Finesse VCS -F-B-10E Operation Instructions Manual Download Page 1

FINESSE Air Curtain

CONDITIONS FOR 
SAFETY AND PROPER 
FUNCTION OF THE 
AIR CURTAIN

ENVIRONMENT 
PROTECTION

ASSEMBLY INSTRUCTION

INSPECTION OF THE 
DELIVERY

This  instruction  contains  important  hints  and  safety  instruction.  To  ensure  proper  function  and  own  safety  read 
thoroughly this manual before the use of the air curtain and follow the instruction. We reserve the right of changes in 
accordance  with  the  technical  development  in  the  production.The  priority  of  electric  wiring  schemes  placed  on  the 
product is higher than these ones which are included in this user´s manual.

 

Any changes or interventions to the inner 

connexion are prohibited, and lead to cancellation of the warranty. We recommend to use the accessories supplied by 
us. In the case other than original accessories or regulations are used the product may be damaged. The manufacturer is 
not responsible for damage occurred as a result of using non-original accessories (regulations),or improper use of the 
accessories (regulations).

 

Frequency converter shall not be used to adjust the fans' rotation.

-

-

Our company is continuously improving the new technologies and technical solutions with the aim to reduce energy 

consumption and to maintain natural sources and to contribute thus effectively to slow down the environment harm.

- Before you will put the air curtain to scrap, make it unusable. Even the old air curtain contain reusable raw materials. It is 

recommended to scrap the air curtain by a specialised company which is capable to recycle the materials.

- Air  curtain  is  protected  by  packing  against  damage  during  transport. All  used  packing  materials  are  ecological  and 

recyclable.  Will  you  contribute  actively  to  the  environment  protection  and  dispose  and  recycle  properly  all  packing 
material.

- Will you follow this instruction manual for maximum gains from function, energy savings and long service life of the air 

curtain.

Read this instruction manual before the installation and using of the air curtain and keep the instruction thereof. You will 

find there the important information not only for installation and use, but also for safety and air curtain maintenance.

- Close to the air curtain and in distance up to 100 mm in all directions around just incombustible materials (do not burn, do 

not glow, do not carbonate) or hard to burn materials (do not burn, mostly glow and carbonate e.g. gypsboard) can be 
used. However, these materials may cover neither inlet nor outlet openings. National technical standards are applicable 
for safe distance of combustible materials from electric appliances. 

- As to the safety distance of the electric-heated air curtain  from surfaces of structure constructions, floor covers and items 

made from combustible materials, the following applies: 

-

safe distance of combustible materials in the direction of the main air stream (behind the outlet slot) is 500 mm

-

safe distance of combustible materials above the air curtain is 500 mm

-

safe distance of combustible materials in all other directions is 100 mm

- Never start damaged air curtain.
- Assembly and connection of the  air curtain must be executed by an authorised person and according to the installation 

hints and applicable regulations. When you will not comply with the hints and regulations, you risk the loose of warranty. 

- We do recommend to keep this instruction manual for future reference or for possible use by another user. 
- FINESSE air curtains have been designed for operation indoors in dry environment with ambient temperature between 0° 

and 40°C for transportation of air free of fat, chemical vapours and other impurities. 

- Relative humidity of the air should be up to 80%.
- Electric protection degree of the air curtain equipped with inlet cover is IP 20. 
- Operator of this air curtain should be acquainted with this manual. 
- When  the  air  curtain  has  been  transported  under  other  temperatures  that  the  operation  one  (lower  than  0°C),  it  is 

necessary  to  let  it  under  operation  environment  for  at  least  1  hour  switched  off  to  balance  the  inner  and  outer 
temperatures (recommendation).

- As  to  the  appliances  powered  by  400  V AC  it  is  necessary  to  place  close  to  that  an  lockable  switch  with  minimum 

contactors distance 3mm when it is not connected by a power cord, pursuant to requirements of EN 292-2+A1:2000, EN 
60335-1:1997.

- There must be the main switch connected to the main power supply of the air curtain for disconnection of all poles.

To minimize the possibility of damage in transport the air curtain is packed in a wooden framed structure. The air curtain 
must be carefully handled to avoid damage if dropped. On delivery check that no damage has occurred in transport. The air 
curtain must be stored indoors in dry environment with ambient temperature between 0° and +40°C.
- Check immediately after delivery if there is not any damage to the air curtain during the transport. 
- Check the data on the machine index plate with those on the purchase order. When of any discrepancy, or of any damage 

on the packing, will you not unpack the air curtain and report the problem to the supplier, when of damage of the packing 
call the forwarder, too. When the claim is not applied immediately, none claim related to that can be laid in the future.

- Check the index plate, when of the discrepancy of the parameters, follow the instruction in the above sentence. 

FINESSE air curtains are manufactured in accordance with the  internationally valid standards and regulations and they 
confirm with Electric, Mechanic and Noise Safety.

EN 60335-2-30 ed. 2:2004+A1:05+A2:08 / idt EN 60335-2-30:2003+A1:04+A2:07
EN 60335-1 ed. 2:2003+A11:04+A12:06+A2:07+Z1:07
      / idt EN 60335-1:2002+A11:04+A1:04+A12:06+A2:06+A1/Cor:07
EN 60204-1 ed. 2:2007 / idt EN 60204-1:2006
EN 55014-1 ed. 3:2007 / idt EN 55014-1:2006
EN 61000-6-3 ed. 2:2007 / idt EN 61000-6-3:2007
EN 61000-3-2 ed. 3:2006 / idt EN 61000-3-2:2006
EN 61000-3-3:1997+Z1:02+A2:06+Z2:07 / idt EN 61000-3-3:1995+A1:01+A2:05+IS1:05
EN 55014-2:1998+A1:02 / idt EN 55014-2:1997+A1:01

CERTIFICATION

12

/0

9

page 01

A 80

R

EN

OPERATION INSTRUCTIONS

The right for changes reserved 

©2VV, spol. s r.o.

Summary of Contents for VCS -F-B-10E

Page 1: ...mm safe distance of combustible materials in all other directions is 100 mm Never start damaged air curtain Assembly and connection of the air curtain must be executed by an authorised person and acco...

Page 2: ...B 15S 3360 58 9 230 50 3 34 VCS F B 20S 4480 60 5 230 50 4 48 VCS F B 10E 2220 9 0 54 8 400 50 15 25 VCS F B 15E 3330 13 5 58 9 400 50 22 5 37 VCS F B 20E 4440 18 0 60 5 400 50 30 51 VCS F B 10V 2180...

Page 3: ...3 54 71 4 0 35 4 93 VCS F B 20V 35 4 0 39 5 46 42 7 0 48 7 54 VCS F B 10W 41 8 0 24 1 71 50 4 0 30 2 37 VCS F B 15W 44 5 0 4 5 67 53 3 0 48 7 71 VCS F B 20W 44 6 0 53 9 42 53 3 0 65 12 83 VCS F C 10V...

Page 4: ...reundermentioneddimensions 4 Drill four holes into the ceiling construction according to the dimensions scheme see Dimensions for hanging of the air curtainto 4 anchoringpoints Screw the air curtain d...

Page 5: ...ssible to follow the current room temperature by the water mixer controller and to set the required temperature Water mixer must be installed according to the delivered technical documentation 1 Conne...

Page 6: ...nstallation must be done by a qualified electrician only Applicable national standards and regulations must be kept Air curtain must be connected by NTSC system i e with zeroing conductor always conne...

Page 7: ...om thermostat is used for switching the electric heater in the air curtain ON and OFF according to the pre set temperature version DA For version DM SM it is used for air curtain control ON OFF Locati...

Page 8: ...temperature sensors C OPERATION MANUAL C Time switch is used to switch the air curtain ON OFF according to the pre set time schedule The time schedule can be set for the all office days in the week Sw...

Page 9: ...E DM There are the following push buttons on the V DM controller for water heating The air curtain is switched ON and OFF by push button A The fan speed is set by three buttons B C D Switching of the...

Page 10: ...ol system controls the fans speed and the electric heater output according to the outdoor temperature see followingTable Reading accuracy 3 C Function of the air curtain with connected outdoor tempera...

Page 11: ...outdoor temperature When the doors are closed again the automatic system reduces the speed of fans to the original speed with about 30 seconds delay When the door is opened within this time period the...

Page 12: ...F THE AIR CURTAINS BUILDING MANAGEMENT SYSTEM BSM Chaining of the air curtains is possible just in case of DM and DAcontrol systems It is possible to interconnect up to 6 air curtains including the co...

Page 13: ...day HOW TO START Electrical connection of the time switch shall be made by an authorized person according to the national regulations and directives Manipulations and modifications on the switch will...

Page 14: ...vals different for Monday or Saturday interval is the same For example if you set the first time interval on 15 30 ON and 18 00 OFF for selected weekdays it is already reserved and it can not be used...

Page 15: ...rks are to be done Tilt the grille see Tilting of the grille by using Philips screwdriver remove the steel sheet holder with electronic system or interconnecting terminal board and move it out a piece...

Page 16: ...mode Exact description of single states can be found in chapter Air curtain operation The other possible cause of malfunction of the electric heater is that the operation thermostat with automatic re...

Page 17: ...DOOR CONTACT L1 L1 3 400V L3 N N L3 L2 L2 0 V INPUT PE PE max 8 mA 20 21 23 22 EXTERNAL CONTACT OFF OFF ON ON max 8 mA 0 V INPUT 0 V INPUT TIMER AIR CURTAIN 27 26 ROOM THERMOSTAT TEMPERATURE ON UNDER...

Page 18: ...Ausblas ffnungen nicht verdecken F r den sicheren Abstand der entflammbaren Stoffe von den elektrischen Produkten gelten landesspezifische technische Normen F r einen sicheren Abstand der Oberfl chen...

Page 19: ...CS F C 20V 4720 VCS F C 10V 2610 VCS F C 15V 3640 VCS F C 20V 4600 9 0 13 5 18 0 18 5 15 1 29 4 24 1 40 7 33 4 25 2 20 6 40 9 33 9 54 5 45 2 9 0 13 5 18 0 20 7 16 9 31 7 26 0 42 6 35 0 28 4 23 2 44 1...

Page 20: ...3 54 71 4 VCS F B 20V 35 4 0 39 5 46 42 7 VCS F B 10W 41 8 0 24 1 71 50 4 VCS F B 15W 44 5 0 4 5 67 53 3 VCS F B 20W 44 6 0 53 9 42 53 3 VCS F C 10V 30 8 0 20 3 85 37 5 VCS F C 15V 33 3 0 31 4 06 40...

Page 21: ...eiter Anschluss des Wasserw rmetauschers In der Untersicht ist eine ffnung mit nachstehend genanntenAbmessungen auszuschneiden oder herzustellen 4 Danach sind in der Deckenkonstruktion zum Aufh ngen d...

Page 22: ...rinstallation durchgef hrt und dabei die g ltigen Normen und landesinternen Vorschriften beachtet werden der Heizregister ist f r Wasser mit einem Druck von maximal 1 6 Mpa und einerTemperatur von max...

Page 23: ...on einem qualifizierten Elektrofachmann ausgef hrt werden Dabei sind die jeweiligen g ltigen Landesvorschriften und richtlinien zu beachten Das Luftschleierger t ist nach dem NTSC System anzuschlie en...

Page 24: ...r ge ffnet l uft der Luftschleier an Beim Schlie en der T r ist die Funktion des Luftschleierger tes vom jeweiligen Steuerungstyp abh ngig Der T rkontakt passt zu allen Steuerungstypen Eine genaue Fun...

Page 25: ...standardm ige Bestandteil der Lieferung ist Eine ausf hrliche Funktionsbeschreibung finden Sie im Abschnitt Bedienung DA Steuerung Au entemperaturf hler potentialfreier Kontakt mit 12V Maximalspannun...

Page 26: ...1 2 Nur eine der angegebenen Nummern C BEDIENUNGSANLEITUNG 12 09 seite 09 SM STEUERUNG IN FRAGE KOMMENDE STEUERUNGSARTEN ELEKTRISCHE HEIZUNG Typ E SM nderungsrechte vorbehalten 2VV spol s r o 1 OFF 2...

Page 27: ...des elektrischen Heizregisters L uft der Luftschleier einschl des elektrischen Heizregisters und gibt die Bedienperson mit der TasteAam Steuerger t den Befehl AUS so wird lediglich der elektrische Hei...

Page 28: ...izregisters in Abh ngigkeit von derAu entemperatur sieheTabelle unten Messgenauigkeit 3 C Funktion des Luftschleierger tes mit angeschlossenemAu entemperaturf hler undT rschalter Beim Einsatz des T rs...

Page 29: ...e ffnet oder geschlossen ist siehe Tabelle unten Bei geschlossener T r stellt die Elektronik die niedrigste Luftleistung ein Wird die T r ge ffnet erh ht sie sofort die Ventilatordrehzahl inAbh ngigke...

Page 30: ...ossen verkettet werden Bei Luftschleier Verkettungen ist die Funktion des Steuerger tes und des externen Schaltgliedes T rkontakt Thermostat Zeitschalter absolut identisch mit der Bedienung eines einz...

Page 31: ...kennen siehe Wartung des Luftschleierger tes E FILTER Nach demAnschluss der Schaltuhr in den Elektronetz die abgebildeten Tasten gleichzeitig dr cken Reset des Ger ts Nach dem Reset entscheiden in wel...

Page 32: ...che Einstellung durchgef hrt wird Alle Intervalle k nnen durch p Taste f r Kontrolle wieder gelistet werden Hinweis F r alle Tage der Woche stehen 4 ON OFF Intervalle zur Verf gung Ein Intervall kann...

Page 33: ...rafo f r die Wartung zug nglich machen verfahren Sie wie folgt klappen Sie das Gitter herunter sieheAbschnitt ffnen des Sichtgitters schrauben Sie den Blechhalter mit der Elektronik oder mit den Ansch...

Page 34: ...es Luftschleierger tes Steuerungsversion Montageort Installationsbedingungen auch elektrische Laufzeit usw Versuchen Sie niemals die innere Schaltung des Luftschleiers anzupassen oder jedwede Luftschl...

Page 35: ...tsprechend der Funkentst rungsnorm Bei extrem weiten Entfernungen k nnen Kabel mit st rkerer Abschirmung bestellt werden Wie verh lt sich das Luftschleierger t wenn einer der F hler falsch angeschloss...

Page 36: ...A Luftschleier offene T r geschlossene T r OFF ON A B C D VCS x 10S V W 3 x 0 5 3 x 0 5 3 x 0 5 3 x 0 75 VCS x 15S V W 3 x 0 5 3 x 0 5 3 x 0 5 3 x 1 5 VCS x 20S V W 3 x 0 5 3 x 0 5 3 x 0 75 3 x 2 5 VC...

Page 37: ...FINESSE BEDINGUNGEN F R DIE SICHERHEIT UND DAS FUNKTIONIEREN DES LUFTSCHLEIERS 100 500 500 100 Finesse 0 C 40 C 80 IP20 1 400 EN 292 2 A1 2000 EN 60335 1 1997 3 0 C 40 C 12 09 01 RU OOO 2VV...

Page 38: ...57 4 58 6 55 6 59 5 60 9 55 6 59 5 60 9 54 7 57 9 58 9 54 7 57 9 58 9 230 50 230 50 230 50 400 50 400 50 400 50 230 50 230 50 230 50 230 50 230 50 230 50 230 50 230 50 230 50 400 50 400 50 400 50 230...

Page 39: ...48 5 VCS F C 15W 43 9 52 5 VCS F C 20W 44 6 0 17 0 28 0 39 0 24 0 4 0 53 0 20 0 31 0 41 0 27 0 43 0 56 3 13 3 54 5 46 1 71 5 67 9 42 3 85 4 06 5 92 2 11 6 48 10 18 53 2 0 22 0 35 0 48 0 30 0 48 0 65...

Page 40: ...1990 370 4 3 1 410 304 361 B A 250 300 4 x M 8 1 2 12 09 04 A B 1100 1073 410 300 1500 1473 410 300 2000 1973 410 300 1100 1073 410 300 1500 1473 410 300 2000 1973 410 300 VCS F B 10 VCS F B 15 VCS F...

Page 41: ...SMU OSMU DK P10L1000 DA ZV 3 TER P 1 2 3 3 3 4 4 5 5 6 6 2 2 1 1 1 6 100 C P12L1000 SMU 1 3 12 09 05 OOO 2VV...

Page 42: ...SM DM DA 1 2 KABEL05 CONTROL 3 DA DM 50 DA DM 150 SM DM DA NTSC 2 12 09 06 90 C 2 3 3 1 1 1 2 1 2 3 CONTROL...

Page 43: ...DM DA 12 09 07 SM CONTROL 10 OOO 2VV 1 2 3 4 1 2 3 4 5 6 7 8 9 CLICK...

Page 44: ...50 12 0 35 5 DA 17 18 19 DM DA SM 1 2 22 23 17 18 19 PE C TER P DA DM SM ON OFF 1200 12 0 5 50 1200 DM DA SM 1 3 26 27 12 09 08 SM DM DA DS SM DK DM DA 12 0 5 50 230 50 1 5 50 1 2 20 21 1 1 2 DK DK 1...

Page 45: ...12 09 09 SM DM DA 6 C ALARM FILTER 1 2 C SM E SM OOO 2VV 1 OFF 2 3 3 2 2 1 OFF...

Page 46: ...12 09 10 E DM B C D 3 E F B F 30 60 30 30 30 E DM V DM B C D 3 30 DM V DM 2 1 3 2 1 3 1 2 DM V SM OFF 1 2 3 OFF A E F B C D A B C D...

Page 47: ...E F G H D E F G H E DA 3 C 30 3 C 3 C 3 1 2 2 1 5 C 5 10 C 10 15 C 3 2 2 2 2 1 T r auf T r zu 2 2 1 1 1 1 15 20 C 1 0 1 1 20 C 2 0 0 0 5 C 3 2 20 C 2 0 5 10 C 2 2 10 15 C 2 1 15 20 C 1 0 DA E DA AUT...

Page 48: ...C 3 1 2 5 C 5 10 C 10 15 C 15 20 C 3 2 2 1 2 1 1 1 20 2 0 C 5 C 5 10 C 10 15 C 15 20 C 20 C 3 2 2 1 2 C V DA C C C 3 C 3 1 2 1 3 2 2 2 0 0 0 0 2 2 1 1 5 10 C 5 C 2 1 1 0 2 1 1 0 0 0 0 0 1 1 1 1 10 15...

Page 49: ...orks LonTalk LonWorks MASTER 1 2 3 6 DM DA DM MASTER SLAVE MASTER SLAVE MASTER SLAVE MASTER SLAVE 3 2 3 2 0 0 2 1 5 10 C 10 15 C 5 C 2 1 2 1 0 0 1 1 15 20 C 20 C 2 2 0 0 OFF OFF SM 0 0 0 DM 30 30 0 0...

Page 50: ...12 09 14 RESET RESET FILTER DA FILTER DA E FILTER RESET 1 2 Yx a o c y a p RC 7 1 ON 1OFF 2ON 2OFF 3ON 3OFF Holiday program ON OFF ON OFF d h m h...

Page 51: ...h 1 2 40 RESET RESET h m 1 7 d 6 6 ON OFF 1 7 1 2 3 4 5 6 7 1 7 RESET h m d 1 4 4 ON OFF p ON OFF ON OFF DS 18 1 2 3 4 5 6 7 1 7 1 OFF ON h m d d p 4 p d h m DS 18 1 2 3 4 5 6 7 1 7 1 OFF ON ON OFF m...

Page 52: ...DA FILTER FILTER FINESSE 24 12 09 16 230V 10 50Hz 7VA 10 A 250V cos n 1 2 A 250V cos n 0 6 quartz 4 6 4 ON OFF 6 ON OFF 1 2 1 20 24 10 40 IP 20 En60529 73 23 EEC 89 336 EEC EMC...

Page 53: ...FINESSE 99 1 2 3 4 CONTROL DA DM DA DM SM 5 6 7 8 DA DA 12 09 17 SM CONTROL DM DA CLICK OOO 2VV...

Page 54: ...SM DM DA CONTROL SLAVE DM DA 50 50 SM DA 12 09 18...

Page 55: ...PE DK2 DK1 230V max 10 A OFF ON A B C D VCS x 10S V W 3 x 0 5 3 x 0 5 3 x 0 5 3 x 0 75 VCS x 15S V W 3 x 0 5 3 x 0 5 3 x 0 5 3 x 1 5 VCS x 20S V W 3 x 0 5 3 x 0 5 3 x 0 75 3 x 2 5 VCS x 10E 5 x 2 5 5...

Reviews: