PARAMETERS OF THE
HEATERS
KEY CODE
Electric heater
Water heater
SM
-
power control in standatd delivery)
DM
- manual control with electronic regulation
DA
- automatic/manual control with electronic regulation
LW
- LONWORKS (building management system)
S
- No heater
E
- Electric heater
V
- Standard water heater
W
- Multiple water heater
10, 15, 20
- Length of the air curtain 1; 1.5 and 2 meters
B, C
- Power range
Air curtain to be installed into ceiling -
FINESSE
12
/0
9
page 03
Inlet air tempe18°C
All figures measured at maximum speed.
Water flow
Pressure loss on
the water side
Pressure loss on
the water side
Water flow
(°C)
(I/s)
(°C)
(I/s)
VCS -F-B-10V
32,5
0,17
3,13
39,5
0,22
4,39
VCS -F-B-15V
34,2
0,28
3,54
71,4
0,35
4,93
VCS -F-B-20V
35,4
0,39
5,46
42,7
0,48
7,54
VCS -F-B-10W
41,8
0,24
1,71
50,4
0,30
2,37
VCS -F-B-15W
44,5
0,4
5,67
53,3
0,48
7,71
VCS -F-B-20W
44,6
0,53
9,42
53,3
0,65
12,83
VCS -F-C-10V
30,8
0,20
3,85
37,5
0,24
5,41
VCS -F-C-15V
33,3
0,31
4,06
40,4
0,37
5,65
VCS -F-C-20V
35,1
0,41
5,92
42,4
0,50
8,18
VCS -F-C-10W
40,2
0,27
2,11
48,5
0,33
2,94
VCS -F-C-15W
43,9
0,43
6,48
52,5
0,52
8,83
VCS -F-C-20W
44,6
0,56
10,18
53,2
0,68
13,86
Type
Temperature drop 80/60°C
Temperature drop 90/70°C
t
t
Electric heater
Water heater
OPERATION INSTRUCTIONS
[°C]
[kW]
[A]
11,9
9
13
11,9
13,5
19,5
11,9
18
26
9,5
9
13
10,2
13,5
19,5
10,8
18
26
Power
Maximum electric
heat output
supply
Type
t
VCS-F-B-10E
VCS-F-B-15E
VCS-F-B-20E
VCS-F-C-10E
VCS-F-C-15E
VCS-F-C-20E
The right for changes reserved
©2VV, spol. s r.o.
VCS - F - B - 10 S - SM
General packing sheet of the air curtain
Air curtain type sheet