Translation of the original instructions MFS-05 

Δp, Filtration Group GmbH, 16.01.18, Mat. No. 70303409, Version 03 

 

  Valve alarm: Red 

  Alarm threshold: Red 

Electrical 
connection

 

  Screw-type terminal strips 

2.5 mm² 

  Valve connections 1.0 mm² 

Ambient 
temperature

 

0 ... 50°C 

Climatic 
category

 

KWF acc. to DIN 40040 

(≤ 75% relative humidity, no 
condensation allowed) 

Design

 

  Dust-tight Makrolon casing 

(Ex II 3D T60°C IP65) 

  175 x 175 x 100 mm (W x H x D) 

 

Mains power supply

 

230 V AC, 

50-60 Hz 

24 V DC 

Tolerance

 

±

 10% 

±

 10% 

Mains fuse

 

0.315 A time-

lag 

3.15 A time-

lag 

Power consumption

 

30 W 

42 W 

 

Transport and storage 

Transport  

  Always transport in the original packaging 

  Avoid vibrations 

 

Storage 

  Always store in the original packaging 

  The unit must be stored in a dry room at 0 … 70°C 

  Avoid vibrations 

  Avoid direct UV radiation (sunlight) 

 

  

 

 

Functions 

9.1 

Operating modes 

The controller can operate in three different modes. The 
mode is selected by altering the assignment of terminal  
16-18 and the setting of the “XS1” jumper. 
 

9.1.1  Interval time control 

If “interval time control” mode is selected, the controller is 
permanently active. The interval time varies as a function 
of 

p. 

 

Factory settings: 

  Terminal 16-17 not assigned 

  Terminal 18-19 jumpered 

  XS1 jumper Schw./Reg. switch up 

  XS1 jumper T/G Cycle switch up 

 

 

 

 

Fig. 11:  Jumper settings for interval time control 

 

Valve activation is controlled by a ∆p-dependent interval 
time.  

 

The interval duration is determined by Δp and the 
selected controller characteristic. 

 

Possible controller characteristics: 

 

0

4

8

12

16

20

24

28

32

36

40 mbar

2

aus

ein

 

 

Fig. 12:  Controller characteristics 

Example:  

The filter must be cleaned at a differential pressure 
equivalent to 30% of the differential pressure measuring 
range (= 12 mbar) with an interval time of approximately  
70 s.  
 
To select the characteristic:  

  Find and plot the 30% line. 

  Find and plot the 70 s line. 

  The point of intersection is located on characteristic 60. 

  Set the “interval” potentiometer to 60 s. 

Summary of Contents for MFS-05

Page 1: ...Translation of the original instructions Filter controller MFS 05 p Material No of Instruction Manual 70303409...

Page 2: ...l mode 18 20 Declaration of incorporation 19 21 Declaration of conformity 20 22 Index 24 2 General safety instructions 2 1 Safety instructions for installation and operating personnel This Instruction...

Page 3: ...lled pulsing Pulsing is activated at fixed time intervals Switching threshold Preset differential pressure that must not be exceeded or at which a defined action such as activation of a valve must tak...

Page 4: ...ontroller has three relays for operating fault signals cleaning signals and alarm threshold exceeded 6 Main components 0 1 0 3 0 6 1 0 1 5 1 5 2 0 2 5 3 0 5 20 50 1 0 0 2 0 0 35 0 5 0 0 1 2 3 4 5 6 7...

Page 5: ...on the motherboard On the P module Cleaning cycles 1 10 High threshold 0 40 mbar Alarm threshold 0 40 mbar Fig 5 Controls on the p module Zero The p zero adjusting screw is located to the right of the...

Page 6: ...ment momentary contact signal Pressure measuring lines P1 pressure on dirty side upstream of filter element P1 pressure on clean side downstream of filter element Measuring hose diameter 4 mm Valve ou...

Page 7: ...ee different modes The mode is selected by altering the assignment of terminal 16 18 and the setting of the XS1 jumper 9 1 1 Interval time control If interval time control mode is selected the control...

Page 8: ...t threshold is exceeded Factory settings Terminal 16 17 not assigned Terminal 18 19 jumpered Jumper 3 down Full cycle optional XS1 jumper T G Cycle switch up A full cycle is executed if the switching...

Page 9: ...ntact terminals 18 and 20 A cleaning process starts with an interval time of 8 s 9 2 3 Fault acknowledgement If a fault occurs the red fault LED lights up Find the fault Rectify the fault Acknowledge...

Page 10: ...from interference fields The electrical connection should correspond to the connection terminal diagrams for the unit concerned All electrical wiring should be laid in accordance with the relevant EM...

Page 11: ...ler in time control mode terminals 16 17 and 18 19 jumpered 13 2 Troubleshooting table Fault Possible cause Remedy Green operation LED not lit Power supply faulty Test the voltage Fuse F1 defective Re...

Page 12: ...out at workplaces that are protected against electrostatic discharge During retrofitting If the unit is tampered with during the warranty period all warranty claims are rendered invalid Switch off the...

Page 13: ...Page 13 Translation of the original instructions MFS 05 p Filtration Group GmbH 16 01 18 Mat No 70303409 Version 03 15 Appendix Connection variants 15 1 Interval time and switching threshold control...

Page 14: ...58 59 60 61 62 63 64 65 37 38 39 40 41 66 67 68 69 70 B RS 485 PE 24 V DC 230 V DC Valve extension A Lag Discharge p Alert 25 mA Start GND DP In Release Stop Post cleaning 0 4 20 mA Output Rapid clean...

Page 15: ...67 hex 0 1020 Not possible see program version Pulse D 68 hex 0 1020 x div 4 div 44 2 100 1000 s Interval potentiometer E 69 hex 0 1020 x div 4 div 64 10 2 s Valves F 70 hex 0 1020 x 46 92 0 5 Post c...

Page 16: ...kinks No condensate must be allowed to accumulate on the instrument lines Provide a condensate trap if necessary No dust protection is necessary for the cleaned gas line Leaking or dirty lines can lea...

Page 17: ...17 Translation of the original instructions MFS 05 p Filtration Group GmbH 16 01 18 Mat No 70303409 Version 03 18 Appendix Dimension drawing MFS 05 p Fig 24 Connection diagram for optional pressure sw...

Page 18: ...reshold 18 mbar Terminal assignment See circuit diagram Jumper 18 19 Jumper settings Schw Reg jumper Up T G Cycle jumper Up 19 2 Other operating modes 19 2 1 Switching threshold mode Parameter Comment...

Page 19: ...Page 19 Translation of the original instructions MFS 05 p Filtration Group GmbH 16 01 18 Mat No 70303409 Version 03 20 Declaration of incorporation As defined by the EC Machinery Directive...

Page 20: ...Page 20 Translation of the original instructions MFS 05 p Filtration Group GmbH 16 01 18 Mat No 70303409 Version 03 21 Declaration of conformity...

Page 21: ...Page 21 Translation of the original instructions MFS 05 p Filtration Group GmbH 16 01 18 Mat No 70303409 Version 03...

Page 22: ...Page 22 Translation of the original instructions MFS 05 p Filtration Group GmbH 16 01 18 Mat No 70303409 Version 03...

Page 23: ...Page 23 Translation of the original instructions MFS 05 p Filtration Group GmbH 16 01 18 Mat No 70303409 Version 03...

Page 24: ...E Emergency shut down 10 Environmental protection 3 F Full cycle 8 16 I Installation 10 Installation work 10 Interval time 4 5 6 7 8 9 13 16 19 J Jumper 5 7 8 11 19 L Leakage 2 M Main components 4 Man...

Page 25: ...Filtration Group GmbH Schleifbachweg 45 D 74613 hringen Phone 49 7941 6466 0 Fax 49 7941 6466 429 fm de sales filtrationgroup com www filtrationgroup com 70303409 I03 01 2018...

Reviews: