
11
Maintenance of the OS2200
Maintenance of the OS2200
Maintenance of the OS2200
Maintenance of the OS2200
Maintenance of the OS2200
At the beginning and end of each heating season, take time to thoroughly check your furnace
and chimney system. Make sure there are no leaks where the metal panels are joined or at the caulk
lines, should you find a leak, hi-temp silicone will correct the problem. Check the doors for signs of
rust, should rust develop, lightly sand or steel wool the surface and follow-up with black high tempera-
ture paint to keep the doors looking new. Check the gaskets, if they are frayed and burnt, replace the
gasket. Check the firebricks for breakage or crumbling and replace as needed. Check the chimney pipe
for signs of creosote formation, if you find creosote, thoroughly clean the chimney system - replacing
the chimney cap securely so rain or snow does not run down the chimney into the firebox - if the cap is
removed for any length of time when the furnace is not in use, cover the pipe so no moisture gets into
the firebox. Check the chimney pipe for holes or loosened connections- replace and secure as neces-
sary. Check the grates for signs of wear and replace as needed. Check the heat duct and cold air return
to be sure they have not come loose or been damaged, if so tighten or replace as needed. Check the duct
work for any air leaks that will affect the furnace’s performance - airtight duct work increases effi-
ciency and furnace performance while delivering higher Btus. Check guy wires to be sure they are
secure and have not broken. Remove any accumulated ashes at the end of the season. By following
these procedures your furnace will provide many years of trouble-free service.
ALWAYS:
☺
☺
☺
☺
☺
Locate the OS2200 on a level, solid, non-combustible surface.
☺
☺
☺
☺
☺
Follow local codes concerning installation requirements.
☺
☺
☺
☺
☺
Connect power cord to a grounded 110 outlet with GFI.
☺
☺
☺
☺
☺
Connect cold air return to the house.
☺
☺
☺
☺
☺
Use Class “A” Insulated 6” SuperPro/SuperMax Chimney or equivilant.
☺
☺
☺
☺
☺
Follow guidelines within the manual regarding burn procedures.
☺
☺
☺
☺
☺
Operate furnace with fuel door and ash drawer closed.
☺
☺
☺
☺
☺
Inspect the furnace several times a year to insure furnace caulking is adequate.
☺
☺
☺
☺
☺
Inspect chimney pipe for creosote formation.
☺
☺
☺
☺
☺
Use dry, seasoned hardwood - maximum length, 34” - always keep your wood covered.
☺
☺
☺
☺
☺
Have access to a backup generator in case of power failure, minimum of 2000 watts.
☺
☺
☺
☺
☺
Use Guy Wire to secure chimney pipe
NEVER:
Never allow anyone to operate the furnace who is not familiar with the unit.
Operate furnace with spin draft wide open, unattended.
Operate with the fuel door and ash drawer open.
Use gasoline, oil or any other flammable liquid to start or maintain the fire.
Operate your furnace without a backup power supply (generator).
Fuel your furnace with wet unseasoned wood.
Use 90° angles when running duct work.
Operate the furnace without the chimney attached.
Alter the furnace in any way.
Burn garbage, plastic, wood containing glue/resins, paraffin or treated with chemical
preservatives.