Audio Command Center Series Manual —
P/N 51889:E1 6/8/2010
133
MS-5UD-3/7 and MS-10UD-3/7
Programmed Activation by FACP
Press the down arrow key 3 times until the following screen is displayed.
Press the
2
key to display the following screen:
Using these screens, the programmer can assign an audio message to each input zone. The selected
message will play when the FACP is connected to an ACC-25/50ZS/T audio panel via the ANN-
BUS and the corresponding FACP input goes into alarm. The factory default setting is Message 2.
Repeat the procedure outlined above for each speaker zone and then exit Programming by pressing
the Escape
(ESC)
key to save the programming changes. Test the system to ensure proper opera-
tion.
Programming an FACP Zone as an ALL-CALL Zone
To Program a an FACP Zone as an ALL-CALL Zone, press
2
while viewing the following screen:
INPUT ZONE 1
1=FREEZE SUPV. NO
2=ACC MSG#
ZONE MESSAGE
1=NO MESSAGE
2=MESSAGE 1
3=MESSAGE 2
ZONE MESSAGE
1=MESSAGE 3
2=MESSAGE 4
3=MESSAGE 5
1=READ STATUS MODE
2=PROGRAMMING MODE
3=FUTURE USE
4=REMOTE DOWNLOAD