Fire feature L38DF-ST Installation Operation & Maintenance Download Page 8

Page

L38DF-ST See-thru Gas Fireplace

Part No. XG0810

f i r e   f e a t u r e

Side Vent Venting Requirements

If your installation requires more than 12" of horizontal venting, some 

vertical lift is required. Use the vent graph below to determine an 

acceptable vent run. Unacceptable venting can affect the fireplace's 

performance.

  the maximum horizontal vent run is 16 feet

The Venting Graph

Measure the vertical height from the fireplace hearth to the centre of 

the termination and the horizontal run from the from the fireplace flue 

collar to the wall flange of the termination. Plot on the Venting Graph 

(Fig. 6) with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the 

installation is acceptable.

Example A: (Acceptable Installation)

If the vertical dimension from the hearth is 82", and the hori

-

zontal run to the wall flange of the vent termination is 156", this 

would be an acceptable installation.

Example B: (Acceptable Installation)

If the vertical dimension from the hearth is 72" and the horizontal 
run to the wall flange of the vent termination is 36", this would be 
an acceptable installation.

Example C: (Unacceptable Installation)

If the vertical dimension from the floor of the fireplace is 48" and 
the horizontal run to the wall flange of the vent termination is 
108", 

this would NoT be an  acceptable installation.

Figure 13a.

 L38DF -ST Side Vent Venting Graph

NOTES: 

All dimension lengths for vertical or horizontal runs are 

measured from centre of the vent pipe.

 

Venting runs 

must

 fall within the limits set by the venting 

graph (see Figure 9a).

Installation

26 1/2

A

C

B

Figure 11.

 Vertical venting with 1 offset (1 offset= two 

90° bends).

Figure 12.

  Vertical venting with 2 offsets (1 offset= two 

90° bends).

For venting with four 90° a restrictor may need to be used. (PEXT 

5/8 Vent).

Caution: 

The Installation shown in Figure 12., only 5/8 (PEXT) 

Vent to be used.

p

Summary of Contents for L38DF-ST

Page 1: ...s supplier s instructions If you cannot reach your gas supplier call the fire department For Your Safety Do not store or use gasolineorotherflammable vapors and liquids in the vicinity of this or any...

Page 2: ...ted in this manual Consult your local Gas Inspection Branch on installation requirements for factory built gas fireplaces Installation repairs should be done by a qualified contractor Installations in...

Page 3: ...e clearances apply to all dimensions except the framed opening where the clearance to combustibles is 0 The L38DF ST clearance to unprotected combustible walls which are perpendicular to the fireplace...

Page 4: ...by closing its individual manual shut off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 psig 3 5 kPa Vent Installation This section cove...

Page 5: ...s in the termination MSR PTO 3F 5 8 PTO 3F 5 8 PTO 3F 5 8 PTKOG 5 8 1 Ensure that the two long mounting brackets are facing the bottom ofthetermination Seeinset Thiswillprovidemoreheatprotection at th...

Page 6: ...Venting runs must fall within the limits set by the venting graph see Figure 9a Figure 8 Retracted Installation using a combination of solid and flex venting Use the vent graph to determine your allow...

Page 7: ...ination PVTK 1 B Flex Sections PFL 1 12 Section PFL 2 24 Section PFL 3 36 Section PFL 4 48 Section C Rigid Sections PEXT 1 12 m f Section PEXT 2 24 m f Section PEXT 3 36 m f Section PEXT 4 48 m f Sect...

Page 8: ...ll flange of the vent termination is 156 this would be an acceptable installation Example B Acceptable Installation If the vertical dimension from the hearth is 72 and the horizontal run to the wall f...

Page 9: ...onents using the chart on Page 8 Figure 16 Extended horizontal installation using a combination of rigid and flex venting Figure 15 Heat Shield for short horizontal installation Install by slid ing ov...

Page 10: ...ace Note Flame characteristics will change if the maximum vent height is used Minimum clearance to combustible construction around the vent pipe is 1 on all sides must be maintained except on horizont...

Page 11: ...fireplace with a non combustible material Please Note The decorative facing materials may be subject to temperatures in excess of 250 F This should be considered when selecting facing materials We rec...

Page 12: ...oors Both Sides Typical Cautions DO NOT OPERATE THIS FIREPLACE WITHOUT THE GLASS DOOR OR WITH A BROKEN GLASS DOOR p Cautions 5 1 60 Supply G L1 L2 NOTE If any of the original wire supplied with the ap...

Page 13: ...Off Gas To Appliance Operation Model L38DF ST 3 Push in gas control knob slightly and turn clockwise to Off Do not force 4 Flip up the lower trim 1 Turn off remote switch 2 Flip down the lower trim 1...

Page 14: ...not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructio...

Page 15: ...ing Instructions To Turn Off Gas To Appliance 1 STOP Read the safety information above on this label 2 Flip down the lower trims 3 If the switch on the control module is set to Continuous Pilot Off th...

Page 16: ...o inspect the appliance and to replace any part of the control system and any gas control which has been under water p p p p p Operation Lighting Instructions See pages 13 to 15 Burner Adjustment The...

Page 17: ...s appear until the bubbling stops completely Figure 34 Pilot Burner Troubleshooting The following is a troubleshooting chart of possible problems PROBLEM CORRECTIVE ACTION Noisy Pilot Flame Locate pil...

Page 18: ...subjected to normal use The Gas Appliances are designed to burn gas only Burning conventional fireplace fuels such as wood coal or any other solid fuel will cause damage to the Gas Appliance will prod...

Page 19: ...feet minimum in the United States 6 feet 1 8 m minimum in Canada L clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance 16 inches 41 cm minimum f...

Page 20: ...rade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS...

Page 21: ...Part No XG0810 f i r e f e a t u r e Maintenance Notes Spare Parts L38DF ST L DF ST NG Gas Valve RGC1006 LP Gas Valve RGC1005 NG Pilot RPA020 LP Pilot RPA021 Burner NG RBL38501 Burner LPG RBL38502 ROR...

Page 22: ...Canadian Heating Products Inc Langley BC V4W 4A1 Montigo Del Ray Corp Ferndale WA 98248 XG0810 041808 f i r e f e a t u r e...

Reviews: