Fire feature L38DF-ST Installation Operation & Maintenance Download Page 20

Page 0

L38DF-ST See-thru Gas Fireplace

Part No. XG0810

f i r e   f e a t u r e

 

                   

                       

 

Amendment

 

 

 

  (Gas Fireplace / Equipment sold in the State of Massachusetts)

 

 

 

 

   5.08: Modifications to NFPA-54, Chapter 10

 

(1) Revise NFPA-54 section 10.5.4.2

 

by adding a second exception as follows:

Existing chimneys shall be permitted to have their use continued when a gas conversion burner is installed, and shall be equipped with a manually reset device 

that will automatically shut off the gas to the burner in the event of a sustained back-draft

.

 

(2) Revise 10.8.3

 by 

adding the following additional requirements:

(a) For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, 

including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in 

the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied: 

 

1. INSTALLATION OF CARBON MONOXIDE DETECTORS.

 

At the time of installation of the side wall horizontal vented gas fueled equip

-

ment, the installing plumber or gas fitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back-up is installed on the floor 

level where the gas equipment is to be installed. In addition, the installing plumber or gas fitter shall observe that a battery operated or hard wired carbon 

monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled 

equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon 

monoxide detectors

a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired carbon monoxide detector with 

alarm and battery back-up may be installed on the next adjacent floor level.

b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall have a period of thirty (30) days 

to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm 

shall be installed.

 

2. APPROVED CARBON MONOXIDE DETECTORS.

 

Each carbon monoxide detector as required in accordance with the above provisions 

shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified. 

 

3. SIGNAGE.

 

A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet 

above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print 

size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.

 

4. INSPECTION.

 The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, 

upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4. 

(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4: 

 

1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54 as adopted by the 

Board; and 

 

2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the dwelling, building or struc

-

ture used in whole or in part for residential purposes.  

 

(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED

. When the manufacturer of Product 

Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions 

provided by the manufacturer for installation of the equipment and the venting system shall include:

 

1. Detailed instructions for the installation of the venting system design or the venting system components; and

 

2. A complete parts list for the venting system design or venting system. 

 

(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED

. When the manufacturer of a Prod

-

uct Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, 

the following requirements shall be satisfied by the manufacturer:

 

1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and 

 

2. The “special venting systems”

 shall be Product Approved by the Board, and the instructions for that system shall include a parts list and 

detailed installation instructions. 

(e) A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting instructions, all parts lists for 

venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.

 

(3) After NFPA-54 section 10.10.4.2

 add a new section 10.10.4.3 as follows:

When more than four gas appliances are to be vented through a common gas vent or common horizontal vent manifold, a plan of the proposed vent installation 

shall be submitted to the Inspector and the serving gas supplier for review and approval.

Extraction from: Massachusets Rules and Regulations

5.00: Amendments To 2002 Edition Of ANSI Z223.1-NFPA-54

Appendix B - State of  Massachusetts

Summary of Contents for L38DF-ST

Page 1: ...s supplier s instructions If you cannot reach your gas supplier call the fire department For Your Safety Do not store or use gasolineorotherflammable vapors and liquids in the vicinity of this or any...

Page 2: ...ted in this manual Consult your local Gas Inspection Branch on installation requirements for factory built gas fireplaces Installation repairs should be done by a qualified contractor Installations in...

Page 3: ...e clearances apply to all dimensions except the framed opening where the clearance to combustibles is 0 The L38DF ST clearance to unprotected combustible walls which are perpendicular to the fireplace...

Page 4: ...by closing its individual manual shut off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1 2 psig 3 5 kPa Vent Installation This section cove...

Page 5: ...s in the termination MSR PTO 3F 5 8 PTO 3F 5 8 PTO 3F 5 8 PTKOG 5 8 1 Ensure that the two long mounting brackets are facing the bottom ofthetermination Seeinset Thiswillprovidemoreheatprotection at th...

Page 6: ...Venting runs must fall within the limits set by the venting graph see Figure 9a Figure 8 Retracted Installation using a combination of solid and flex venting Use the vent graph to determine your allow...

Page 7: ...ination PVTK 1 B Flex Sections PFL 1 12 Section PFL 2 24 Section PFL 3 36 Section PFL 4 48 Section C Rigid Sections PEXT 1 12 m f Section PEXT 2 24 m f Section PEXT 3 36 m f Section PEXT 4 48 m f Sect...

Page 8: ...ll flange of the vent termination is 156 this would be an acceptable installation Example B Acceptable Installation If the vertical dimension from the hearth is 72 and the horizontal run to the wall f...

Page 9: ...onents using the chart on Page 8 Figure 16 Extended horizontal installation using a combination of rigid and flex venting Figure 15 Heat Shield for short horizontal installation Install by slid ing ov...

Page 10: ...ace Note Flame characteristics will change if the maximum vent height is used Minimum clearance to combustible construction around the vent pipe is 1 on all sides must be maintained except on horizont...

Page 11: ...fireplace with a non combustible material Please Note The decorative facing materials may be subject to temperatures in excess of 250 F This should be considered when selecting facing materials We rec...

Page 12: ...oors Both Sides Typical Cautions DO NOT OPERATE THIS FIREPLACE WITHOUT THE GLASS DOOR OR WITH A BROKEN GLASS DOOR p Cautions 5 1 60 Supply G L1 L2 NOTE If any of the original wire supplied with the ap...

Page 13: ...Off Gas To Appliance Operation Model L38DF ST 3 Push in gas control knob slightly and turn clockwise to Off Do not force 4 Flip up the lower trim 1 Turn off remote switch 2 Flip down the lower trim 1...

Page 14: ...not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructio...

Page 15: ...ing Instructions To Turn Off Gas To Appliance 1 STOP Read the safety information above on this label 2 Flip down the lower trims 3 If the switch on the control module is set to Continuous Pilot Off th...

Page 16: ...o inspect the appliance and to replace any part of the control system and any gas control which has been under water p p p p p Operation Lighting Instructions See pages 13 to 15 Burner Adjustment The...

Page 17: ...s appear until the bubbling stops completely Figure 34 Pilot Burner Troubleshooting The following is a troubleshooting chart of possible problems PROBLEM CORRECTIVE ACTION Noisy Pilot Flame Locate pil...

Page 18: ...subjected to normal use The Gas Appliances are designed to burn gas only Burning conventional fireplace fuels such as wood coal or any other solid fuel will cause damage to the Gas Appliance will prod...

Page 19: ...feet minimum in the United States 6 feet 1 8 m minimum in Canada L clearance to non mechanical air supply inlet to building or the combustion air inlet to any other appliance 16 inches 41 cm minimum f...

Page 20: ...rade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS...

Page 21: ...Part No XG0810 f i r e f e a t u r e Maintenance Notes Spare Parts L38DF ST L DF ST NG Gas Valve RGC1006 LP Gas Valve RGC1005 NG Pilot RPA020 LP Pilot RPA021 Burner NG RBL38501 Burner LPG RBL38502 ROR...

Page 22: ...Canadian Heating Products Inc Langley BC V4W 4A1 Montigo Del Ray Corp Ferndale WA 98248 XG0810 041808 f i r e f e a t u r e...

Reviews: