13
calIBratIon
Manual Calibration
Manual calibration can be done setting the micro switches on PCB in the
proper combination in according with the pipe size (from d20-DN15 up to
d>200-DN>180) where sensor will be installed. Positions are reported in the
following table.
Lock position is a No Functioning Combination while the USB combination is
for accessing to the USB connection.
The setting has to be done before powering up the instrument.
F6.60 provides a frequency output (0Hz@0m/s - 800Hz@8m/s) by a
Open Collector (connectors 9-10) and an analog output (4mA@0m/s –
20mA@8m/s).
Both outputs are proportional to the flow velocity and so to the flow rate.
Moreover a Open Collector (connectors 7-8) is dedicated to specify the flow
direction.
In manual calibration the S.S.R. cannot be set and consequently used.
Switch 1
Switch 2
Switch 3
Switch 4
Diameter
Off
Off
Off
Off
Lock
Off
Off
Off
On
D20
Off
Off
On
Off
D25
Off
Off
On
On
D32
Off
On
Off
Off
D40
Off
On
Off
On
D50
Off
On
On
Off
D63
Off
On
On
On
D75
On
Off
Off
Off
D90
On
Off
Off
On
D110
On
Off
On
Off
D125
On
On
On
On
D140
On
On
Off
Off
160
On
On
Off
On
D200
On
On
On
Off
> D200
On
On
On
On
USB
Summary of Contents for FLS F6.60
Page 6: ...6 Fig 1 Fig 2 Fig 3 Fig 4 ...