background image

 

Assemble main RO system 

7.   Remove all packaging and plastic wrapping/seals from filters. 

Do 

not include the membrane(s) in this step.

  

Connect housings to RO system by hand and then use spanner 
provided to completely tighten. From right to left (closest to inlet):  

Sediment 5-micron pre-filter in - 1

st

 stage housing 

Granular activated carbon (GAC) filter 

– 2

nd

 stage housing 

Carbon block filter in 

– 3

rd

 stage housing  

Connect system 

Determine length of tubing needed between RO system and mains 
water supply and remove red stopper on unit. Connect tubing from 
cold water supply, drain clamp and water outlet to RO system by 
removing the coloured stoppers and inserting tubing into the 
connections listed below:  

Mark 1 (WHITE stopper) 

– Cold water supply to RO system 

Mark 2 (BLACK stopper) 

– Wastewater to drain 

Mark 3 (YELLOW stopper) 

– Do not remove unless you are 

connecting to a pressurised storage tank. 
Mark 4 (BLUE stopper) 

– Last stage on RO system to water outlet.  

 
Check all tubing is secure by pulling back on tubing, remembering to 
always remove collet clips before inserting tubing.  

System Flushing 

–  

It is very important to flush the RO system through in 2 stages to protect 
the membrane(s) and to ensure optimum performance for your unit.  

Flushing the unit releases any carbon fines, dust, air etc from the pre 
and post filters which may have been present at the manufacturing 
process.  

By flushing the unit in 2 stages this stops the membrane from getting 
clogged or a reduction in flow as the pre and post filters have already 
been flushed.  

 

 

Summary of Contents for RO400-E2

Page 1: ...01704 807600 www finerfilters co uk enquiries finerfilters co uk Reverse Osmosis System Installation and Maintenance Manual For System RO400 E2...

Page 2: ...1 Contents 1 General Information Page 2 2 Unit Information Page 3 3 Preparation Page 4 4 Installation Page 5 5 Maintenance Page 10 6 Replacement Filters Page 11 7 Troubleshooting Page 13...

Page 3: ...f foreign particles colloid organic substances heavy metals soluble solids bacteria viruses pyrogen nitrate microorganisms hormones fluoride and other harmful impurities It only retains water molecule...

Page 4: ...2 Inlet water temperature 4 42 C 4 Pre treatment filters total water output 1000L 5 Water supply tap or ground water TDS 1000ppm 6 Operating bar pressure 3 Bar 45PSI or more Optimal pressure to recei...

Page 5: ...cut to length through each stage of installation The inlet to the unit is the larger pipe which is 3 8 size and the smaller is the output tubing which is size Mark 1 WHITE stopper Cold water supply to...

Page 6: ...TRAIGHT WITH NO JAGGED EDGES Fitting type 1 Quick Connect QC fitting How to connect See Fig 3 Remove collet clip insert tubing into fitting until it locks Gently pull tubing back to ensure fit is secu...

Page 7: ...ll prefer to gather the water directly into a clean bucket 1 Determine location for tap cut tubing to length see fig 1 and 2 and install tap using the diagram below or using white fitting provided Dia...

Page 8: ...bit drill a 1 8 hole into one side of the drainpipe Then to enlarge the hole use a drill bit 4 Taking the side of the drain clamp with the QC fitting stick the self adhesive sponge provided to the in...

Page 9: ...bing into the connections listed below Mark 1 WHITE stopper Cold water supply to RO system Mark 2 BLACK stopper Wastewater to drain Mark 3 YELLOW stopper Do not remove unless you are connecting to a p...

Page 10: ...and check the fitting tubing where the leak was found Also see our troubleshooting section at the back of the manual Once the issue is resolved start process again Turn off the mains water by the isol...

Page 11: ...arly can also prolong the life of your RO system The table below shows how often it is recommended to replace each filter stage in your system This is dependent upon water quality water hardness parti...

Page 12: ...sed through our website www finerfilters co uk or call us on 01704 807600 Replacing your filters Filters only not membrane Please have some towels and cloths ready as some water will escape from the u...

Page 13: ...rom the packaging and screw the fittings back in place Ensure the filter is the correct way by the flow arrow Put filter back in place and re insert the tubing and collet clip and pull back to ensure...

Page 14: ...ush valve is closed Slow flow 1 Pre or post filter clogged 2 Low Water Pressure 3 Clogged Membrane 1 Check replace pre or post filter 2 Booster Pump required 3 Open L1 flush valve and carry out system...

Page 15: ...sure O ring is in groove and lubricated Membrane housing see insert membrane on pg 10 Cloudy milky water 1 Defective membrane 2 New filters or membrane 1 Replace if TDS reading is below 85 2 Flush sys...

Reviews: