alarm Control Panel
Receive/Transmit LDM-32F
Set to Address X
Receive Only LDM-32F
Set to Address X
LDM-32F LDM-E32F
LDM-32F LDM-E32F
EIA-485 Circuit
Ld
msupv.cd
r
Summary of Contents for LDM-32F
Page 4: ...4 LDM 32F PN 50055 C 03 20 01 This page intentionally left blank...
Page 8: ...8 LDM 32F PN 50055 C 03 20 01 This page intentionally left blank...
Page 16: ...1 Introduction Related Documentation 16 LDM 32F PN 50055 C 03 20 01 NOTES...
Page 28: ...3 Operation Graphic Annunciator Lamps LEDs 28 LDM 32F PN 50055 C 03 20 01 NOTES...
Page 30: ...4 LDM Communications Receive Transmit LDM 32F 30 LDM 32F PN 50055 C 03 20 01 NOTES...
Page 50: ...Appendix B MS 9200 Configuration 50 LDM 32F PN 50055 C 03 20 01 NOTES...
Page 61: ...LDM 32F PN 50055 C 03 20 01 61...
Page 62: ...62 LDM 32F PN 50055 C 03 20 01...