Finesse VCS -F-B-10E Operation Instructions Manual Download Page 13

12

/0

9

page 13

FAN OVERHEATING

CLOGGED FILTER SIGNAL

When one electric motor is overheated and thermo-contact stops it, other motors remain in operation. Thermo-contact is 
automatic one, so when the motor cools down, the thermo-contact returns to its original position and the fan starts again. 
This situation is not indicated on any type of control systems. This state can be recognised by reduced air curtain output and 
in case the  air curtain heats, the air flow temperature in the place of fan failure rises up. This failure cannot be considered to 
be a normal one. It is necessary to check the air curtain and to find out the reason of fan failure. The reasons are usually as 
follows: 
- Clogged filter and thus lower air flow  it is necessary to clean the filter (see “Air curtain maintenance”)
- Insufficient space in front of the inlet grille (see “ Principles of the air curtain location”) it is necessary to ensure proper 

installation.

- Defective fan  this is the less frequent cause. It is necessary to call the authorised service centre and to change the fan.

When a filter is clogged in any air curtain, signal FILTER appears (on DA type control systems only). In case the signal is on, 
it means that the filter is clogged so it prevents the air curtain to operate properly and so it is necessary to clean or change the 
filter. As to other control systems than DA, you recognise the clogged filter by its higher noise level and by reduction of its air 
output (see “Air curtain maintenance”).

E

FILTER

USE AND SETTING OF TIME SWITCH

OPERATION INSTRUCTIONS

After electric connection of time switch the shown keys have to be pressed simultaneously.
Reset (Total clearance of the time switch).

Just after the reset you have to decide how do you want to use the switch:
1. Switch OFF/ON in pre-set time intervals the same for all weekdays (use „Easy setting“)
2. Switch OFF/ON in pre-set time intervals depending on selected day(s) in a week 

(use “Setting for individual selected day”).

HOW TO START ?

Electrical connection of the time switch shall be made by an authorized person according to the national regulations 
and directives. Manipulations and modifications on the switch will result in loss of warranty.

Note:

 In spite of an internal safety control, unusual strong noise fields could cause a disturbance of the microprocessor-

controlled time switch.

Interference can be avoided if the following details are considered during installation :
- the device should not be installed close to inductive consumers
- there has to be layed a separate line for the mains supply (if necessary mains suppresion filter)
- inductive consumers should have to be interference suppressed (varistor, RC-section)

After having cleared the interference a reset of the time switch is necessary.

Current time/
switch ON/OFF time

Weekday(7 = Sunday)

Hours setting

Weekday setting

Time setting

Program entry / recall

Response time number for the weekday
indicated (1 ON, 1 OFF, 2 ON, 2 OFF, 
3 ON, 3 OFF) H = Holiday program

The point indicates permanent
control ON or OFF

Indication of actual switch position 
ON = Switch ON, OFF = Switch OFF

Minutes setting

Switching between automatic or 
manual control

INSTALLATION

d

h

m

h

For return from program mode you can choose these two ways :
1. press button
2. if there is no interruption (no action) on time switch for 40 seconds it returns automatically

For possibility of choosing between two basic settings (see “How to start”) you have to first press Reset.

CONTROL PRINCIPLE

After Reset is done you can set the current time. You need to keep the button       + press 

>>h<<

 (for setting hours) and 

press 

>>m<<

 (for setting minutes). Arrow that displayes actual selection of the day will appear above symbol 1-7.

Attention:

 If you want to use “Easy setting” (see point 1 in chapter “How to start”) do not 

press button 

>>d<< 

during setting the time !

This easy program offer 6 different pre-set time intervals Switch ON/Switch OFF 
(6 ON/OFF) without selection of the weekday. These pre-set time intervals will repeat every day the same.

EASY SETTING (1-7)

DS 1800

1 2 3 4 5 6 7 1 7

DS 1800

TIME GUARD

1 2 3 4 5 6 7 1 7

d

h

m

h

H

OFF

The right for changes reserved 

©2VV, spol. s r.o.

Summary of Contents for VCS -F-B-10E

Page 1: ...mm safe distance of combustible materials in all other directions is 100 mm Never start damaged air curtain Assembly and connection of the air curtain must be executed by an authorised person and acco...

Page 2: ...B 15S 3360 58 9 230 50 3 34 VCS F B 20S 4480 60 5 230 50 4 48 VCS F B 10E 2220 9 0 54 8 400 50 15 25 VCS F B 15E 3330 13 5 58 9 400 50 22 5 37 VCS F B 20E 4440 18 0 60 5 400 50 30 51 VCS F B 10V 2180...

Page 3: ...3 54 71 4 0 35 4 93 VCS F B 20V 35 4 0 39 5 46 42 7 0 48 7 54 VCS F B 10W 41 8 0 24 1 71 50 4 0 30 2 37 VCS F B 15W 44 5 0 4 5 67 53 3 0 48 7 71 VCS F B 20W 44 6 0 53 9 42 53 3 0 65 12 83 VCS F C 10V...

Page 4: ...reundermentioneddimensions 4 Drill four holes into the ceiling construction according to the dimensions scheme see Dimensions for hanging of the air curtainto 4 anchoringpoints Screw the air curtain d...

Page 5: ...ssible to follow the current room temperature by the water mixer controller and to set the required temperature Water mixer must be installed according to the delivered technical documentation 1 Conne...

Page 6: ...nstallation must be done by a qualified electrician only Applicable national standards and regulations must be kept Air curtain must be connected by NTSC system i e with zeroing conductor always conne...

Page 7: ...om thermostat is used for switching the electric heater in the air curtain ON and OFF according to the pre set temperature version DA For version DM SM it is used for air curtain control ON OFF Locati...

Page 8: ...temperature sensors C OPERATION MANUAL C Time switch is used to switch the air curtain ON OFF according to the pre set time schedule The time schedule can be set for the all office days in the week Sw...

Page 9: ...E DM There are the following push buttons on the V DM controller for water heating The air curtain is switched ON and OFF by push button A The fan speed is set by three buttons B C D Switching of the...

Page 10: ...ol system controls the fans speed and the electric heater output according to the outdoor temperature see followingTable Reading accuracy 3 C Function of the air curtain with connected outdoor tempera...

Page 11: ...outdoor temperature When the doors are closed again the automatic system reduces the speed of fans to the original speed with about 30 seconds delay When the door is opened within this time period the...

Page 12: ...F THE AIR CURTAINS BUILDING MANAGEMENT SYSTEM BSM Chaining of the air curtains is possible just in case of DM and DAcontrol systems It is possible to interconnect up to 6 air curtains including the co...

Page 13: ...day HOW TO START Electrical connection of the time switch shall be made by an authorized person according to the national regulations and directives Manipulations and modifications on the switch will...

Page 14: ...vals different for Monday or Saturday interval is the same For example if you set the first time interval on 15 30 ON and 18 00 OFF for selected weekdays it is already reserved and it can not be used...

Page 15: ...rks are to be done Tilt the grille see Tilting of the grille by using Philips screwdriver remove the steel sheet holder with electronic system or interconnecting terminal board and move it out a piece...

Page 16: ...mode Exact description of single states can be found in chapter Air curtain operation The other possible cause of malfunction of the electric heater is that the operation thermostat with automatic re...

Page 17: ...DOOR CONTACT L1 L1 3 400V L3 N N L3 L2 L2 0 V INPUT PE PE max 8 mA 20 21 23 22 EXTERNAL CONTACT OFF OFF ON ON max 8 mA 0 V INPUT 0 V INPUT TIMER AIR CURTAIN 27 26 ROOM THERMOSTAT TEMPERATURE ON UNDER...

Page 18: ...Ausblas ffnungen nicht verdecken F r den sicheren Abstand der entflammbaren Stoffe von den elektrischen Produkten gelten landesspezifische technische Normen F r einen sicheren Abstand der Oberfl chen...

Page 19: ...CS F C 20V 4720 VCS F C 10V 2610 VCS F C 15V 3640 VCS F C 20V 4600 9 0 13 5 18 0 18 5 15 1 29 4 24 1 40 7 33 4 25 2 20 6 40 9 33 9 54 5 45 2 9 0 13 5 18 0 20 7 16 9 31 7 26 0 42 6 35 0 28 4 23 2 44 1...

Page 20: ...3 54 71 4 VCS F B 20V 35 4 0 39 5 46 42 7 VCS F B 10W 41 8 0 24 1 71 50 4 VCS F B 15W 44 5 0 4 5 67 53 3 VCS F B 20W 44 6 0 53 9 42 53 3 VCS F C 10V 30 8 0 20 3 85 37 5 VCS F C 15V 33 3 0 31 4 06 40...

Page 21: ...eiter Anschluss des Wasserw rmetauschers In der Untersicht ist eine ffnung mit nachstehend genanntenAbmessungen auszuschneiden oder herzustellen 4 Danach sind in der Deckenkonstruktion zum Aufh ngen d...

Page 22: ...rinstallation durchgef hrt und dabei die g ltigen Normen und landesinternen Vorschriften beachtet werden der Heizregister ist f r Wasser mit einem Druck von maximal 1 6 Mpa und einerTemperatur von max...

Page 23: ...on einem qualifizierten Elektrofachmann ausgef hrt werden Dabei sind die jeweiligen g ltigen Landesvorschriften und richtlinien zu beachten Das Luftschleierger t ist nach dem NTSC System anzuschlie en...

Page 24: ...r ge ffnet l uft der Luftschleier an Beim Schlie en der T r ist die Funktion des Luftschleierger tes vom jeweiligen Steuerungstyp abh ngig Der T rkontakt passt zu allen Steuerungstypen Eine genaue Fun...

Page 25: ...standardm ige Bestandteil der Lieferung ist Eine ausf hrliche Funktionsbeschreibung finden Sie im Abschnitt Bedienung DA Steuerung Au entemperaturf hler potentialfreier Kontakt mit 12V Maximalspannun...

Page 26: ...1 2 Nur eine der angegebenen Nummern C BEDIENUNGSANLEITUNG 12 09 seite 09 SM STEUERUNG IN FRAGE KOMMENDE STEUERUNGSARTEN ELEKTRISCHE HEIZUNG Typ E SM nderungsrechte vorbehalten 2VV spol s r o 1 OFF 2...

Page 27: ...des elektrischen Heizregisters L uft der Luftschleier einschl des elektrischen Heizregisters und gibt die Bedienperson mit der TasteAam Steuerger t den Befehl AUS so wird lediglich der elektrische Hei...

Page 28: ...izregisters in Abh ngigkeit von derAu entemperatur sieheTabelle unten Messgenauigkeit 3 C Funktion des Luftschleierger tes mit angeschlossenemAu entemperaturf hler undT rschalter Beim Einsatz des T rs...

Page 29: ...e ffnet oder geschlossen ist siehe Tabelle unten Bei geschlossener T r stellt die Elektronik die niedrigste Luftleistung ein Wird die T r ge ffnet erh ht sie sofort die Ventilatordrehzahl inAbh ngigke...

Page 30: ...ossen verkettet werden Bei Luftschleier Verkettungen ist die Funktion des Steuerger tes und des externen Schaltgliedes T rkontakt Thermostat Zeitschalter absolut identisch mit der Bedienung eines einz...

Page 31: ...kennen siehe Wartung des Luftschleierger tes E FILTER Nach demAnschluss der Schaltuhr in den Elektronetz die abgebildeten Tasten gleichzeitig dr cken Reset des Ger ts Nach dem Reset entscheiden in wel...

Page 32: ...che Einstellung durchgef hrt wird Alle Intervalle k nnen durch p Taste f r Kontrolle wieder gelistet werden Hinweis F r alle Tage der Woche stehen 4 ON OFF Intervalle zur Verf gung Ein Intervall kann...

Page 33: ...rafo f r die Wartung zug nglich machen verfahren Sie wie folgt klappen Sie das Gitter herunter sieheAbschnitt ffnen des Sichtgitters schrauben Sie den Blechhalter mit der Elektronik oder mit den Ansch...

Page 34: ...es Luftschleierger tes Steuerungsversion Montageort Installationsbedingungen auch elektrische Laufzeit usw Versuchen Sie niemals die innere Schaltung des Luftschleiers anzupassen oder jedwede Luftschl...

Page 35: ...tsprechend der Funkentst rungsnorm Bei extrem weiten Entfernungen k nnen Kabel mit st rkerer Abschirmung bestellt werden Wie verh lt sich das Luftschleierger t wenn einer der F hler falsch angeschloss...

Page 36: ...A Luftschleier offene T r geschlossene T r OFF ON A B C D VCS x 10S V W 3 x 0 5 3 x 0 5 3 x 0 5 3 x 0 75 VCS x 15S V W 3 x 0 5 3 x 0 5 3 x 0 5 3 x 1 5 VCS x 20S V W 3 x 0 5 3 x 0 5 3 x 0 75 3 x 2 5 VC...

Page 37: ...FINESSE BEDINGUNGEN F R DIE SICHERHEIT UND DAS FUNKTIONIEREN DES LUFTSCHLEIERS 100 500 500 100 Finesse 0 C 40 C 80 IP20 1 400 EN 292 2 A1 2000 EN 60335 1 1997 3 0 C 40 C 12 09 01 RU OOO 2VV...

Page 38: ...57 4 58 6 55 6 59 5 60 9 55 6 59 5 60 9 54 7 57 9 58 9 54 7 57 9 58 9 230 50 230 50 230 50 400 50 400 50 400 50 230 50 230 50 230 50 230 50 230 50 230 50 230 50 230 50 230 50 400 50 400 50 400 50 230...

Page 39: ...48 5 VCS F C 15W 43 9 52 5 VCS F C 20W 44 6 0 17 0 28 0 39 0 24 0 4 0 53 0 20 0 31 0 41 0 27 0 43 0 56 3 13 3 54 5 46 1 71 5 67 9 42 3 85 4 06 5 92 2 11 6 48 10 18 53 2 0 22 0 35 0 48 0 30 0 48 0 65...

Page 40: ...1990 370 4 3 1 410 304 361 B A 250 300 4 x M 8 1 2 12 09 04 A B 1100 1073 410 300 1500 1473 410 300 2000 1973 410 300 1100 1073 410 300 1500 1473 410 300 2000 1973 410 300 VCS F B 10 VCS F B 15 VCS F...

Page 41: ...SMU OSMU DK P10L1000 DA ZV 3 TER P 1 2 3 3 3 4 4 5 5 6 6 2 2 1 1 1 6 100 C P12L1000 SMU 1 3 12 09 05 OOO 2VV...

Page 42: ...SM DM DA 1 2 KABEL05 CONTROL 3 DA DM 50 DA DM 150 SM DM DA NTSC 2 12 09 06 90 C 2 3 3 1 1 1 2 1 2 3 CONTROL...

Page 43: ...DM DA 12 09 07 SM CONTROL 10 OOO 2VV 1 2 3 4 1 2 3 4 5 6 7 8 9 CLICK...

Page 44: ...50 12 0 35 5 DA 17 18 19 DM DA SM 1 2 22 23 17 18 19 PE C TER P DA DM SM ON OFF 1200 12 0 5 50 1200 DM DA SM 1 3 26 27 12 09 08 SM DM DA DS SM DK DM DA 12 0 5 50 230 50 1 5 50 1 2 20 21 1 1 2 DK DK 1...

Page 45: ...12 09 09 SM DM DA 6 C ALARM FILTER 1 2 C SM E SM OOO 2VV 1 OFF 2 3 3 2 2 1 OFF...

Page 46: ...12 09 10 E DM B C D 3 E F B F 30 60 30 30 30 E DM V DM B C D 3 30 DM V DM 2 1 3 2 1 3 1 2 DM V SM OFF 1 2 3 OFF A E F B C D A B C D...

Page 47: ...E F G H D E F G H E DA 3 C 30 3 C 3 C 3 1 2 2 1 5 C 5 10 C 10 15 C 3 2 2 2 2 1 T r auf T r zu 2 2 1 1 1 1 15 20 C 1 0 1 1 20 C 2 0 0 0 5 C 3 2 20 C 2 0 5 10 C 2 2 10 15 C 2 1 15 20 C 1 0 DA E DA AUT...

Page 48: ...C 3 1 2 5 C 5 10 C 10 15 C 15 20 C 3 2 2 1 2 1 1 1 20 2 0 C 5 C 5 10 C 10 15 C 15 20 C 20 C 3 2 2 1 2 C V DA C C C 3 C 3 1 2 1 3 2 2 2 0 0 0 0 2 2 1 1 5 10 C 5 C 2 1 1 0 2 1 1 0 0 0 0 0 1 1 1 1 10 15...

Page 49: ...orks LonTalk LonWorks MASTER 1 2 3 6 DM DA DM MASTER SLAVE MASTER SLAVE MASTER SLAVE MASTER SLAVE 3 2 3 2 0 0 2 1 5 10 C 10 15 C 5 C 2 1 2 1 0 0 1 1 15 20 C 20 C 2 2 0 0 OFF OFF SM 0 0 0 DM 30 30 0 0...

Page 50: ...12 09 14 RESET RESET FILTER DA FILTER DA E FILTER RESET 1 2 Yx a o c y a p RC 7 1 ON 1OFF 2ON 2OFF 3ON 3OFF Holiday program ON OFF ON OFF d h m h...

Page 51: ...h 1 2 40 RESET RESET h m 1 7 d 6 6 ON OFF 1 7 1 2 3 4 5 6 7 1 7 RESET h m d 1 4 4 ON OFF p ON OFF ON OFF DS 18 1 2 3 4 5 6 7 1 7 1 OFF ON h m d d p 4 p d h m DS 18 1 2 3 4 5 6 7 1 7 1 OFF ON ON OFF m...

Page 52: ...DA FILTER FILTER FINESSE 24 12 09 16 230V 10 50Hz 7VA 10 A 250V cos n 1 2 A 250V cos n 0 6 quartz 4 6 4 ON OFF 6 ON OFF 1 2 1 20 24 10 40 IP 20 En60529 73 23 EEC 89 336 EEC EMC...

Page 53: ...FINESSE 99 1 2 3 4 CONTROL DA DM DA DM SM 5 6 7 8 DA DA 12 09 17 SM CONTROL DM DA CLICK OOO 2VV...

Page 54: ...SM DM DA CONTROL SLAVE DM DA 50 50 SM DA 12 09 18...

Page 55: ...PE DK2 DK1 230V max 10 A OFF ON A B C D VCS x 10S V W 3 x 0 5 3 x 0 5 3 x 0 5 3 x 0 75 VCS x 15S V W 3 x 0 5 3 x 0 5 3 x 0 5 3 x 1 5 VCS x 20S V W 3 x 0 5 3 x 0 5 3 x 0 75 3 x 2 5 VCS x 10E 5 x 2 5 5...

Reviews: